Setting the Baud Rate of Serial Ports
2.7.2 CRT Serial Port
The default setting for the serial EIA-232 CRT port is "disabled". To enable the EIA-232 CRT port
at 9600 baud, follow the steps below.
NOTE: The serial EIA-232 CRT port can only be enabled in standalone (non-networked)
applications. The only baud rate supported is 9600.
1.
From the SYSTEM NORMAL screen, press the
screen, as shown below:
2.
Press the 1 key. The control panel displays the Enter Password screen, as shown below:
3.
Enter CRT96 and press
will disappear when you press
4.
Press
5.
To switch back to the default network mode (no CRT) repeat steps 1, 2, and 3 entering
NOCRT.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
1 = P R O G R A M M I N G
( E S C A P E T O A B O R T )
ENTER PROG OR STAT PASSWORD, THEN ENTER.
_
(ESCAPE TO ABORT)
. The five asterisks that appear when you type in the code
twice to return to the "SYSTEM NORMAL" screen.