How to Program a Releasing Zone
REL AUDIBLE
NOTE: An output with a
Zone selection (R0-R9); An output circuit mapped to the same Releasing Zone; Switch Inhibit
selected.
The following contains information needed to program a Release Audible circuit for an output
circuit (control module or NAC)
Description
An output circuit programmed to activate an audio or visual device when all releasing outputs,
programmed to the same Releasing Zone, turn on. You can also program multiple outputs with the
REL AUDIBLE
outputs with the
Programming
1.
Select a control module or NAC (refer to "Modify or Delete a Point (2=point)" on page 19) to
use as a Releasing Circuit.
2.
Select the
shown).
3.
Select the Releasing Zone (R0-R9) for your releasing application.
4.
Press the
screen.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Type Code
Type Code requires the following selections: A Releasing
REL AUDIBLE
.
Type Code to the same Releasing Zone. When the Releasing Zone activates, all
Type Code activate at the same time.
REL AUDIBLE
Type Code, as shown in the following example (control module
REL AUDIBLE
P R O G R M R E L A U D I B L E
Releasing Zone
selection (R5 shown)
Switch Inhibit: I = selected
key to save, then press the
ENTER
Type Code selection:
REL AUDIBLE
M O D U L E A D D R 2 M 1 0 8
R 5 _ _ _ _ _ _ _ _
key two times to return to the Program Change
ESC
Releasing Applications
I * *
2 M 1 0 8
Walk Test
Selection: * = off
Silenceable: * = off
87