Programming
1.
Use the Clear option to clear program information from memory. For instructions on clearing
memory, refer to "How to Clear Memory (0=
NOTE: Once Step 1 is completed, Step 2 will cause the panel to assess whether a loop is
comprised of all FlashScan devices or not. If they are all FlashScan, autoprogramming will
change the loop setting to FlashScan if it was not already at that setting. If the devices are not all
FlashScan, autoprogramming will not make a change to the default setting of CLIP. (See
"FlashScan Poll" on page 49 for FlashScan settings.)
2.
From the "Basic Program" screen, press the 1 key to start Autoprogram. While the control
panel scans the system to identify all SLC devices and NACs, it displays the following screen:
When the autoprogram is finished identifying SLC devices and NACs, it displays a summary
screen that gives a count of all the devices it has located. Refer to the following screen for an
example of this display.
SB represents detectors with B200 series sounder bases. Refer to VeriFire Tools for B200 sounder
base programming.
3.
Press
following screen displays briefly, followed by the
To edit the autoprogramming default values for a point, refer to "How to Modify or Delete a Point
(2=
POINT
To edit the autoprogram default values assigned to all modules and detectors during
autoprogramming, refer to "Change Autoprogram Default Values" on page 18.
Add a Device to the Program
You can also use the Autoprogram option to add addressable devices to the control panel program.
NOTE: When using the Autoprogram option with an existing program, the control panel does not
change program information for installed and programmed devices. However, it will assess
whether a loop contains all FlashScan devices and change the loop setting to FlashScan if
necessary.
The following steps describe how to add a new detector at SLC address 1D147 with 10 detectors in
the existing program:
1.
Physically install the addressable detector to SLC 1 at address 147 (for instructions, refer to the
NF2S-640 Installation Manual and the installation document that comes with the detector).
2.
From the "Basic Program" screen, press the 1 key to start Autoprogram. The Autoprogram
Prompt screen appears in the LCD display as the control panel identifies addressable devices.
When finished identifying addressable devices, the control panel displays information for the
new detector at SLC address 1D147 on the LCD display as shown below:
16
A U T O P R O G R A M
L 1 : 0 1 0 D e t s , 1 5 9 M o d s L 2 : 1 5 9 D e t s , 1 5 9 M o d s
S B L 1 : 0 0 0 , L 2 : 1 5 9
. All devices are automatically accepted during initial autoprogramming. The
ENTER
A C C E P T A L L D E V I C E S
)" on page page 19.
P R O G R M S M O K E ( P H O T O ) D E T E C T O R A D D R 1 D 1 4 7
)" on page page 15.
CLR
P L E A S E W A I T
B e l l s : 0 4
SYSTEM NORMAL
P l e a s e W a i t ! ! !
0 3 _ _ _ _ _ _ _ _ A 8 P 8 * * 1 D 1 4 7
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14