3.1 Overview

Status Change provides a second programming level - accessed by an assigned password - for
changing operating parameters. (These operating parameters do not affect control program
settings.) For example, the Status Change password lets you change settings such as detector
sensitivity and system time and date.
NOTE: Assign the Status Change password to persons who do not have access to Level 1
programming options.
Status Change Options are described below.
Option 1=DISABL - The Disable/Enable option lets you disable programmed points for detectors,
modules, zones and NACs. For details, refer to "Disable or Enable a Point" on page 53.
Option 2=SENSITIV - The Detector Sensitivity option lets you change the Alarm and Pre-alarm
(sensitivity) level for an installed detector. For details, refer to "Changing Detector Sensitivity" on
page 54.
Option 3=CLR VER - The Clear Verification screen lets you clear all counters for detectors
selected for Alarm Verification. For details, refer to "Clearing Alarm Verification Counters" on
page 55.
Option 4=CLR HIST - The Clear History screen lets you clear the entire History buffer from
memory. For details, refer to "Clearing the History Buffer" on page 55.
Option 5=TIME - The Time/Date option lets you set the time and date for the system clock. For
details, refer to "Setting the System Time and Date" on page 55.
Option 6=WALK TEST - The Walk Test option lets you test the entire fire alarm system while
away from the control panel. For details, refer to "Walk Test" on page 56".

3.2 How to Enter Status Change

To enter Status Change, follow these steps:
1.
From the SYSTEM NORMAL" screen, press the
"Entry" screen, as shown below:
2.
From the "Entry" screen, press the 1 key. The control panel displays the "Enter Password"
screen as shown below:
3.
Enter your Status Change password (See "How to Enter a Password", page page 11). The
control panel displays the "Status Change Selection" screen, as shown below:
4.
Select a Status Change selection: 1,2,3,4,5, or 6.
52

Section 3: Status Change

1 = P R O G R A M M I N G
E N T E R P R O G O R S T A T P A S S W O R D , T H E N E N T E R .
S T A T U S C H A N G E P R E S S : 1 = D I S A B L 2 = S E N S I T I V
3 = C L R V E R 4 = C L R H I S T 5 = T I M E 6 = W A L K T E S T
key. The control panel displays the
ENTER
2 = R E A D S T A T U S E N T R Y
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14