Basic Program
• Map the panel zones to the desired annunciator point. Refer to the FirstCommand or
FireVoice NFV-25/50ZS manual for more information, including dipswitch settings.
Panel Programming
If VeriFire Tools is not used and Group M is programmed at the panel, Zone 00 (general alarm) will
be mapped to A1p11 and A1p40. A general alarm will play message 1 and activate an all-call on
the FirstCommand or FireVoice. VeriFire Tools must be used for speaker circuit and message
control.
ACS Selection Group N
This group is the same as Group A (See Table 2.14 on page 35), with the following exceptions:
• It should be selected only for TM-4s used for remote station communication.
• Selection Group N follows the alarm relay for annunciation (Selection Group A annunciates
immediately).
• The yellow LED of annunciator point 2 is for Alarm Silence only (in Selection Group A it is
for Signal Silenced).
ACS Selection Group O
This group is the same as Group A (See Table 2.14 on page 35), with the following exceptions:
• It should be selected for only for TM-4s used as Fire Municipal Box Trip outputs.
• Selection Group O provides a "Master Box" trouble displayed at the panel.
• Selection Group O follows the alarm relay for annunciation (Selection Group A annunciates
immediately).
The yellow LED of annunciator point 2 is for Alarm Silence only (in Selection Group A it is for
Signal Silenced).
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Table 2.26 Point Definitions for Group M
Annunciator Point Type
1 - 9
Unused
10
Message 0 (No Message/Message Off)
11
Message 1
12
Message 2
13
Message 3
14
Message 4
15
Message 5
16 - 39
FFT Circuits
40
All-Call
41 - 64
Speaker Circuits 1 - 24