A.2.4 Programming a Soak Timer
The Soak Timer specifies the length of time (0001 to 9999 seconds, or 0000 for not used) to dump
releasing agents when a Releasing Zone activates. When the Soak Timer expires, the control panel
automatically shuts off the releasing solenoids for the active Releasing Zone. To program a Soak
Timer for a Releasing Zone, follow these instructions:
Press
changing. To change another field on the screen, move the cursor into position by pressing the
arrow keys on the keypad.
A Soak Timer value of 600 seconds is shown below:
72
at this point to save the Cross Zone value if no other fields on the screen are
To Program
Do this
Soak Timer
Type a seconds value of 0000 (no soak timer) to 9999 from the
numeric keys on the keypad in the SOK= field.
at this point to save the Soak Timer value if no other fields on the screen are
P R G R E L E A S E F U N C T I O N R E L E A S E C O N T R O L
D E L A Y = 0 0 A B O R T = U L I C R O S S = N S O K = 0 6 0 0
How to Program a Releasing Zone
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14