Operating Menus Independent of Measured Variables

9.5 Setting the Interference Variable

pause / feedfwd:
setting
?
Fig. 59: Interference variable
The DULCOMETER
®
ference variable. This interference variable affects the actuating variable calculated by the
DULCOMETER
D1Cb as a function of this external signal.
®
Depending of the nature of the effect on the actuating variable, it is referred to either as a
n
multiplicative interference variable or an
n
additive interference variable
The interference variables input can process digital signals up to 500 Hz.
When "commissioning", the zero point signal of the flow gauge has to be checked without flow (must
be ≥ 0).
Setting values of the actuating variable
Factory setting Increment
Interference
10 Hz
variable
nominal
value
* Values below 1 Hz are treated as "Pause". To remove the Pause status, the frequency has to
exceed 2 Hz (hysteresis function)
106
pause / feedfwd:
function
feedforward ctrl
pause / feedfwd:
function
pause
D1Cb can, for example, process a signal of a flow measurement as an inter‐
1
feedforward ctrl
rated value:
10.00 Hz
multiplicative
Possible values
Lower value
Upper value
2* Hz
500 Hz
feedforward ctrl
disturb. variable
additive
feedforward ctrl
max. additive
regulated value
100 %
A0030_GB
Remarks
Depending on signal
type