Operating Menus Independent of Measured Variables
In the "Change measured variable" setting range, it is possible to select the measured variable required
for the respective process and suitable for the sensor or measuring device. Depending on the meas‐
ured variable, different setting windows have to be completed, which are provided by the
DULCOMETER
D1Cb software. The values are set, selected and confirmed using keys
®
and
.
9.7.2
Sub-Functions of the "General
Settings" Menu
The following sub-functions can be found in the
"General Settings" menu item.
9.7.2.1 Operating Menu
In the "Operating Menu" menu item, the
language in which the operating menu is
displayed can be selected and it is also possible
to select between a "reduced" and "complete"
operating menu.
9.7.2.2 Calibration Timer
The calibration timer reminds the user of a
routinely necessary calibration. The calibration
timer is activated by inputting a number of
days. Recalibration is necessary at the end of
this period.
The calibration timer serves to remind the device
operator that the connected sensors need to be
recalibrated. The time is thus not based directly
on the state of the sensors but on the expiry of a
period of time set by the operator. If the calibra‐
tion timer is enabled, an interval of between 1 and
100 days can be entered. If the calibration timer
is activated and if the menu is called up again,
the remaining period of time until the timer runs
out is shown by way of information. A remaining
time of less than one day is shown in "hours".
Resetting the timer: The calibration timer is auto‐
matically reset to its initial value following a
successful calibration. Any possible display
message disappears.
110
"Snooze" mode: If the calibration timer has
expired, the message on the display can be
acknowledged for a period of 15 minutes by
pressing the
button. The message "Calibra‐
tion timer" will reappear. The
pressed for as long as the "Calibration timer"
message is visible. If another message is shown
alternately, it is necessary to wait until the "Cali‐
bration timer" message reappears. Any fault
messages have priority.
9.7.2.3 Washing Timer
The washing timer serves to remind the operator
of the DULCOMETER
sensors require cleaning. The time is thus not
based directly on the state of the sensors but on
the expiry of a period of time set by the oper‐
ator.
The "Washing timer" entry can be found in the
system menu. The washing timer can be enabled
and disabled in this menu. If the washing timer is
enabled, an interval of between 1 and 100 days
can be entered. If the washing timer is enabled
and if the menu is called up again, the remaining
period of time until the timer runs out is shown for
information. A remaining time of less than one
day is shown in "hours".
Resetting the timer: once the washing timer
period has expired, it can be reset in the associ‐
ated menu.
,
key has to be
®
D1Cb that the connected
,