9 SERVICING
A system failure indicates a failure of a power system input or that the relay has been disabled by a user command. It is
indicated by the closing of the non-critical alarm contact, by a red LED, or by the closing of the critical alarm contact. How-
ever, no LCD display is provided until the Information Status command is invoked.
Turn off and reapply the dc input power. The non-critical alarm contact is closed if the failure still exists. Use the Information
Status command to determine the cause of the trouble.
e) FAILURE MESSAGES: 960 CPU BOARD
FAIL-FLASH MEMORY
FAIL-STATIC RAM
FAIL-STATIC RAM CRC
FAIL-DPRAM 960 ACCESS
FAIL-I960 INTRPT CONTROLLER
FAIL-CPU TIMER
FAIL-CPU EEPROM
FAIL-CPU CAPRAM
FAIL-CPU RTC
FAIL-CPU WATCHDOG TIMER
FAIL-S/W PROT CONSTANTS
FAIL-S/W CONFG. LOGIC
FAIL-CONFIG S/W VERSION ERROR
FAIL-CPU SYSTEM IN RESET
FAIL-CPU SYSTEM SHUTDOWN
f) FAILURE MESSAGES: MAGNETICS MODULE
FAIL-MAG SEEPROM
g) FAILURE MESSAGES: COMMUNICATIONS WARNINGS
FRONT PORT LOGIN FAILURE
REAR PORT #1 LOGIN FAILURE
REAR PORT #2 LOGIN FAILURE
WARN-FRONT PORT FAIL
h) FAILURE MESSAGES: MISCELLANEOUS FAILURES
CON MONITOR ALARM
UNBALANCED SYS ALARM
FUSE FAILURE
GE Power Management
FAIL-DO FEED BACK
FAIL-LUI LCD DISPLAY
FAIL-IRIGB
FAIL-TRIP CKT #1 CONTINUITY ERROR
FAIL-TRIP CKT #2 CONTINUITY ERROR
FAIL-TRIP CKT #3 CONTINUITY ERROR
FAIL-TRIP CKT #4 CONTINUITY ERROR
FAIL-TRIP CKT #5 CONTINUITY ERROR*
FAIL-TRIP CKT #6 CONTINUITY ERROR*
FAIL-CONFIG H/W MISMATCH
FAIL-NO DMA INTERRUPT
FAIL-RUNTIME SETTINGS AREA
FAIL-EEP CONTENTS ERROR
STAT-DO DISABLED HARDWARE
WARN-REAR PORT #1 FAIL
WARN-REAR PORT #2 FAIL
WARN-REAR PORT 1 ABSENT
WARN-REAR PORT 2 ABSENT
TRIP BUS CHK FAIL
TIME STROBE FAIL
ALPS Advanced Line Protection System
9.2 TROUBLESHOOTING

9.2.7 SERVICE SYSTEM STATUS FAILURES