B.2 REGISTER MAPS
Table B–4: MODBUS MEMORY MAP (Sheet 10 of 10)
ALPS
CONTENTS
REGISTER
3410
A7
3411
A8
3412
A9
B
3413
A10
3414
A11
3415
A12
3416
C1
3417
C2
3418
KT1
3419
KT2
3420
KT3
3421
KT4
3422
CONFTRIP
3423
CONFOSC
3424
Reserved
3499
Reserved
SETTINGS REGISTERS GROUP 2
3500
Settings address equivalent to SETTINGS REGISTERS GROUP 1 plus 300. See registers 3200 to 3499 for details of the
individual registers.
3799
SETTINGS REGISTERS GROUP 3
3800
Settings address equivalent to SETTINGS REGISTERS GROUP 1 plus 600. See registers 3200 to 3499 for details of the
individual registers
4099
SETTINGS REGISTERS GROUP 4
4100
Settings address equivalent to SETTINGS REGISTERS GROUP 1 plus 900. See registers 3200 to 3499 for details of the
individual registers
4399
REPORT CONTROL REGISTERS
4400
Report Control Register
1, 2, 3, 4, 5, 6, 7, 8
See page B–14 for footnote explanations.
MEMORY MAP FOOTNOTES:
1.
Valid for single-pole models only.
2.
Valid only when blocking scheme is selected.
3.
Valid only for models with recloser.
4.
Specific to each serial interface.
5.
Valid for models with rear serial port only.
6.
Valid for single-pole and LPS models only.
7.
Valid for models with series compensation only.
8.
Valid for models with positive-sequence overvoltage only.
9.
Valid for three-pole models only
B-14
TYPE
FORMAT
NO. OF
REGS.
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
R/W
Unsigned Int
1
RO
-
-
RO
-
-
RO
-
-
R/W
Integer
1
ALPS Advanced Line Protection System
RANGE
UNITS
1 A
5 A
0 to 256
0 to 256
0 to 256
0 to 256
0 to 256
0 to 256
0 to 256
0 to 256
0 to 256
0 to 256
0 to 256
0 to 256
0 to 40
0 to 256
0 to 40
0 to 256
-
-
-
-
-
-
XXYY , where X=0 (none – default) or 2 (Fault Report);
Y =01 to 36 (fault index, dependent on NUMFLTS setting)
GE Power Management
APPENDIX B
DEFAULT
1 A
5 A
-
38
-
45
-
-
-
-
-
-
-
-
-
52
-
115
-
39
-
40
-
39
-
40
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-