2.5 REFERENCE TABLES
Table 2–13: PROTECTION SETTINGS DATA SHEET (Sheet 1 of 7)
NO.
MNEMONIC
Z1 DISTANCE
101
Z1PHASE
2
102
Z1PHREACH
103
Z1PLEVDET
104
Z1GROUND
105
Z1GRDREACH
106
Z1GRDCHAR
107
Z1SUREACH
108
Z1GROUNDK0
109
Z1GLEVDET
110
Z1BLOCK
Z1GCHARANG
111
Z1RGREACH
112
Z2DISTANCE
201
Z2PHASE
202
Z2PHREACH
203
Z2PCHARANG
204
Z2GROUND
205
Z2GRDCHAR
206
Z2GRDREACH
207
Z2GCHARANG
208
Z2TIMERS
209
Z2P_TIME
210
Z2G_TIME
Z2RGREACH
211
Z3DISTANCE
301
Z3PHASE
302
Z3PHREACH
303
Z3PCHARANG
304
Z3GROUND
305
Z3GRDREACH
306
Z3GCHARANG
307
Z3P_TIME
308
Z3G_TIME
† Setting value QUAD applies to Revision B models only.
‡ Setting applicable to Revision B models only.
^ Setting applicable to Single Phase Tripping models only.
2-66
DESCRIPTION
Z1 Phase Distance
Z1 Phase Reach
Z1 Phase Level Detector (Series
Capacitor Model Only)
Z1 Ground Distance
Z1 Ground Reach
Z1 Ground Characteristic
Z1 Ground Reaction Mho
Supervision Reach
Z1 Ground K0
Z1 Ground Level Detector (Series
Capacitor Model Only)
Blocking Supervision of Z1
Z1 Ground Characteristic Timer
Angle
Z1 Resistive Ground Reach
Z2 Phase Distance
Z2 Phase Reach
Z2 Phase Characteristic Angle
Z2 Ground Distance
Z2 Ground Characteristic
Z2 Ground Reach
Z2 Ground Characteristic Angle
Z2 Timers
Z2 Phase Timer
Z2 Ground Timer
Zone 2 Resistive Ground Reach
Z3 Phase Distance
Z3 Phase Reach
Z3 Phase Characteristic Angle
Z3 Ground Distance
Z3 Ground Reach
Z3 Ground Characteristic Angle
Z3 Phase Timer
Z3 Ground Timer
ALPS Advanced Line Protection System
2 CALCULATION OF SETTINGS

2.5.4 PROTECTION SETTINGS DATA SHEETS

RANGE (5A)
RANGE (1A)
NO, YES
0.01 to 50.0 ohms
0.05 to 250.0 ohms
step 0.01
step 0.05
0.0 to 9.9 p.u. volts step 0.1
NO, YES
0.01 to 50.0 ohms
0.05 to 250.0 ohms
step 0.01
step 0.05
MHO, REACT, QUAD
0.01 to 50.0 ohms
0.05 to 250 ohms
step 0.01
step 0.05
1.0 to 7.0 step 0.01
0.0 to 9.9 p.u. volts step 0.1
NO, YES
80° to 155° step 1
0.01 to 100.00 Ω
0.05 to 500 Ω
step 0.01
step 0.01
NO, YES
0.01 to 50.0 ohms
0.05 to 250.0 ohms
step 0.01
step 0.05
90 to 120° step 5
NO, YES
MHO, GDOC, MHOGDOC, MHO2GDOC,
QUAD
0.01 to 50.0 ohms
0.05 to 250.0 ohms
step 0.01
step 0.05
80 to 155 deg. step 5
NO, YES
0.10 to 3.0 sec. step 0.01
0.10 to 3.0 sec. step 0.01
0.01 to 100.00 Ω
0.05 to 500 Ω
step 0.01
step 0.01
NO, YES
0.01 to 50.0 ohms
0.05 to 250.0 ohms
step 0.01
step 0.05
90 to 120 deg. step 5
NO, YES
0.01 to 50.0 ohms
0.05 to 250.0 ohms
step 0.01
step 0.05
80 to 155 deg. step 5
0.10 to 10.0 sec. step 0.01
0.10 to 10.0 sec. step 0.01
USER
SETTING