1.3 CUSTOM PROGRAMMABILITY
1
All of the output relays in the ALPS, except for the alarm output relays, are user-configurable. However, each ALPS relay is
shipped with Default Output Relay Assignments. These are shown below and in Figure 1–28: ELEMENTARY DIAGRAM
WITH DEFAULT I/O (THREE PHASE TRIPPING) on page 1–50 for the three phase model and Figure 1–27: ELEMEN-
TARY DIAGRAM WITH DEFAULT I/O (SINGLE PHASE TRIPPING) on page 1–49 for the single phase model.
Table 1–5: ALPS DEFAULT OUTPUT CONTACT ASSIGNMENTS: SINGLE PHASE MODEL
RELAY
DESCRIPTION
T1
TRIP BUS PHASE A
T2
TRIP BUS PHASE A
T3
TRIP BUS PHASE A
T4
TRIP BUS PHASE A
T5
TRIP BUS PHASE B
T6
TRIP BUS PHASE C
A1
MANUAL CLOSE BREAKER 1
A2
MANUAL CLOSE BREAKER 2
A3
TRIP BUS PHASE A
A4
TRIP BUS PHASE A
A5
THREE PHASE RECLOSE INITIATE
A6
THREE PHASE RECLOSE INITIATE
A7
RECLOSE CANCEL OUTPUT FROM SCHEME LOGIC
A8 to A12
UNASSIGNED
KT1
KEY TRANSMITTER 1 / CARRIER START #1
KT2
KEY TRANSMITTER 2 / CARRIER STOP #1
KT3
KEY TRANSMITTER 1 / CARRIER START #1
KT4
KEY TRANSMITTER 2 / CARRIER START #2
C1
NON-CRITICAL ALARM
C2
PT FUSE FAILURE ALARM
Table 1–6: ALPS DEFAULT OUTPUT CONTACT ASSIGNMENTS: THREE PHASE MODEL
RELAY
DESCRIPTION
T1
TRIP CIRCUIT #1
T2
TRIP CIRCUIT #2
T3
TRIP CIRCUIT #3
T4
TRIP CIRCUIT #4
A1
MANUAL CLOSE CIRCUIT BREAKER #1
A2
MANUAL CLOSE CIRCUIT BREAKER #2
A3
BREAKER FAILURE INITIATE #1
A4
BREAKER FAILURE INITIATE #2
A5
RECLOSE INITIATE #1
A6
RECL OSE INITIATE #2
A7
RECLOSE CANCEL
A8
RECLOSE CANCEL
KT1
KEY TRANSMITTER 1 / CARRIER START #1
KT2
KEY TRANSMITTER 2 / CARRIER STOP #1
KT3
KEY TRANSMITTER 1 / CARRIER START #1
KT4
KEY TRANSMITTER 2 / CARRIER START #2
C1
NON-CRITICAL ALARM
C2
PT FUSE FAILURE ALARM
1-10
ALPS Advanced Line Protection System
1 PRODUCT DESCRIPTION

1.3.4 CONFIGURABLE OUTPUTS

MNEMONIC
INDEX NO.
TRIPA
33
TRIPA
33
TRIPA
33
TRIPA
33
TRIPB
34
TRIPC
34
MNCLS1
58
MNCLS2
59
TRIPA
33
TRIPA
33
RI-3P
37
RI-3P
37
CANCL
38
---
---
KEY1
39
KEY2
40
KEY1
39
KEY2
40
NCALM
52
FF
115
MNEMONIC
INDEX NO.
TRIPA
33
TRIPA
33
TRIPA
33
TRIPA
33
MNCLS1
58
MNCLS2
59
TRIPA
33
TRIPA
33
RI_3P
37
R1_3P
37
CANCL
38
CANCL
38
KEY1
39
KEY2
40
KEY1
39
KEY2
40
NCALM
52
FF
115
GE Power Management