GE ALPS Instruction Manual page 122

Advanced line protection system
Table of Contents

Advertisement

2.5 REFERENCE TABLES
Table 2–11: PROTECTION SETTINGS GUIDE (Sheet 2 of 7)
NO.
MNEMONIC
Z3RGREACH
310
Z4DISTANCE
401
Z4PHASE
402
Z4PHREACH
2
403
Z4PCHARANG
404
Not Used
405
Z4GRND
406
Z4GRDREACH
407
Z4GCHARANG
408
Z4DIRECTN
409
Z4_TIMERS
410
Z4P_TIME
411
Z4G_TIME
Z4GRDCHAR
412
Z4RGREACH
413
CURVSUPVISN
501
IT_PICKUP
502
IB_PICKUP
503
IPT_PICKUP
504
IPB_PICKUP
505
IPBKFACTOR
506
NT_OFFSET
507
UNBALALARM
OVERCURRNT
601
50
602
50_DIRCNL
603
50PICKUP
604
50PICKUPFF
605
50G
606
50G_DIRCNL
607
50GPICKUP
608
50GPCKPFF
609
50GRESTNT
610
51G
611
51G_DIRCNL
612
51GPICKUP
† Setting value QUAD applies to Revision B models only.
‡ Setting applicable to Revision B models only.
^ Setting applicable to Single Phase Tripping models only.
2-58
DESCRIPTION
Z3 Resistive Ground Reach
Z4 Phase Distance
Z4 Phase Reach
Z4 Phase Characteristic Angle
Z4 Ground Distance
Z4 Ground Reach
Z4 Ground Characteristic Angle
Z4 Direction
Z4 Timers
Z4 Phase Timer
Z4 Ground Timer
Z4 Ground Characteristic
Z4 Resistive Ground Reach
Trip Supervision Current
Block Supervision Current
GDOC Trip Current
GDOC Block Current
IPB I1 Restraint
NT/NB Offset
Unbalanced Current Alarm
Phase Instantaneous Overcurrent
Directional Control of 50
50 Pickup Setting
50 Pickup during fuse failure
Ground Instantaneous
Overcurrent
Directional Control of 50G
50G Pickup Setting
50G Pickup during fuse failure
50G Restraint Setting
Ground Time Overcurrent
Directional Control of 51G
51G Pickup Setting
ALPS Advanced Line Protection System
2 CALCULATION OF SETTINGS
RANGE (5A)
RANGE (1A)
0.01 to 100 ohms
0.05 to 500 ohms
step 0.01
step 0.05
NO, YES
0.01 to 50.0 ohms
0.05 to 250.0 ohms
step 0.01
step 0.05
80 to 120 deg. step 5
NO, YES
0.01 to 50.0 ohms
0.01 to 250.0 ohms
step 0.01
step 0.05
80 to 155 deg., step 5
FORWRD, REVERS
NO, YES
0.10 to 10.0 sec. step 0.01
0.10 to 10.0 sec. step 0.01
MHO, QUAD
0.01 to 100 ohms
0.05 to 500 ohms
step 0.01
step 0.05
0.20 to 4.0 amps
0.04 to 0.8 amps
step 0.01
step 0.01
0.20 to 4.0 amps
0.04 to 0.8 amps
step 0.01
step 0.01
0.50 to 5.0 amps
0.10 to 1.0 amps
step 0.01
step 0.01
0.25 to 3.75 amps
0.05 to 0.75 amps
step 0.01
step 0.01
0.0, 0.066
0.0 to 20.0 ohms
0.0 to 100 ohms
step 0.01
step 0.01
NO, YES
NO, YES
NO, YES
2.0 to 160.0 amps
0.4 to 32.0 amps
step 0.1
step 0.1
2.0 to 160.0 amps
0.4 to 32.0 amps
step 0.1
step 0.1
NO, YES
NO, YES
0.5 to 80.0 amps
0.1 to 16.0 amps
step 0.1
step 0.1
0.5 to 80.0 amps
0.1 to 16.0 amps
step 0.1
step 0.1
0.0, 0.3
NO, YES
NO, YES
0.20 to 15.0 amps
0.04 to 3.0 amps
step 0.01
step 0.01
DEFAULT
18Ω at 5A
90Ω at 1A
YES
18.0Ω at 5A
90.0Ω at 1A
90 deg.
YES
18.0Ω at 5A
90.0Ω at 1A
90 deg.
FORWRD
YES
3.0 sec.
3.0 sec.
MHO
135Ω at 1A
27Ω at 5A
0.20 A at 5A
0.04 A at 1A
0.20 A at 5A
0.04 A at 1A
0.75 A at 5A
0.15 A at 1A
0.25 A at 5A
0.05 A at 1A
0.066
0.05Ω at 5A
0.25Ω at 1A
YES
NO
YES
20.0 A at 5A
4.0A at 1A
30.0 A at 5A
6.0 A at 1A
YES
YES
10.0 A at 5A
2.0 A at 1A
15.0 A at 5A
3.0A at 1A
0.3
YES
YES
1.0 A at 5A
0.2 A at 1A
GE Power Management