Continuous Monitor - GE ALPS Instruction Manual

Advanced line protection system
Table of Contents

Advertisement

1.7 SELF-TEST FEATURES
1
The ALPS relay includes a Continuous Monitor feature in addition to its self test features. The Continuous Monitor is
intended to detect any ALPS tripping units (Zone 2 or Zone 3 distance functions, 50G or 50 overcurrent functions) that are
in the picked up condition without a corresponding operation of the Fault Detector. If such a condition occurs and persists
for 1 second, the ALPS relay will issue a Non-Critical Alarm and log a Continuous Monitor event.
These Continuous Monitor Alarm points are found in Table 2–10: INDEX NUMBERS – SCHEME, RECLOSER, & PRO-
GRAMMABLE LOGIC on page 2–52 . The Index numbers used for the Continuous Monitor are as follows:
48: Trip Circuit alarm
49: ZONE flags on alarm
50: Overcurrent Alarm
51: Unbalanced Current Detector alarm.
They are assigned in the default settings as inputs to the non-critical alarm. These flags may also be used in configurable
logic, or assigned to other alarm contacts if required.
1-22
ALPS Advanced Line Protection System
1 PRODUCT DESCRIPTION

1.7.3 CONTINUOUS MONITOR