Index Numbers - GE ALPS Instruction Manual

Advanced line protection system
Table of Contents

Advertisement

2 CALCULATION OF SETTINGS
2.5 REFERENCE TABLES
Table 2–9: INDEX NUMBERS – CONTACT CONVERTER INPUT ASSIGNMENT
ALPS with Single Phase Tripping
Index
Description
1
Breaker #1 52b Contact Input Phase A
2
Breaker #1 52b Contact Input Phase B
3
Breaker #1 52b Contact Input Phase C
4
Breaker #2 52b Contact Input Phase A
5
Breaker #2 52b Contact Input Phase B
6
Breaker #2 52b Contact Input Phase C
7
Enable Three Phase Tripping
8
Change Setting Group Input (BIT0)
9
Change Setting Group Input (BIT1)
10
External Contact Input to Stop Carrier *
11
External Contact Input to Block Pilot
Tripping *
12
Receiver 1 Input
13
Receiver 2 Input
14
External Reclose Initiate 1 Pole
15
External Reclose Initiate 3 Pole
16
External Reclose Inhibit
17
External Reclose Cancel
18
Reclose Reset
19
External Phase 3 Reclose
20
External Contact Input to Reset ALPS
Trip Target Display
21
Spare
22
External Contact Input to Disable
Outputs
23
External Contact Input to Trigger
Oscillography Capture
24
Manual Lockout
25
CONFIGURABLE INPUT1
26
CONFIGURABLE INPUT2
27
CONFIGURABLE INPUT3
28
CONFIGURABLE INPUT4
29
CONFIGURABLE INPUT5
30
CONFIGURABLE INPUT6
31
CONFIGURABLE INPUT7
32
CONFIGURABLE INPUT8
NOTE:
Any of the above signals (1 to 32) may be assigned to the 8 available ALPS Contact Converter Inputs (CC1 to CC8). Those 8
signals will also be available for use for the Programmable Outputs and/or the Configurable Logic. Unassigned signals will
NOT be available.
NOTE:
Contacts are normally open; add 1000 to number to close contact under normal conditions.
* Applies to Blocking Scheme Only
GE Power Management
ALPS with Three Phase Tripping
Mnemonic
Index
52B_1A
1
52B_1B
2
52B_1C
3
52B_2A
4
52B_2B
5
52B_2C
6
EXTRP3P
7
CGST1
8
CGST2
9
STCR
10
BPLTRP
11
RCVR1
12
RCVR2
13
EXRI1P
14
EXRI3P
15
EXRINH
16
EXRCNL
17
RCLRST
18
CLOS3P
19
RESET
20
21
DISOUT
22
OSCTRG
23
MANLKT
24
CNFDI1
25
CNFDI2
26
CNFDI3
27
CNFDI4
28
CNFDI5
29
CNFDI6
30
CNFDI7
31
CNFDI8
32
ALPS Advanced Line Protection System
2.5 REFERENCE TABLES

2.5.1 INDEX NUMBERS

Description
Breaker #1 52b Contact Input
Spare
Spare
Breaker #2 52b Contact Input
Spare
Spare
Spare
Change Setting Group Input (BIT0)
Change Setting Group Input (BIT1)
External Contact Input to Stop Carrier *
External Contact Input to Block Pilot
Tripping*
Receiver 1 Input
Receiver 2 Input
Spare
External Reclose Initiate 3 Pole
External Reclose Inhibit
External Reclose Cancel
Reclose Reset
Spare
Spare
Spare
External Contact Input to Disable
Outputs
External Contact Input to Trigger
Oscillography Capture
Manual Lockout
CONFIGURABLE INPUT1
CONFIGURABLE INPUT2
CONFIGURABLE INPUT3
CONFIGURABLE INPUT4
CONFIGURABLE INPUT5
CONFIGURABLE INPUT6
CONFIGURABLE INPUT7
CONFIGURABLE INPUT8
Mnemonic
52B_1
2
52B_2
CGST1
CGST2
STCR
BLPTRP
RCVR1
RCVR2
EXRI3P
EXRINH
EXRCNL
RCLRST
DISOUT
OSCTRG
MANLLT
CNFDI1
CNFDI2
CNFDI3
CNFDI4
CNFDI5
CNFDI6
CNFDI7
CNFDI8
2-51

Advertisement

Table of Contents
loading

Table of Contents