Description - GE ALPS Instruction Manual

Advanced line protection system
Table of Contents

Advertisement

B.2 REGISTER MAPS
Table B–5: DATA FORMATS (Sheet 3 of 12)
TYPE
VALUE/
BITMASK
F10
16 bits
bit 0
bit 1
bit 2
B
bit 3
bit 4
bit 5
bits 6 to 11
bit 12
bit 13
bit 14
bit 15
F11
16 bits
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit 10
bit 11
bit 12
bit 13
bit 14
bit 15
F12
Integer
F56
F57
F58
F13
Integer
F59
F56
F57
F58
F14
2 bytes
F18
F17
B-16

DESCRIPTION

SYS_MISCSTAT1
Protection disabled flag
N/A
Continuous monitor alarm error
Unbalanced system detection error
Fuse failure error
Trip bus check error
N/A
Time strobe fail (to be looked into)
Jumper (remote manual trip/close)
Jumper (Remote change settings/
Soft DO enable/disable)
Jumper (keypad enabled/disabled)
SYS_MISCSTAT2 (16 bits)
Group selection through contact
converters
Relay test
Digital output test
Channel test
Playback
MMI passwords enabled/disabled
Logon failure through front port
Logon failure through Rear port#1
Logon failure through Rear port#2
D.O. software disable flag
Comm. access level - low bit
Comm. access level - high bit
Factory Setting access level
Active setting group - low bit
Active setting group - high bit
N/A
Comm Port 1 Settings (xxyz)
Baud Rate (xx)
Parity (y)
Stop Bits (z)
Comm Port 2 Settings (ixxyz)
Interface (i)
Baud Rate (xx)
Parity (y)
Stop Bits (z)
Fault Data
Fault Type (Lower byte)
Trip Type (Upper byte)
ALPS Advanced Line Protection System
Table B–5: DATA FORMATS (Sheet 4 of 12)
TYPE
VALUE/
DESCRIPTION
BITMASK
F17
2 bytes
Trip Types
0
No trip available
1
Z1
2
Z2
3
Z3
4
Z4
5
PLT
6
50G
7
50P
8
51G
9
LPU
10
REM
11
WI
12
OSC
13
SZ1
14
SZ2
15
SP1
16
SWI
17
CTB
255
Undefined
F18
2 bytes
Fault Types
1
AG_-phase A to Ground
2
BG_-phase B to Ground
3
CG_-phase C to Ground
4
ABG-phase A to phase B to Ground
5
BCG-phase B to phase C to Ground
6
CAG-phase C to phase A to Ground
7
AB_-phase A to phase B
8
BC_-phase B to phase C
9
CA_-phase C to phase A
10
3PH-phase A to phase B to phase C
255
Undefined
F20
2 bytes
Download Status
0
OK
1
Erasing Flash RAM
2
Communication Error
3
Code CRC Error
4
Flash Write Error
5
Flash Erase Error
6
Incorrect Application Error
7
Incorrect Size
8
Computing application code CRC
APPENDIX B
GE Power Management

Advertisement

Table of Contents
loading

Table of Contents