6 FUNCTIONAL TESTS (USER SETTINGS)
1.
Setting:
OVERCURRNT
(610)
51G = YES
(611)
51G_DIRCNL = NO
(612)
51GPICKUP = [_________] amps,
(615)
51GTIMDIAL =
(614)
51GCURVE = [________] Curve,
51G is calculated with the equation
×
51G =
3
I
0
where I
is equal to the zero-sequence current. Since I
0
I
/ 3 = I
.
op
0
Substituting Equation 6–17 into Equation 6–16 yields
I
=
51G.
op
Therefore, 51G will pick up when I
Chapter 2: CALCULATION OF SETTINGS.
If the test current exceeds 2 x In ( In is the rated current), then the current test should be applied with a
50% duty cycle. For instance, if current is applied for 5 minutes, it should be left off for 5 minutes
CAUTION
before it is reapplied.
2.
Connect the relay as shown in Figure 5–2: GROUND REACH TIMER TEST CONNECTIONS on page 5–7.
Start the timer when I
NOTE
3.
For this test remove the relay from test mode and assign TOCTRP to A1.
(2007) A1 = index 119, TOCTRP
4.
Apply I
at 2·51G = [________] amps rms and start the timer. Leave the current on until the A1 contact closes, then
op
stop the timer. The time should be within ±7% of the value found on the ALPS time-dial curve in use.
5.
Reduce I
to zero.
op
6.
Repeat steps 4 and 5 for I
7.
Change the setting of 51G_DRCNL (0611) back to YES if directional control of 51G is required.
GE Power Management
[________] Time dial,
(eq. 6–16)
op
(eq. 6–17)
(eq. 6–18)
= 51G. The time it takes for 51G to pick up is determined by the time-dial curve in
op
is applied and stop the timer when the A1 closes (the relay trips).
op
at 6·51G = [________] and 10·51G = [________].
op
ALPS Advanced Line Protection System
6.4 BACKUP PROTECTION TESTS
6.4.3 T11 – GROUND TIME OVERCURRENT 51G
is single-phase, I
is given by
0
6
6-9