2 CALCULATION OF SETTINGS
Table 2–12: GENERAL SETTINGS GUIDE (Sheet 2 of 2)
NO.
MNEMONIC
DESCRIPTION
403
MAX_IXT
Maximum Breaker Duty for a
Breaker
404
IXTPHASEA
Accumulated Breaker Duty,
Phase A
405
IXTPHASEB
Accumulated Breaker Duty,
Phase B
406
IXTPHASEC
Accumulated Breaker Duty,
Phase C
‡
NUM_OP
Present Number of Breaker
407
Operations
†
NUM_OP_A
Present Number of Breaker
407
Operations for Phase A
†
NUM_OP_B
Present Number of Breaker
408
Operations for Phase B
NUM_OP_C
Present Number of Breaker
†
409
Operations for Phase C
INPUTS
501
CC1
Contact Converter 1
502
CC2
Contact Converter 2
503
CC3
Contact Converter 3
504
CC4
Contact Converter 4
505
CC5
Contact Converter 5
506
CC6
Contact Converter 6
507
CC7
Contact Converter 7
508
CC8
Contact Converter 8
509
Contact Converter 9
†
CC9
510
†
Contact Converter 10
CC10
511
Contact Converter 11
†
CC11
512
†
Contact Converter 12
CC12
† Applicable to the Single Phase Tripping model only.
‡ Applicable to the Three Phase Tripping model only.
* Contact converter output normally appears as a Logic 1 with normally open contact connected; to invert output to Logic 0, add 1000 to
the number.
GE Power Management
RANGE
(5A & 1A)
0 to 9999999 A
0 to 9999999 A
0 to 9999999 A
0 to 9999999 A
0 to 9999
0 to 9999
0 to 9999
0 to 9999
0 to 32 *
0 to 32 *
0 to 32 *
0 to 32 *
0 to 32 *
0 to 32 *
0 to 32 *
0 to 32 *
0 to 32 *
0 to 32 *
0 to 32 *
0 to 32 *
ALPS Advanced Line Protection System
2.5 REFERENCE TABLES
STEP
x
100
sec.
x
100
sec.
x
100
sec.
x
100
sec.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
DEFAULT
0
0
0
2
0
0
0
0
0
12
13
10
11
†
7
†
1
†
‡
2
, 4
†
3
†
4
†
5
†
6
2-65