GE ALPS Instruction Manual page 272

Advanced line protection system
Table of Contents

Advertisement

12.1 INTRODUCTION
Table 12–2: ASCII COMMAND LIST (Sheet 1 of 5)
ASCII
COMMAND DESCRIPTION
COMMAND
MNEMONIC
LOGIN
Login to the relay
12
QUIT
Logs out from the relay,
displays the relay status,
and returns the privilege
level to VIEW for the relay
port used.
PASSword
Change the passwords
used by ALPS-Link and
ASCII; MMI passwords are
not affected by this
command
VALues
Display the present values
of voltages, currents, watts,
Vars, etc., including Breaker
Health in the second
screen. Press ENTER to
see the second screen
READings
Display the present values
of voltages, currents, watts,
Vars, etc., and update them
once per second. The ESC
key stops the update. No
Breaker Health is displayed.
FAUlts
Display fault reports. The list
of available faults is
displayed first then a
number is chosen to view a
particular fault
12-2
LOWEST
RELAY PROMPT
LEVEL
PASSWORD
NEEDED
NONE
Unit ID?
Password?
Reports the access level granted or that the
password entered is INVALID
VIEW
Press ENTER to continue
Do you want to logout?
You have logged out from the relay
Level equal to
Enter Current Password
the password
Enter New Password
being
Re-enter New Password
changed
Password changed or INVALID; password not
changed
Present Values
VA rms: V
VB rms: V
VC rms: V
VA: V degs
VB: V degs
VC: V degs
VIEW
Watts: KW
P ow er Factor
S etting G roup N um ber:1
Breaker 1: Closed
Breaker Health
Phase A accumulated
Amps: 45.2 A
Phase B accumulated
Amps: 11.1 A
Phase C accumulated
Amps: 25.7A
VIEW
FLTNO DATE TIME TRIP
1
07/09/98
15:32:23.6833
Enter Fault Number (press ESC to quit): 1
Report for Fault No: 1
TRIP DATE: 07/03/98
TRIP TIME: 16.32.23.6833
Trip Type(s): Z1
Fault Type: ABG
Relay Operating Time: 488 ms
Breaker Operating Time: 1152 ms
Distance: 9999 miles
ITEM
Prefault Current (A)
Fault Current (A)
Fault Voltage (kV)
Press ENTER to Continue
List of Fault Events:
TIME
16:32:23.7025
16:32:23.7041
Press Y to get oscillography data
Press ESC to quit
Press Any Key to continue
ALPS Advanced Line Protection System
12 ASCII COMMUNICATIONS
IA rms: A
IB rms: A
IC rms: A
In rms: A
IA: A degs
IB: A degs
IC: A degs
In: A degs
Vars: kVar
Frequency: Hz
No. of Breakers: 2
Breaker 2: N/A
Breaker Operations: 129
FAULT DISTANCE
TYPE
TYPE
EXT
AG
0.2mi
A
B
C
D
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
EVENT
Oscillography Capture
RMS Oscillography Data
GE Power Management
USER
RESPONSE
Relay ID number;
up to 10 character
password
Press the enter
key; Y or N
old password;
new password;
new password
None
Press E for
expanded mode,
ESC to end
Two digit number,
1 to 16