12.1 INTRODUCTION
Table 12–2: ASCII COMMAND LIST (Sheet 3 of 5)
ASCII
COMMAND DESCRIPTION
COMMAND
MNEMONIC
MODEL
Retrieve the model number,
serial number, and version
of the relay
12
CRCcalc
Recalculates the CRC of
various settings groups (this
is primarily a
troubleshooting command -
it is used only where a relay
may have gone through a
loss power during a settings
change, and the settings
are corrupted beyond the
ability of the relay to
correct).
STLINID
Allows the station and line
IDs to be changed
RELTest
Selects and runs a given
relay test. Puts the relay in
test mode (Contact A!
Reports test function
operation).
ACCESS
Allows the user to change
privilege level
OSCtrg
Start oscillography
recording
CHNLtest
Test PLC channel. The test
starts when a B is entered
and ends only when an E is
entered.
PLAYBack
Re-run a fault produced
earlier or test case for relay.
There are three choices for
running a fault: 1) re-run a
fault saved in the relay; 2)
with factory test data; 3)
download oscillography into
relay and run fault
LUIPass
Display coded LUI
passwords. See decoding
table in Chapter 8
HELP
Displays the ASCII
command mnemonics as
well as descriptions of each
command
12-4
LOWEST
RELAY PROMPT
LEVEL
PASSWORD
NEEDED
VIEW
MODEL: ALPSDA35U143VE3S
VERSION: V0001.11
SETTINGS
CRCs are recalculated
SETTINGS
Station ID: Current Station ID
Line ID: Current Line ID
Do you want to change Station and/or
Line ID? (Y/N): y
Enter new Station ID (max. 32 characters): NEW
STATION ID
Enter new Line ID (max. 32 characters): NEW
FEEDER ID
Are you sure? (Y/N): y
MASTER
Disable Outputs? (Y/N):
Select the function to be tested (2 to 49)
To stop the test in progress enter I
To see the list of functions enter H
To quit without suspending the test enter Q
To quit press ESC
Enter your choice: 2
Z1 AG test function is routed to contact A!
VIEW
Enter Password:?
VIEW
Are you sure? (Y/N): y
Oscillography is triggered
MASTER
To begin Channel Test enter B, To end Channel Test
enter E
ACTION
To run the relay on Fault Data enter Fault Number
To run the relay on factory test case enter F
To run the relay on downloaded test data enter D
To quit press ESC
Enter your choice: 5
The fault is absent
There is no factory test data in the relay
There is no downloaded data in the relay
VIEW
MMI PASSWORDS
Settings Password: [DHLPPPPPPPPPPPP
Control Password: [AEIPPPPPPPPPPPP
Master Password: [MBFPPPPPPPPPPPP
VIEW
ALPS Advanced Line Protection System
12 ASCII COMMUNICATIONS
USER
RESPONSE
None
None
Y to change, N to
exit; NEW
STATION ID or
ENTER to keep
current ID; NEW
FEEDER ID or
ENTER to keep
current ID; enter
letter
Enter letter Y or
N; one to two digit
number, 1 to 49;
enter letter H or Q
User-defined
password
Enter letter Y or N
Enter letter B or E
Fault number, F,
D, or ESC
None
None