GE ALPS Instruction Manual page 135

Advanced line protection system
Table of Contents

Advertisement

2 CALCULATION OF SETTINGS
Table 2–13: PROTECTION SETTINGS DATA SHEET (Sheet 6 of 7)
NO.
MNEMONIC
1815
HOLD
1816
HOLDTIME
1817
HOLDSENSE
1818
SYNCCHECK
1819
CLOSEANG
1820
SLIPFREQ
1821
BUSLINE
1822
SYNCPHASE
1823
SYNCHOLD
^
SP1DELAY2
1824
SP1DELAY3
^
1825
^
SP1DELAY4
1826
1827
SP3DELAY1
1828
SP3DELAY2
1829
SP3DELAY3
1830
SP3DELAY4
1831
SYNCMANCLS
1832
VBUSLIVE
1833
VBUSDEAD
1834
VLINELIVE
1835
VLINEDEAD
1836
LBUSDLINE
1837
DBUSLLINE
1838
DBUSDLINE
1839
DELTAV
1840
DELTAVBLK
NONCRIT_AL
1901
NCAIN1
1902
NCAIN2
1903
NCAIN3
1904
NCAIN4
1905
NCAIN5
1906
NCAIN6
1907
NCAIN7
1908
NCAIN8
OUTPUTS
2001
T1
2002
T2
† Setting value QUAD applies to Revision B models only.
‡ Setting applicable to Revision B models only.
^ Setting applicable to Single Phase Tripping models only.
GE Power Management
DESCRIPTION
Inhibit Hold Select
Inhibit Hold Time
Contact Input Status
Synch Check Supervision
Closing Angle
Slip Frequency
Bus or Line Voltage
Voltage used by SYNCCHECK
SYNCCHECK Hold Time
Supervise 2nd 3P Reclose after
1P Trip
Supervise 3rd 3P Reclose after 1P
Trip
Supervise 4th 3P Reclose after 1P
Trip
Supervise 1st 3P Reclose after 3P
Trip
Supervise 2nd 3P Reclose after
3P Trip
Supervise 3rd 3P Reclose after 3P
Trip
Supervise 4th 3P Reclose after 3P
Trip
Supervise Manual Close
Live Bus Voltage
Dead Bus Voltage
Live Line Voltage
Dead Line Voltage
Live Bus Dead Line
Dead Bus Live Line
Dead Bus Dead Line
Voltage Difference
Block Synch Check by DELTAV
Non-Critical Alarm Input #1
These 8 inputs are ORed together
and then outputted to the contact
assigned to the Non-Critical Alarm
Non-Critical Alarm Input #2
Non-Critical Alarm Input #3
Non-Critical Alarm Input #4
Non-Critical Alarm Input #5
Non-Critical Alarm Input #6
Non-Critical Alarm Input #7
Non-Critical Alarm Input #8
T1 Contract
T2 Contact
ALPS Advanced Line Protection System
RANGE (5A)
RANGE (1A)
NO, YES
1 to 1000 sec. step 1
CC, CO
NO, YES
0 to 75 deg. step 1
0.1 to 5 Hz step 0.1
BUS, LINE
VA, VB, VC, VAB, VBC, VCA
1 to 100 sec. step 1
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
0.1 to 130 volts step 0.1
0.1 to 130 volts step 0.1
0.1 to 130 volts step 0.1
0.1 to 130 volts step 0.1
NO, YES
NO, YES
NO, YES
0.1 to 30 volts step 0.1
NO, YES
0 to 256 step 1
0 to 256 step 1
0 to 256 step 1
0 to 256 step 1
0 to 256 step 1
0 to 256 step 1
0 to 256 step 1
0 to 256 step 1
0 to 256 step 1
0 to 256 step 1
2.5 REFERENCE TABLES
USER
SETTING
2-71
2

Advertisement

Table of Contents
loading

Table of Contents