Contact Converter Inputs - GE ALPS Instruction Manual

Advanced line protection system
Table of Contents

Advertisement

13.2 XPRESSION BUILDER FLAGS
13.2 XPRESSION BUILDER FLAGS
Table 13–2: CONTACT CONVERTER INPUT FLAGS
INDEX
DESCRIPTION
0
No Assignment to Input
1
Breaker #1 52b Contact Input
4
Breaker #2 52b Contact Input
8
Change Setting Group Input Bit 0
9
Change Setting Group Input Bit 1
10
External Contact Input to Stop Carrier
11
External Contact Input to Block Pilot Tripping
12
Receiver 1 Input
13
13
Receiver 2 Input
15
External Reclose Initiate 3-Pole
16
External Reclose Inhibit
17
External Reclose Cancel
18
Reclose Reset
19
External Manual Close
22
External Contact Input to Disable Outputs
23
External Contact to Trigger Oscillography
24
Manual Lock-Out
25
Configurable Input 1
26
Configurable Input 2
27
Configurable Input 3
28
Configurable Input 4
29
Configurable Input 5
30
Configurable Input 6
31
Configurable Input 7
32
Configurable Input 8
The input flags available for assignment to user defined logic are as follows:
Table 13–3: CONFIGURABLE INPUTS
INDEX
DESCRIPTION
25
Configurable Input 1
26
Configurable Input 2
27
Configurable Input 3
28
Configurable Input 4
29
Configurable Input 5
30
Configurable Input 6
31
Configurable Input 7
32
Configurable Input 8
13-4
ALPS Advanced Line Protection System
13 XPRESSION BUILDER

13.2.1 CONTACT CONVERTER INPUTS

MNEMONIC
NONE
52B_1
52B_2
CGST1
CGST2
STCR
BPLTRP
RCVR1
RCVR2
EXRI3P
EXRINH
EXRCNL
RCLRST
EMNCLS
DISOUT
OSCTRG
MANLKT
CNFDI1
CNFDI2
CNFDI3
CNFDI4
CNFDI5
CNFDI6
CNFDI7
CNFDI8
13.2.2 INPUT/OUTPUT FLAGS
MNEMONIC
CNFDI1
CNFDI2
CNFDI3
CNFDI4
CNFDI5
CNFDI6
CNFDI7
CNFDI8
GE Power Management