GE ALPS Instruction Manual page 311

Advanced line protection system
Table of Contents

Advertisement

APPENDIX B
Table B–5: DATA FORMATS (Sheet 5 of 12)
TYPE
VALUE/
DESCRIPTION
BITMASK
F22
2 bytes
Digital Test Number
0
END OF TEST
1
T1
2
T2
3
T3
4
T4
5
T5 (1-phase tripping model only)
6
T6 (1-phase tripping model only)
7
A1
8
A2
9
A3
10
A4
11
A5
12
A6
13
A7
14
A8
15
A9 (1-phase tripping model only)
16
A10 (1-phase tripping model only)
17
A11 (1-phase tripping model only)
18
A12 (1-phase tripping model only)
19
KT1
20
KT2
21
KT3
22
KT4
23
C1A/C1B
24
C2A/C2B
25
CA-A/B (Critical Alarm)
F26
2 bytes
Output Mode
0
output enabled
1
Output disabled
F27
2 bytes
Contact Converter Status Bits
(0=not activated, 1=activated)
bit 0
Status for CC1
bit1
Status for CC2
bit 2
Status for CC3
bit 3
Status for CC4
bit 4
Status for CC5
bit 5
Status for CC6
bit 6
Status for CC7
bit 7
Status for CC8
bit 8
Status for CC9 (1-phase model)
bit 9
Status for CC10 (1-phase model)
bit 10
Status for CC11 (1-phase model)
bit 11
Status for CC12 (1-phase model)
GE Power Management
Table B–5: DATA FORMATS (Sheet 6 of 12)
TYPE
F28
F43
F48
F49
F52
ALPS Advanced Line Protection System
B.2 REGISTER MAPS
VALUE/
DESCRIPTION
BITMASK
2 bytes
Output Contact Status Bits
(0=not activated, 1=activated)
bit 0
status for T1
bit 1
status for T2
bit 2
status for T3
bit 3
status for T4
bit 4
status for T5 (1-phase model)
bit 5
status for T6 (1-phase model)
bit 6
status for A1
bit 7
status for A2
bit 8
status for A3
bit 9
status for A4
bit 10
status for A5
bit 11
status for A6
bit 12
status for A7
bit 13
status for A8
bit 14
status for A9 (1-phase model)
bit 15
status for A10 (1-phase model)
bit 16
status for A11 (1-phase model)
bit 17
status for A12 (1-phase model)
bit 18
status for KT1
bit 19
status for KT2
bit 20
status for KT3
bit 21
status for KT4
bit 22
status for C1
bit 23
status for C2
bit 24
status for CA-A/B (Critical Alarm)
2 bytes
Reset Type
0
Fault report and oscillography data
1
Event Data
2
OST Data
3
Breaker Health
4
Reset Target LEDs, Clear Warn and
Fail and Trip Message from Display
and EEPROM
2 bytes
Breaker Duty
0 to 9999
Actual Value
10000 to
Value 10000
------------------------------------- -
19999
10
20000 to
Value 20000
------------------------------------- -
29999
10
2 bytes
Multiplier
0
M - Millions
1
K - Thousands
2
Actual Value
2 bytes
PHASEROTATE value
0
ABC
1
ACB
B
3
×
10
6
×
10
B-17

Advertisement

Table of Contents
loading

Table of Contents