5 FUNCTIONAL TESTS (FACTORY SETTINGS)
5 FUNCTIONAL TESTS (FACTORY SETTINGS) 5.1 TEST SUMMARY
a) MEASURING UNIT TESTS
T1 – FD Fault Detector
T2 – IT Trip Supervision
T3 – IB Blocking Supervision
T4 – Ground Directional Trip
T5 – Ground Directional Block
T6 – Phase Instantaneous Overcurrent
T7 – Ground Instantaneous Overcurrent
T8 – Ground Time Overcurrent
T9 – Undervoltage
T10 – Overvoltage
b) ZONE GROUND / PHASE REACH and TIMERS TESTS
T11 – Zone 1 Ground Reach M1G
T12 – Zone 2 Ground Reach MTG
T13 – Zone 3 Ground Reach M3G
T14 – Zone 4 Ground Reach M4G
T15 – Ground (Zone Backup) Timer
c) PHASE-TO-PHASE ZONE REACH TESTING
T16 – Zone 1 Phase Reach M1
T17 – Zone 2 Phase Reach MT
T18 – Zone 3 Phase Reach M3
T19 – Zone 4 Phase Reach M4
T20 – Phase (Zone Backup) Timer
T21 – Out-of-Step Reach MOB
Refer to Section 4.1: OVERVIEW for information on beginning functional tests.
Contact A1 will chatter when the unit under test is near the threshold. Do not allow this to continue .
Remove the test current. A single contact closure is enough to determine that the unit picked up.
CAUTION
Before starting to test the ALPS, download all the relay settings to your PC using the ALPS-Link program
CAUTION
GE Power Management
ALPS Advanced Line Protection System
5.1 TEST SUMMARY

5.1.1 DESCRIPTION