GE L30 Instruction Manual

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

GE
Digital Energy
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet:
http://www.GEDigitalEnergy.com
*1601-9050-X3*
L30 Line Current Differential
UR Series Instruction Manual
Manual P/N: 1601-9050-X3 (GEK-113622A)
E83849
LISTED
IND.CONT. EQ.
System
L30 revision: 6.0x
831776A2.CDR
52TL
GE Multilin's Quality Management
System is registered to ISO
9001:2008
QMI # 005094
UL # A3775

Advertisement

Table of Contents
loading

Summary of Contents for GE L30

  • Page 1 Digital Energy L30 Line Current Differential System UR Series Instruction Manual L30 revision: 6.0x Manual P/N: 1601-9050-X3 (GEK-113622A) 831776A2.CDR E83849 GE Digital Energy LISTED 650 Markland Street IND.CONT. EQ. 52TL Markham, Ontario GE Multilin's Quality Management Canada L6C 0M1 System is registered to ISO...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3: Table Of Contents

    1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 PC REQUIREMENTS ..................1-6 1.3.2 INSTALLATION....................1-6 1.3.3 CONFIGURING THE L30 FOR SOFTWARE ACCESS........1-7 1.3.4 USING THE QUICK CONNECT FEATURE............. 1-10 1.3.5 CONNECTING TO THE L30 RELAY ............... 1-16 1.4 UR HARDWARE 1.4.1 MOUNTING AND WIRING................
  • Page 4 MANAGED SWITCH LED INDICATORS ............3-46 3.4.4 INITIAL SETUP OF THE ETHERNET SWITCH MODULE.......3-46 3.4.5 CONFIGURING THE MANAGED ETHERNET SWITCH MODULE ....3-50 3.4.6 UPLOADING L30 SWITCH MODULE FIRMWARE..........3-53 3.4.7 ETHERNET SWITCH SELF-TEST ERRORS...........3-55 4. HUMAN INTERFACES 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4.1.1 INTRODUCTION ....................4-1...
  • Page 5 DIGITAL ELEMENTS..................5-190 5.7.9 DIGITAL COUNTERS ..................5-193 5.7.10 MONITORING ELEMENTS ................5-195 5.8 INPUTS AND OUTPUTS 5.8.1 CONTACT INPUTS..................5-206 5.8.2 VIRTUAL INPUTS..................5-208 5.8.3 CONTACT OUTPUTS..................5-209 5.8.4 VIRTUAL OUTPUTS ..................5-211 GE Multilin L30 Line Current Differential System...
  • Page 6 FAULT REPORTS ....................6-22 6.4.2 EVENT RECORDS ...................6-22 6.4.3 OSCILLOGRAPHY ...................6-23 6.4.4 DATA LOGGER ....................6-23 6.4.5 PHASOR MEASUREMENT UNIT RECORDS ..........6-23 6.4.6 BREAKER MAINTENANCE ................6-24 6.5 PRODUCT INFORMATION 6.5.1 MODEL INFORMATION ...................6-25 6.5.2 FIRMWARE REVISIONS..................6-25 L30 Line Current Differential System GE Multilin...
  • Page 7: Security

    9.2.2 TRIP DECISION EXAMPLE................9-18 9.2.3 TRIP DECISION TEST ..................9-18 9.3 FAULT LOCATOR 9.3.1 DESCRIPTION....................9-20 10. APPLICATION OF 10.1 CT REQUIREMENTS SETTINGS 10.1.1 INTRODUCTION....................10-1 10.1.2 CT SATURATION ANALYSIS TOOL............... 10-2 GE Multilin L30 Line Current Differential System...
  • Page 8 10.3.2 COMPENSATION METHOD 1 .................10-7 10.3.3 COMPENSATION METHOD 2 .................10-8 10.3.4 COMPENSATION METHOD 3 .................10-8 10.4 INSTANTANEOUS ELEMENTS 10.4.1 INSTANTANEOUS ELEMENT ERROR DURING L30 SYNCHRONIZATION ........................10-10 11. COMMISSIONING 11.1 TESTING 11.1.1 CHANNEL TESTING ..................11-1 11.1.2 CLOCK SYNCHRONIZATION TESTS .............11-2 11.1.3 CURRENT DIFFERENTIAL................11-3...
  • Page 9 ACSI MODELS CONFORMANCE STATEMENT ..........C-23 C.6.3 ACSI SERVICES CONFORMANCE STATEMENT .........C-24 C.7 LOGICAL NODES C.7.1 LOGICAL NODES TABLE ................C-27 D. IEC 60870-5-104 D.1 IEC 60870-5-104 COMMUNICATIONS D.1.1 INTEROPERABILITY DOCUMENT ..............D-1 D.1.2 POINT LIST......................D-9 GE Multilin L30 Line Current Differential System...
  • Page 10 E.2.4 ANALOG INPUTS.................... E-11 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY..................F-1 F.1.2 CHANGES TO THE L30 MANUAL ..............F-1 F.2 ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS ................. F-4 F.3 WARRANTY F.3.1 GE MULTILIN WARRANTY................F-6 L30 Line Current Differential System...
  • Page 11: Getting Started

    1.1 IMPORTANT PROCEDURES 1 GETTING STARTED 1.1IMPORTANT PROCEDURES Please read this chapter to help guide you through the initial setup of your new L30 Line Current Differential System. 1.1.1 CAUTIONS AND WARNINGS Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment damage, or downtime.
  • Page 12: Inspection Procedure

    For product information, instruction manual updates, and the latest software updates, please visit the GE Digital Energy website at http://www.gedigitalenergy.com. If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE Digital Energy immediately.
  • Page 13: Ur Overview

    This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals. GE Multilin...
  • Page 14: Hardware Architecture

    (dual) ring configuration. This feature is optimized for speed and intended for pilot- aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis. L30 Line Current Differential System GE Multilin...
  • Page 15: Software Architecture

    Employing OOD/OOP in the software architecture of the L30 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functionality classes.
  • Page 16: Enervista Ur Setup Software

    Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color) • RS232 and/or Ethernet port for communications to the relay The following qualified modems have been tested to be compliant with the L30 and the EnerVista UR Setup software. • US Robotics external 56K FaxModem 5686 •...
  • Page 17: Configuring The L30 For Software Access

    OVERVIEW The user can connect remotely to the L30 through the rear RS485 port or the rear Ethernet port with a PC running the EnerVista UR Setup software. The L30 can also be accessed locally with a computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature.
  • Page 18 RS232 port. A computer with an RS232 port and a serial cable is required. To use the RS485 port at the back of the relay, a GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.
  • Page 19 11. Click the Read Order Code button to connect to the L30 device and upload the order code. If a communications error occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step correspond to the relay setting values.
  • Page 20: Using The Quick Connect Feature

    MODBUS PROTOCOL 11. Click the Read Order Code button to connect to the L30 device and upload the order code. If an communications error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting values.
  • Page 21 L30. This ensures that configuration of the EnerVista UR Setup software matches the L30 model number. b) USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the L30 from a computer through Ethernet, first assign an IP address to the relay from the front panel keyboard.
  • Page 22 Right-click the Local Area Connection icon and select Properties. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button. Click on the “Use the following IP address” box. 1-12 L30 Line Current Differential System GE Multilin...
  • Page 23 1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE Enter an IP address with the first three numbers the same as the IP address of the L30 relay and the last number dif- ferent (in this example, 1.1.1.2). Enter a subnet mask equal to the one set in the L30 (in this example, 255.0.0.0).
  • Page 24 If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon- nected from the L30 relay. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or online from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.
  • Page 25 Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica- tions to the L30. This ensures that configuration of the EnerVista UR Setup software matches the L30 model number. When direct communications with the L30 via Ethernet is complete, make the following changes: From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con- nections window.
  • Page 26: Connecting To The L30 Relay

    The EnerVista UR Setup software has several new quick action buttons that provide users with instant access to several functions that are often performed when using L30 relays. From the online window, users can select which relay to interro- gate from a pull-down window, then click on the button for the action they wish to perform. The following quick action func- tions are available: •...
  • Page 27: Ur Hardware

    Figure 1–7: RELAY COMMUNICATIONS OPTIONS To communicate through the L30 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the L30 rear communications port.
  • Page 28: Using The Relay

    LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain until the relay is explicitly put in the “Programmed” state. Select the menu message    SETTINGS PRODUCT SETUP INSTALLATION RELAY SETTINGS RELAY SETTINGS: Not Programmed 1-18 L30 Line Current Differential System GE Multilin...
  • Page 29: Relay Passwords

    Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level pass- words. NOTE 1.5.6 FLEXLOGIC™ CUSTOMIZATION FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex- Logic™ section in Chapter 5 for additional details. GE Multilin L30 Line Current Differential System 1-19...
  • Page 30: Commissioning

    1.5.7 COMMISSIONING The L30 requires a minimum amount of maintenance when it is commissioned into service. Since the L30 is a microproces- sor-based relay, its characteristics do not change over time. As such, no further functional tests are required. Expected ser- vice life is 20 years for UR devices manufactured June 2014 or later when applied in a controlled indoors environment and electrical conditions within specification.
  • Page 31: Product Description

    The L30 is intended to provide complete protection for transmission lines of any voltage level. Both three phase and single phase tripping schemes are available. Models of the L30 are available for application on both two and three terminal lines.
  • Page 32 Direct inputs (8 per pilot channel) Modbus user map User-programmable self-tests Disconnect switches Non-volatile latches Virtual inputs (64) DNP 3.0 or IEC 60870-5-104 protocol Non-volatile selector switch Virtual outputs (96) Event recorder Open Pole Detector VT fuse failure L30 Line Current Differential System GE Multilin...
  • Page 33: Features

    Zero-sequence removal for application on lines with tapped transformers connected in a grounded wye on the line side. • GE phaselets approach based on the Discrete Fourier Transform with 64 samples per cycle and transmitting two time- stamped phaselets per cycle. •...
  • Page 34: Ordering

    2.1.3 ORDERING a) OVERVIEW The L30 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod- ules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications.
  • Page 35 2.1 INTRODUCTION b) ORDER CODES WITH TRADITIONAL CTS AND VTS The order codes for the horizontal mount units with traditional CTs and VTs are shown below. Table 2–3: L30 ORDER CODES (HORIZONTAL UNITS) * - F - W/X Full Size Horizontal Mount...
  • Page 36 2.1 INTRODUCTION 2 PRODUCT DESCRIPTION The order codes for the reduced size vertical mount units with traditional CTs and VTs are shown below. Table 2–4: L30 ORDER CODES (REDUCED SIZE VERTICAL UNITS) * - F Reduced Size Vertical Mount BASE UNIT...
  • Page 37 2.1 INTRODUCTION c) ORDER CODES WITH PROCESS BUS MODULES The order codes for the horizontal mount units with the process bus module are shown below. Table 2–5: L30 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS) * - F - W/X...
  • Page 38 2 PRODUCT DESCRIPTION The order codes for the reduced size vertical mount units with the process bus module are shown below. Table 2–6: L30 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS) * - F Reduced Size Vertical Mount...
  • Page 39: Replacement Modules

    Replacement modules can be ordered separately as shown below. When ordering a replacement CPU module or face- plate, please provide the serial number of your existing unit. Not all replacement modules may be applicable to the L30 relay. Only the modules specified in the order codes are available as replacement modules.
  • Page 40 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels 2-10 L30 Line Current Differential System GE Multilin...
  • Page 41: Pilot Channel Relaying

    (DTT) signal to all of the other L30 relays on the protected line. If a slave L30 relay issues a trip from one of its backup functions, it can send a transfer trip signal to its master and other slave relays if such option is designated.
  • Page 42: Channel Monitor

    2.2.2 CHANNEL MONITOR The L30 has logic to detect that the communications channel is deteriorating or has failed completely. This can provide an alarm indication and disable the current differential protection. Note that a failure of the communications from the master to a slave does not prevent the master from performing the current differential algorithm;...
  • Page 43: Loopback Test

    The L30 includes provision for sending and receiving a single-pole direct transfer trip (DTT) signal from current differential protection between the L30 relays at the line terminals using the pilot communications channel. The user may also initiate an additional eight pilot signals with an L30 communications channel to create trip, block, or signaling logic. A FlexLogic™...
  • Page 44: Functionality

    Current differential protection: The current differential algorithms used in the L30 Line Current Differential System are based on the Fourier transform phaselet approach and an adaptive statistical restraint. The L30 uses per-phase differential at 64 kbps with two phaselets per cycle. A detailed description of the current differential algorithms is found in chapter 8.
  • Page 45: Other Functions

    The relay includes a clock which can run freely from the internal oscillator or be synchronized from an external IRIG-B sig- nal. With the external signal, all relays wired to the same synchronizing signal will be synchronized to within 0.1 millisecond. GE Multilin L30 Line Current Differential System 2-15...
  • Page 46 PFLL Status Frequency Deviation Phase and Frequency Master Locked Loop (PFLL) Clock Phase Deviation PHASELETS TO REMOTE Communications Remote Relay PHASELETS FROM REMOTE Interface Direct Transfer Trip 831732A3.CDR Figure 2–3: L30 BLOCK DIAGRAM 2-16 L30 Line Current Differential System GE Multilin...
  • Page 47 Offset and Sequence Charging Current Currents Phaselets Compute Phasors Phaselets Phaselets Align Phaselets Phaselets Compute Phasors and Variance Parameters Fault Detector Trip Output Disturbance Logic Detector 831749A1.CDR Figure 2–4: MAIN SOFTWARE MODULES GE Multilin L30 Line Current Differential System 2-17...
  • Page 48: Specifications

    < 20 ms at 3 × pickup at 60 Hz the range of 0.1<V<0.9 VT Nominal in a Operate at 1.5 × pickup Timing accuracy: fixed linear relationship ±3% or ±4 ms (whichever is greater) 2-18 L30 Line Current Differential System GE Multilin...
  • Page 49 2 × CT rating: ±2.5% of reading Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01 Timing accuracy: ±3% of operate time or ±4 ms (whichever is greater) GE Multilin L30 Line Current Differential System 2-19...
  • Page 50: User-Programmable Elements

    Number: up to 256 logical variables grouped tual input under 16 Modbus addresses Reset mode: self-reset or latched Programmability: any logical variable, contact, or virtual input 2-20 L30 Line Current Differential System GE Multilin...
  • Page 51: Monitoring

    01 channel for NN days 16 channels for NN days Triggers: any element pickup, dropout, or operate; digital input change of state; digital out- put change of state; self-test events Data storage: in non-volatile memory GE Multilin L30 Line Current Differential System 2-21...
  • Page 52: Metering

    17 V, 33 V, 84 V, 166 V Tolerance: ±10% Contacts per common return: 4 Recognition time: < 1 ms Debounce time: 0.0 to 16.0 ms in steps of 0.5 Continuous current draw:4 mA (when energized) 2-22 L30 Line Current Differential System GE Multilin...
  • Page 53: Power Supply

    Contact material: silver alloy Control: separate operate and reset inputs Control mode: operate-dominant or reset-dominant FORM-A VOLTAGE MONITOR Applicable voltage: approx. 15 to 250 V DC Trickle current: approx. 1 to 2.5 mA GE Multilin L30 Line Current Differential System 2-23...
  • Page 54 (0 to 250 V 1.6 A 10 A 10 A BLO; L/R = 20 ms L/R = 40 ms L/R = 40 ms Manufacturer: Conquer; Part number: 0.8 A SCD-A 005 L/R = 40 ms 2-24 L30 Line Current Differential System GE Multilin...
  • Page 55: Communication Protocols

    10Base-T (CAT 3, 4, 5 UTP): 100 m (328 ft.) 100Base-TX (CAT 5 UTP):100 m (328 ft.) Shielded twisted pair: 150 m (492 ft.) OTHER TFTP, HTTP, IEC 60870-5-104, Ethernet Global Data (EGD) GE Multilin L30 Line Current Differential System 2-25...
  • Page 56: Inter-Relay Communications

    – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Noise 0 dB Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6days). 2-26 L30 Line Current Differential System GE Multilin...
  • Page 57: Type Tests

    Safety UL508 e83849 NKCR Safety UL C22.2-14 e83849 NKCR7 Safety UL1053 e83849 NKCR 2.4.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. GE Multilin L30 Line Current Differential System 2-27...
  • Page 58: Approvals

    Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to avoid deterioration of electrolytic capacitors. 2-28 L30 Line Current Differential System GE Multilin...
  • Page 59: Hardware

    HORIZONTAL UNITS The L30 Line Current Differential System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 60 VERTICAL UNITS The L30 Line Current Differential System is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 61 3 HARDWARE 3.1 DESCRIPTION Figure 3–4: L30 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin L30 Line Current Differential System...
  • Page 62 3.1 DESCRIPTION 3 HARDWARE Figure 3–5: L30 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For side mounting L30 devices with the enhanced front panel, see the following documents available on the UR DVD and the GE Digital Energy website: • GEK-113180: UR-Series UR-V Side-Mounting Front Panel Assembly Instructions •...
  • Page 63 3 HARDWARE 3.1 DESCRIPTION Figure 3–6: L30 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL) GE Multilin L30 Line Current Differential System...
  • Page 64 3.1 DESCRIPTION 3 HARDWARE Figure 3–7: L30 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL) L30 Line Current Differential System GE Multilin...
  • Page 65: Rear Terminal Layout

    (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following figure for an example of rear terminal assignments. Figure 3–9: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin L30 Line Current Differential System...
  • Page 66: Wiring

    3.2 WIRING 3 HARDWARE 3.2WIRING 3.2.1 TYPICAL WIRING Figure 3–10: TYPICAL WIRING DIAGRAM L30 Line Current Differential System GE Multilin...
  • Page 67: Dielectric Strength

    (see the Self-test errors section in chapter 7) or control power is lost, the relay will de-energize. For high reliability systems, the L30 has a redundant option in which two L30 power supplies are placed in parallel on the bus.
  • Page 68: Ct And Vt Modules

    CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram. The exact placement of a zero-sequence core balance CT to detect ground fault current is shown as follows. Twisted-pair cabling on the zero-sequence CT is recommended. 3-10 L30 Line Current Differential System GE Multilin...
  • Page 69 NOTE Current inputs Voltage inputs 8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs) Current inputs 8H, 8J, 8N, and 8R modules (8 CTs) 842766A3.CDR Figure 3–13: CT/VT MODULE WIRING GE Multilin L30 Line Current Differential System 3-11...
  • Page 70: Process Bus Modules

    3.2.5 PROCESS BUS MODULES The L30 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.
  • Page 71 Logic™ operand driving the contact output should be given a reset delay of 10 ms to prevent damage of the output contact (in situations when the element initiating the contact output is bouncing, at val- ues in the region of the pickup value). GE Multilin L30 Line Current Differential System 3-13...
  • Page 72 ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs 3-14 L30 Line Current Differential System GE Multilin...
  • Page 73 ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used GE Multilin L30 Line Current Differential System 3-15...
  • Page 74 3.2 WIRING 3 HARDWARE Figure 3–15: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) 3-16 L30 Line Current Differential System GE Multilin...
  • Page 75 3 HARDWARE 3.2 WIRING Figure 3–16: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output con- nections. GE Multilin L30 Line Current Differential System 3-17...
  • Page 76 Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. 3-18 L30 Line Current Differential System GE Multilin...
  • Page 77 CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–19: AUTO-BURNISH DIP SWITCHES The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, the auto-burnish functionality can be checked using an oscilloscope. NOTE GE Multilin L30 Line Current Differential System 3-19...
  • Page 78: Transducer Inputs And Outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE Figure 3–20: TRANSDUCER INPUT/OUTPUT MODULE WIRING The following figure show how to connect RTDs. 3-20 L30 Line Current Differential System GE Multilin...
  • Page 79 3 HARDWARE 3.2 WIRING Figure 3–21: RTD CONNECTIONS GE Multilin L30 Line Current Differential System 3-21...
  • Page 80: Rs232 Faceplate Port

    3.2.8 RS232 FACEPLATE PORT A 9-pin RS232C serial port is located on the L30 faceplate for programming with a personal computer. All that is required to use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
  • Page 81 For instance, the relays must be connected with all RS485 “+” terminals connected together, and all RS485 “–” terminals connected together. Though data is transmitted over a two-wire twisted pair, all RS485 devices require a shared GE Multilin L30 Line Current Differential System 3-23...
  • Page 82 This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the L30 COM terminal (#3); others function cor- rectly only if the common wire is connected to the L30 COM terminal, but insulated from the shield.
  • Page 83: Irig-B

    IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The IRIG-B code allows time accuracies of up to 100 ns. Using the IRIG-B input, the L30 operates an internal oscillator with 1 µs resolution and accuracy.
  • Page 84 (AM). Third party equipment is available for generating the IRIG-B signal; this equipment may use a GPS satellite system to obtain the time reference so that devices at different geographic locations can also be synchronized. Figure 3–25: OPTIONS FOR IRIG-B CONNECTION 3-26 L30 Line Current Differential System GE Multilin...
  • Page 85 20 to 25 degree error in the synchrophasor angle measurement. The IEEE 1588 Precision Time Protocol can also be used to achieve accurate time synchronization for synchrophasor calculation.sing an ampli- tude modulated receiver will also cause errors of up to 1 ms in metered synchrophasor values. GE Multilin L30 Line Current Differential System 3-27...
  • Page 86: Pilot Channel Communications

    RS422, 1 channel RS422, 2 channels, 2 clock inputs RS422, 2 channels All of the fiber modules use ST type connectors. For two-terminal applications, each L30 relay requires at least one com- munications channel. 3-28 L30 Line Current Differential System...
  • Page 87: Fiber: Led And Eled Transmitters

    3.3.3 FIBER-LASER TRANSMITTERS The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module. Figure 3–28: LASER FIBER MODULES Observing any fiber transmitter output can injure the eye. GE Multilin L30 Line Current Differential System 3-29...
  • Page 88 3.3 PILOT CHANNEL COMMUNICATIONS 3 HARDWARE When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maximum optical input power to the receiver. 3-30 L30 Line Current Differential System GE Multilin...
  • Page 89: Interface

    Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. Replace the top cover and the cover screw. GE Multilin L30 Line Current Differential System 3-31...
  • Page 90 For connection to a higher order system (UR- to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). 3-32 L30 Line Current Differential System GE Multilin...
  • Page 91 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–33: G.703 DUAL LOOPBACK MODE GE Multilin L30 Line Current Differential System 3-33...
  • Page 92: Rs422 Interface

    The send timing out- puts from the multiplexer (data module 1), will connect to the clock inputs of the UR–RS422 interface in the usual fashion. 3-34 L30 Line Current Differential System GE Multilin...
  • Page 93 Figure 3–36: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION Data module 1 provides timing to the L30 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they may vary depending on the manufacturer.
  • Page 94: Two-Channel Two-Clock Rs422 Interface

    74 modules are used in two-terminal with a redundant channel or three-terminal configurations where channel 1 is employed via the RS422 interface (possibly with a multiplexer) and channel 2 via direct fiber. 3-36 L30 Line Current Differential System GE Multilin...
  • Page 95: And Fiber Interface

    The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit rate of 2048 kbps. The specifications for the module are as follows:. GE Multilin L30 Line Current Differential System 3-37...
  • Page 96 5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of L30 communi- cation for two and three terminal applications.
  • Page 97 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. Figure 3–41: IEEE C37.94 TIMING SELECTION SWITCH SETTING GE Multilin L30 Line Current Differential System 3-39...
  • Page 98 Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid 3-40 L30 Line Current Differential System GE Multilin...
  • Page 99: C37.94Sm Interface

    5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of L30 communi- cation for two and three terminal applications.
  • Page 100 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. 3-42 L30 Line Current Differential System GE Multilin...
  • Page 101 Modules shipped from January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the follow- ing figure. Figure 3–44: STATUS LEDS The clock configuration LED status is as follows: • Flashing green — loop timing mode while receiving a valid data packet GE Multilin L30 Line Current Differential System 3-43...
  • Page 102 Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid 3-44 L30 Line Current Differential System GE Multilin...
  • Page 103: Managed Ethernet Switch Modules

    The type 2S and 2T embedded managed switch modules are supported by UR-series relays containing type 9S CPU mod- ules with revisions 5.5x and higher. The modules communicate to the L30 through an internal Ethernet port (referred to as the UR port or port 7) and provide an additional six external Ethernet ports: two 10/100Base-T ports and four multimode ST 100Base-FX ports.
  • Page 104: Managed Switch Led Indicators

    DESCRIPTION Upon initial power up of a L30 device with an installed Ethernet switch, the front panel trouble LED will be illuminated and error message will be displayed. It will be necessary to configure the Ethernet switch and then ENET MODULE OFFLINE place it online.
  • Page 105 The following procedure describes how to initially configure the Ethernet switch to work on your LAN. Initiate communications from a PC to the L30 through a front panel serial connection (refer to the Configuring serial communications section in chapter 1 for details), or if you are familiar with the UR keypad you can use it to set up the network IP address and check the Modbus slave address and Modbus TCP port.
  • Page 106 After few seconds you should see your local area connection attempting to connect to the switch. Once connected, check your IP address by going to bottom of your screen and right-clicking the Local Area Connection icon as shown below. 3-48 L30 Line Current Differential System GE Multilin...
  • Page 107 This procedure describes how to configure the L30 switch module through EnerVista UR Setup. Before starting this proce- dure, ensure that the local PC is properly configured on the same network as the L30 device as shown in the previous sec- tion.
  • Page 108: Configuring The Managed Ethernet Switch Module

    Click the Save button. It will take few seconds to save the settings to the Ethernet switch module and the following message displayed. Verify that the target message is cleared and that the L30 displays the MAC address of the Ethernet switch in the Actual Values > Status > Ethernet Switch window.
  • Page 109 SAVING THE ETHERNET SWITCH SETTINGS TO A SETTINGS FILE The L30 allows the settings information for the Ethernet switch module to be saved locally as a settings file. This file con- tains the advanced configuration details for the switch not contained within the standard L30 settings file.
  • Page 110 Navigate to the folder containing the Ethernet switch settings file, select the file, then click Open. The settings file will be transferred to the Ethernet switch and the settings uploaded to the device. 3-52 L30 Line Current Differential System GE Multilin...
  • Page 111: Uploading L30 Switch Module Firmware

    NOTE b) SELECTING THE PROPER SWITCH FIRMWARE VERSION The latest switch module firmware is available as a download from the GE Multilin web site. Use the following procedure to determine the version of firmware currently installed on your switch Log into the switch using the EnerVista web interface.
  • Page 112 Select the firmware file to be loaded on to the Switch, and select the Open option. The following window will pop up, indicating that the firmware file transfer is in progress. If the firmware load was successful, the following window will appear: Note 3-54 L30 Line Current Differential System GE Multilin...
  • Page 113: Ethernet Switch Self-Test Errors

    No setting required; the L30 EQUIPMENT The L30 has not detected the The L30 failed to see the switch module will read the state of a general MISMATCH: Card XXX presence of the Ethernet on power-up, because switch won’t...
  • Page 114 3.4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3-56 L30 Line Current Differential System GE Multilin...
  • Page 115: Human Interfaces

    To start using the EnerVista UR Setup software, a site definition and device definition must first be created. See the EnerV- ista UR Setup Help File or refer to the Connecting EnerVista UR Setup with the L30 section in Chapter 1 for details.
  • Page 116 Site List window will automatically be sent to the on-line communicating device. g) FIRMWARE UPGRADES The firmware of a L30 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
  • Page 117: Enervista Ur Setup Main Window

    Settings list control bar window. Device data view windows, with common tool bar. Settings file data view windows, with common tool bar. Workspace area with data view tabs. Status bar. 10. Quick action hot links. GE Multilin L30 Line Current Differential System...
  • Page 118 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4 HUMAN INTERFACES 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW L30 Line Current Differential System GE Multilin...
  • Page 119: Extended Enervista Ur Setup Features

    (settings file templates) and online devices (online settings templates). The func- tionality is identical for both purposes. The settings template feature requires that both the EnerVista UR Setup software and the L30 firmware are at ver- sions 5.40 or higher.
  • Page 120 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. L30 Line Current Differential System GE Multilin...
  • Page 121 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND GE Multilin L30 Line Current Differential System...
  • Page 122 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. L30 Line Current Differential System GE Multilin...
  • Page 123: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. GE Multilin L30 Line Current Differential System...
  • Page 124 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. 4-10 L30 Line Current Differential System GE Multilin...
  • Page 125: Settings File Traceability

    When a settings file is transferred to a L30 device, the date, time, and serial number of the L30 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the L30 actual values at any later date to determine if security has been compromised.
  • Page 126 4 HUMAN INTERFACES The transfer date of a setting file written to a L30 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
  • Page 127 ONLINE DEVICE TRACEABILITY INFORMATION The L30 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
  • Page 128: Faceplate Interface

    The faceplate is hinged to allow easy access to the removable modules. There is also a removable dust cover that fits over the faceplate which must be removed in order to access the keypad panel. The following figure shows the horizontal arrangement of the faceplate panels. Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS 4-14 L30 Line Current Differential System GE Multilin...
  • Page 129: Led Indicators

    The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. GE Multilin L30 Line Current Differential System 4-15...
  • Page 130 Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack- age of every L30, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
  • Page 131 User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program the operation of the LEDs on these panels. GE Multilin L30 Line Current Differential System 4-17...
  • Page 132: Custom Labeling Of Leds

    EnerVista UR Setup software is installed and operational. • The L30 settings have been saved to a settings file. • The L30 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://www.gedigitalenergy.com/products/support/ur/URLEDenhanced.doc and printed. •...
  • Page 133 Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the L30 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
  • Page 134 4 HUMAN INTERFACES Bend the tab at the center of the tool tail as shown below. The following procedure describes how to remove the LED labels from the L30 enhanced front panel and insert the custom labels. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay.
  • Page 135 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below. The following procedure describes how to remove the user-programmable pushbutton labels from the L30 enhanced front panel and insert the custom labels.
  • Page 136 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will attach the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. 4-22 L30 Line Current Differential System GE Multilin...
  • Page 137: Display

    4.3.6 BREAKER CONTROL a) INTRODUCTION The L30 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, which can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from faceplate keypad or automatically initiated from a FlexLogic™...
  • Page 138: Menus

    Each press of the MENU key advances through the following main heading pages: • Actual values. • Settings. • Commands. • Targets. • User displays (when enabled). 4-24 L30 Line Current Differential System GE Multilin...
  • Page 139  DISPLAY  PROPERTIES ciated with the Product Setup header.  Press the MESSAGE RIGHT key once more and this will display the first setting for FLASH MESSAGE Display Properties. TIME: 1.0 s GE Multilin L30 Line Current Differential System 4-25...
  • Page 140: Changing Settings

    Text settings have data values which are fixed in length, but user-defined in character. They may be comprised of upper case letters, lower case letters, numerals, and a selection of special characters. 4-26 L30 Line Current Differential System GE Multilin...
  • Page 141: Settings

    When the "NEW SETTING HAS BEEN STORED" message appears, the relay will be in "Programmed" state and the In Service LED will turn on. e) ENTERING INITIAL PASSWORDS The L30 supports password entry from a local or remote connection. GE Multilin L30 Line Current Differential System...
  • Page 142 By default, when an incorrect Command or Setting password has been entered via the faceplate interface three times within three minutes, the FlexLogic™ operand is set to “On” and the L30 does not allow settings or LOCAL ACCESS DENIED command level access via the faceplate interface for the next five minutes.
  • Page 143 4.3 FACEPLATE INTERFACE By default, when an incorrect Command or Setting password has been entered via any external communications interface three times within three minutes, the FlexLogic™ operand is set to and the L30 does not REMOTE ACCESS DENIED “ ”...
  • Page 144 4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4-30 L30 Line Current Differential System GE Multilin...
  • Page 145: Overview

    See page 5-60.  SYSTEM SETUP   POWER SYSTEM See page 5-61.   SIGNAL SOURCES See page 5-62.   87L POWER SYSTEM See page 5-65.   BREAKERS See page 5-71.  GE Multilin L30 Line Current Differential System...
  • Page 146  DIGITAL ELEMENTS See page 5-190.   DIGITAL COUNTERS See page 5-193.   MONITORING See page 5-195.  ELEMENTS  SETTINGS  CONTACT INPUTS See page 5-206.  INPUTS / OUTPUTS  L30 Line Current Differential System GE Multilin...
  • Page 147 See page 5-227.  FORCE CONTACT See page 5-228.  INPUTS  FORCE CONTACT See page 5-229.  OUTPUTS  CHANNEL TESTS See page 5-230.   PMU See page 5-230.  TEST VALUES GE Multilin L30 Line Current Differential System...
  • Page 148: Introduction To Elements

    In more complex elements, a set of settings may be provided to define the range of the measured parameters which will cause the element to pickup. L30 Line Current Differential System GE Multilin...
  • Page 149: Introduction To Ac Sources

    Sources, in the context of L30 series relays, refer to the logical grouping of current and voltage signals such that one source contains all the signals required to measure the load or fault in a particular power apparatus. A given source may contain all or some of the following signals: three-phase currents, single-phase ground current, three-phase voltages and an auxiliary voltages from a single-phase VT for checking for synchronism.
  • Page 150 CTs through which any portion of the current for the element being protected could flow. Auxiliary CTs are required to perform ratio matching if the ratios of the primary CTs to be summed are not identical. In the L30 relay, provisions have been included for all the current signals to be brought to the device where grouping, CT ratio correction, and summation are applied internally via configuration settings.
  • Page 151 Upon startup, the CPU configures the settings required to characterize the current and voltage inputs, and will display them in the appropriate section in the sequence of the banks (as described above) as follows for a maximum configuration: F1, F5, L1, L5, S1, and S5. GE Multilin L30 Line Current Differential System...
  • Page 152 When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the L30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 153 ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both commands and settings. NOTE If a remote connection is established, local passcodes are not visible. NOTE GE Multilin L30 Line Current Differential System...
  • Page 154  SUPERVISION  TIMEOUTS Range: 2 to 5 in steps of 1 INVALID ATTEMPTS MESSAGE BEFORE LOCKOUT: 3 Range: 5 to 60 minutes in steps of 1 PASSWORD LOCKOUT MESSAGE DURATION: 5 min 5-10 L30 Line Current Differential System GE Multilin...
  • Page 155 INVALID ATTEMPTS BEFORE LOCKOUT The L30 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is UNAUTHORIZED ACCESS asserted.
  • Page 156 If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. 5-12 L30 Line Current Differential System GE Multilin...
  • Page 157: Display Properties

    Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The L30 applies a cut- off value to the magnitudes and angles of the measured currents.
  • Page 158: Clear Relay Records

    CLEAR EVENT RECORDS: MESSAGE Range: FlexLogic™ operand CLEAR OSCILLOGRAPHY? MESSAGE Range: FlexLogic™ operand CLEAR DATA LOGGER: MESSAGE Range: FlexLogic™ operand CLEAR ARC AMPS 1: MESSAGE Range: FlexLogic™ operand CLEAR ARC AMPS 2: MESSAGE 5-14 L30 Line Current Differential System GE Multilin...
  • Page 159: Communications

    Selected records can be cleared from user-programmable conditions with FlexLogic™ operands. Assigning user-program- mable pushbuttons to clear specific records are typical applications for these commands. Since the L30 responds to rising edges of the configured FlexLogic™ operands, they must be asserted for at least 50 ms to take effect.
  • Page 160 0 ms The L30 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet or RS485 port.
  • Page 161 This allows the EnerVista UR Setup software to be used on the port. The UR operates as a Modbus slave device only. When using Modbus protocol on the RS232 port, the L30 responds regardless of the pro- MODBUS SLAVE ADDRESS grammed.
  • Page 162 DNP OBJECT 23 MESSAGE DEFAULT VARIATION: 2 Range: 1, 2, 3, 4, 5 DNP OBJECT 30 MESSAGE DEFAULT VARIATION: 1 Range: 1, 2, 3, 4, 5, 7 DNP OBJECT 32 MESSAGE DEFAULT VARIATION: 1 5-18 L30 Line Current Differential System GE Multilin...
  • Page 163 TIMEOUT: 120 s The L30 supports the Distributed Network Protocol (DNP) version 3.0. The L30 can be used as a DNP slave device con- nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the L30 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the L30 at one time.
  • Page 164 DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the L30 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer- tain ranges in DNP masters.
  • Page 165 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored. NOTE Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the L30 is restarted. NOTE GE Multilin...
  • Page 166 The L30 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The L30 operates as an IEC 61850 server. The Remote inputs and outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
  • Page 167 IEC 61850 GSSE application ID name string sent as part of each GSSE message. This GSSE ID string identifies the GSSE message to the receiving device. In L30 releases previous to 5.0x, this name string was repre- sented by the setting.
  • Page 168 DESTINATION MAC address; the least significant bit of the first byte must be set. In L30 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the L30) and setting the multicast bit.
  • Page 169 The L30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 170 Configure the transmission dataset. Configure the GOOSE service settings. Configure the data. The general steps required for reception configuration are: Configure the reception dataset. Configure the GOOSE service settings. Configure the data. 5-26 L30 Line Current Differential System GE Multilin...
  • Page 171 MMXU1 HZ DEADBAND change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency. The L30 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. Configure the reception dataset by making the following changes in the ...
  • Page 172 IEC61850 GOOSE ANALOG INPUT 1 UNITS The GOOSE analog input 1 can now be used as a FlexAnalog™ value in a FlexElement™ or in other settings. The L30 must be rebooted (control power removed and re-applied) before these settings take effect.
  • Page 173 DNA and UserSt bit pairs that are included in GSSE messages. To set up a L30 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and “GGIO3.ST.Ind2.stVal”.
  • Page 174 CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta- tus values in the L30. Clients will still be able to connect to the server (L30 relay), but most data values will not be updated.
  • Page 175 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the L30 virtual inputs.
  • Page 176 GGIO4. When this value is NUMBER OF ANALOG POINTS changed, the L30 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly configured number of analog points.
  • Page 177 ITEM 64 attributes supported by the L30. Changes to the dataset will only take effect when the L30 is restarted. It is recommended to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1, GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.
  • Page 178 XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1. 5-34 L30 Line Current Differential System GE Multilin...
  • Page 179 Internet Explorer or Mozilla Firefox. This feature is available only if the L30 has the ethernet option installed. The web pages are organized as a series of menus that can be accessed starting at the L30 “Main Menu”. Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, etc.
  • Page 180 NUMBER: The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the L30 over a network. The L30 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the L30 contains a list and description of all available files (event records, oscillography, etc.).
  • Page 181 L30 clock is closely synchronized with the SNTP/NTP server. It may take up to two minutes for the L30 to signal an SNTP self-test error if the server is offline.
  • Page 182: Modbus User Map

    MESSAGE Disabled These settings appear only if the L30 is ordered with an Ethernet switch module (type 2S or 2T). The IP address and Modbus TCP port number for the Ethernet switch module are specified in this menu. These settings are used in advanced network configurations.
  • Page 183: Real Time Clock

    SNTP, the offset is used to determine the local time for the L30 clock, since SNTP provides UTC time. The daylight savings time (DST) settings can be used to allow the L30 clock can follow the DST rules of the local time zone.
  • Page 184: Fault Reports

    MESSAGE Z0 ANGLE: 75° The L30 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well as the characteristics of the line or feeder, are entered in this menu. The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in the FaultReport.txt file includes:...
  • Page 185 It should be kept in mind that grounding points in vicinity of the installation impact the system zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, etc.). GE Multilin L30 Line Current Differential System 5-41...
  • Page 186: Oscillography

    Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device. 5-42 L30 Line Current Differential System GE Multilin...
  • Page 187 IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear. GE Multilin L30 Line Current Differential System 5-43...
  • Page 188: Data Logger

    436380 s 254460 s 3600000 ms 2727.5 235645200 s 340.9 29455200 s 26182800 s Changing any setting affecting data logger operation will clear any data that is currently in the log. NOTE 5-44 L30 Line Current Differential System GE Multilin...
  • Page 189: User-Programmable Leds

    The control operand is configured under the setting. The test covers all LEDs, LED TEST CONTROL including the LEDs of the optional user-programmable pushbuttons. The test consists of three stages. GE Multilin L30 Line Current Differential System 5-45...
  • Page 190 Assume one needs to check if any of the LEDs is “burned” through user-programmable pushbutton 1. The following set- tings should be applied. Configure user-programmable pushbutton 1 by making the following entries in the  SETTINGS   menu: PRODUCT SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 5-46 L30 Line Current Differential System GE Multilin...
  • Page 191 “Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a com- munications channel, or from any programmed operand, even if the LED operand state de-asserts. GE Multilin L30 Line Current Differential System 5-47...
  • Page 192: User-Programmable Self-Tests

    Refer to the Relay self-tests section in chapter 7 for additional information on major and minor self-test alarms. To enable the Ethernet switch failure function, ensure that the is “Enabled” in this ETHERNET SWITCH FAIL FUNCTION menu. NOTE 5-48 L30 Line Current Differential System GE Multilin...
  • Page 193: Control Pushbuttons

    The location of the control pushbuttons are shown in the following figures. Control pushbuttons 842813A1.CDR Figure 5–4: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the L30 is ordered with the twelve user- programmable pushbutton option. STATUS EVENT CAUSE...
  • Page 194: User-Programmable Pushbuttons

    PUSHBTN 1 DROP-OUT MESSAGE TIME: 0.00 s Range: FlexLogic™ operand PUSHBTN 1 LED CTL: MESSAGE Range: Disabled, Normal, High Priority PUSHBTN 1 MESSAGE: MESSAGE Disabled Range: Disabled, Enabled PUSHBUTTON 1 MESSAGE EVENTS: Disabled 5-50 L30 Line Current Differential System GE Multilin...
  • Page 195 The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the set- PUSHBTN 1 RESET ting or by directly pressing the associated active front panel pushbutton. GE Multilin L30 Line Current Differential System 5-51...
  • Page 196 This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer. 5-52 L30 Line Current Differential System GE Multilin...
  • Page 197 “Normal” if the setting is “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. GE Multilin L30 Line Current Differential System 5-53...
  • Page 198 Off = 0 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–9: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) 5-54 L30 Line Current Differential System GE Multilin...
  • Page 199 User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via NOTE EnerVista UR Setup with the Maintenance > Enable Pushbutton command. GE Multilin L30 Line Current Differential System 5-55...
  • Page 200: Flex State Parameters

    USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL setting. Any FlexLogic™ operand (in particular, the user-programmable pushbutton operands), can be used to navi- gate the programmed displays. 5-56 L30 Line Current Differential System GE Multilin...
  • Page 201 (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this conversion). GE Multilin L30 Line Current Differential System 5-57...
  • Page 202: Installation

    "Programmed" state. UNIT NOT PROGRAMMED setting allows the user to uniquely identify a relay. This name will appear on generated reports. RELAY NAME 5-58 L30 Line Current Differential System GE Multilin...
  • Page 203: Remote Resources

    Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the L30 process card and specific Brick. The relay is then configured to measure spe- cific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
  • Page 204: System Setup

    1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then a pickup level of 1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). 5-60 L30 Line Current Differential System GE Multilin...
  • Page 205: Power System

    ABC or ACB. CT and VT inputs on the relay, labeled as A, B, and C, must be con- nected to system phases A, B, and C for correct operation. GE Multilin L30 Line Current Differential System 5-61...
  • Page 206: Signal Sources

    FREQUENCY TRACKING cial variable-frequency applications. NOTE The frequency tracking feature will function only when the L30 is in the “Programmed” mode. If the L30 is “Not Pro- grammed”, then metering values will be available but may exhibit significant errors. NOTE The nominal system frequency should be selected as 50 Hz or 60 Hz only.
  • Page 207 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting ( PROD-   ) controls the sensitivity of the disturbance detector UCT SETUP DISPLAY PROPERTIES CURRENT CUT-OFF LEVEL accordingly. GE Multilin L30 Line Current Differential System 5-63...
  • Page 208 Figure 5–13: EXAMPLE USE OF SOURCES Y LV D HV SRC 1 SRC 2 SRC 3 Phase CT F1+F5 None Ground CT None None Phase VT None None Aux VT None None 5-64 L30 Line Current Differential System GE Multilin...
  • Page 209: Power System

     TRANSFORMER Any changes to the L30 power system settings will change the protection system configuration. As such, the 87L protection at all L30 protection system terminals must be temporarily disabled to allow the relays NOTE to acknowledge the new settings.
  • Page 210 Charging current compensation calculations should be performed for an arrangement where the VTs are con- nected to the line side of the circuit; otherwise, opening the breaker at one end of the line will cause a calcula- NOTE tion error. 5-66 L30 Line Current Differential System GE Multilin...
  • Page 211 LOCAL (TERMINAL 1 and TERMINAL 2) ID NUMBER: In installations using multiplexers or modems for communica- tion, it is desirable to ensure the data used by the relays protecting a given line comes from the correct relays. The L30 performs this check by reading the ID number contained in the messages sent by transmitting relays and comparing this ID to the programmed correct ID numbers by the receiving relays.
  • Page 212 • BLOCK GPS TIME REF: This setting signals to the L30 that the time reference is not valid. The time reference may be not accurate due to problems with the GPS receiver. The user must to be aware of the case when a GPS satellite receiver loses its satellite signal and reverts to its own calibrated crystal oscillator.
  • Page 213 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–15: CHANNEL ASYMMETRY COMPENSATION LOGIC GE Multilin L30 Line Current Differential System 5-69...
  • Page 214 “None”). Only one in-zone transformer is allowed for both two-terminal and three-terminal applications. Enabling in-zone transformer functionality forces the L30 to automatically remove the zero-sequence component from all terminals currents. It also disables ground differential 87LG functionality and zero-sequence current removal func- tionality defined by the setting.
  • Page 215: Breakers

    Range: 0.000 to 65.535 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic™ operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled GE Multilin L30 Line Current Differential System 5-71...
  • Page 216 1. The number of breaker control elements is dependent on the number of CT/VT modules specified with the L30. The follow- ing settings are available for each breaker control element.
  • Page 217 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–17: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the L30 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin L30 Line Current Differential System...
  • Page 218 5.4 SYSTEM SETUP 5 SETTINGS Figure 5–18: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2) 5-74 L30 Line Current Differential System GE Multilin...
  • Page 219: Disconnect Switches

    For greater security in determination of the switch pole position, both the 89/a and 89/b auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches depends on the number of the CT/VT modules ordered with the L30. •...
  • Page 220 SWITCH 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among the three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the L30 is in “Programmed” mode and not in the local control mode. NOTE 5-76...
  • Page 221 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–19: DISCONNECT SWITCH SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-77...
  • Page 222: Flexcurves

    1.03 pu. It is recommended to set the two times to a similar value; otherwise, the linear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu. 5-78 L30 Line Current Differential System GE Multilin...
  • Page 223 The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE GE Multilin L30 Line Current Differential System 5-79...
  • Page 224 EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the L30 are displayed in the following graphs. 5-80 L30 Line Current Differential System...
  • Page 225 842723A1.CDR Figure 5–23: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–24: RECLOSER CURVES GE113, GE120, GE138 AND GE142 GE Multilin L30 Line Current Differential System 5-81...
  • Page 226 Figure 5–25: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–26: RECLOSER CURVES GE131, GE141, GE152, AND GE200 5-82 L30 Line Current Differential System GE Multilin...
  • Page 227 Figure 5–27: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–28: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 GE Multilin L30 Line Current Differential System 5-83...
  • Page 228 Figure 5–29: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–30: RECLOSER CURVES GE119, GE135, AND GE202 5-84 L30 Line Current Differential System GE Multilin...
  • Page 229: Phasor Measurement Unit

     UNIT  UNIT 1 The L30 Line Current Differential System is provided with an optional phasor measurement unit feature. This feature is specified as a software option at the time of ordering. The number of phasor measurement units available is also dependent on this option. See the Ordering section of chapter 2 for details.
  • Page 230 See page 5–91.  AGGREGATORS  PMU 1 MESSAGE See page 5-93.  CALIBRATION  PMU 1 MESSAGE See page 5-94.  TRIGGERING  PMU 1 MESSAGE See page 5-101.  RECORDING 5-86 L30 Line Current Differential System GE Multilin...
  • Page 231 NM: AnalogChannel16 Range: Available FlexLogic™ operands PMU 1 D-CH-1: MESSAGE Range: 16 character ASCII string PMU 1 D-CH-1 MESSAGE NM: DigChannel1 Range: Off, On PMU 1 D-CH-1 MESSAGE NORMAL STATE: Off ↓ GE Multilin L30 Line Current Differential System 5-87...
  • Page 232 For a system frequency of 60 Hz (50 Hz), the L30 will generate a reporting mismatch message if the selected rate is not set as 10 Hz, 12 Hz, 15 Hz, 20 Hz, 30 Hz, 60 Hz, or 120 Hz (or 10 Hz, 25 Hz, 50 Hz or 100 Hz when the system frequency is 50 Hz) when entered via the keypad or software;...
  • Page 233 4 Hz Same filter as above 100 Hz 25:1 4 Hz 2 Hz Same filter as above 100 Hz 50:1 2 Hz 1 Hz Same filter as above 100 Hz 100:1 1 Hz GE Multilin L30 Line Current Differential System 5-89...
  • Page 234 PMU1 D-CH-1 NORMAL STATE to PMU1 D-CH-16 NORMAL STATE: These settings allow for specifying a normal state for each digital channel. These states are transmitted in configuration frames to the data concentrator. 5-90 L30 Line Current Differential System GE Multilin...
  • Page 235 IDCODES, as per the PMU IDCODE settings. This IDCODE is to be used by the command frame to start/stop transmission, and request configuration. GE Multilin L30 Line Current Differential System 5-91...
  • Page 236 Note: If changes are made to PMU settings the PMU must be removed from the aggregator and the settings saved and then the PMU should be added back into the aggregator and the settings saved such that the new PMU set- tings take effect. 5-92 L30 Line Current Differential System GE Multilin...
  • Page 237 VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter a positive correction of the secondary signal lags the true signal; and negative value if the secondary signal leads the true signal. GE Multilin L30 Line Current Differential System 5-93...
  • Page 238 When receiving synchrophasor data at multiple locations, with possibly different reference nodes, it can be more beneficial to allow the central locations to perform the compensation of sequence voltages. This setting applies to PMU data only. The L30 calculates symmetrical voltages independently for protection and control purposes without applying this correction.
  • Page 239 L30 standards. This element requires the frequency is above the minimum measurable value. If the frequency is below this value, such as when the circuit is de-energized, the trigger will drop out.
  • Page 240 PMU 1 VOLT TRIGGER LOW-VOLT: This setting specifies the low threshold for the abnormal voltage trigger, in per- unit of the PMU source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The comparator applies a 3% hysteresis. 5-96 L30 Line Current Differential System GE Multilin...
  • Page 241 PMU source. A value of 1 pu is a nominal primary current. The comparator applies a 3% hysteresis. • PMU 1 CURR TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unneces- sary triggering of the recorder. GE Multilin L30 Line Current Differential System 5-97...
  • Page 242 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase power. The comparator applies a 3% hysteresis. 5-98 L30 Line Current Differential System GE Multilin...
  • Page 243 S > APPARENT PICKUP APPARENT POWER, SB S > APPARENT PICKUP APPARENT POWER, SC S > APPARENT PICKUP 3P APPARENT POWER, S S > 3*(APPARENT PICKUP) 847003A1.CDR Figure 5–36: POWER TRIGGER SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-99...
  • Page 244 PMU 1 df/dt TRIGGER DPO TIME: PMU 1 SIGNAL FLEXLOGIC OPERAND SOURCE: df/dt > RAISE PMU 1 ROCOF TRIGGER ROCOF, df/dt –df/dt > FALL 847000A1.CDR Figure 5–37: RATE OF CHANGE OF FREQUENCY TRIGGER SCHEME LOGIC 5-100 L30 Line Current Differential System GE Multilin...
  • Page 245 • PMU 1 TIMED TRIGGER POSITION: This setting specifies the amount of pre-trigger data as a percent of the entire record. This setting applies only to the timed mode of recording. GE Multilin L30 Line Current Differential System 5-101...
  • Page 246: Flexlogic

    Figure 5–38: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the L30 are represented by flags (or FlexLogic™ operands, which are described later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an element from operating, as an input to a control feature in a FlexLogic™...
  • Page 247 Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper- ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different types of operands are listed in the table below. Table 5–12: L30 FLEXLOGIC™ OPERAND TYPES OPERAND TYPE STATE...
  • Page 248 Exceeded maximum CRC error threshold on channel 2 87L DIFF CH2 CRCFAIL 87L DIFF CH1 ID FAIL The ID check for a peer L30 on channel 1 has failed 87L DIFF CH2 ID FAIL The ID check for a peer L30 on channel 2 has failed...
  • Page 249 5 SETTINGS 5.5 FLEXLOGIC™ Table 5–13: L30 FLEXLOGIC™ OPERANDS (Sheet 2 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT BKR FAIL 1 RETRIPA Breaker failure 1 re-trip phase A (only for 1-pole schemes) Breaker failure BKR FAIL 1 RETRIPB...
  • Page 250 5.5 FLEXLOGIC™ 5 SETTINGS Table 5–13: L30 FLEXLOGIC™ OPERANDS (Sheet 3 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT LATCH 1 ON Non-volatile latch 1 is ON (Logic = 1) Non-volatile latches LATCH 1 OFF Non-volatile latch 1 is OFF (Logic = 0)
  • Page 251 5 SETTINGS 5.5 FLEXLOGIC™ Table 5–13: L30 FLEXLOGIC™ OPERANDS (Sheet 4 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: PHASE TOC1 PKP At least one phase of phase time overcurrent 1 has picked up Phase time PHASE TOC1 OP...
  • Page 252 5.5 FLEXLOGIC™ 5 SETTINGS Table 5–13: L30 FLEXLOGIC™ OPERANDS (Sheet 5 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: SWITCH 1 OFF CMD Disconnect switch 1 open command initiated Disconnect switch SWITCH 1 ON CMD Disconnect switch 1 close command initiated SWITCH 1 ΦA BAD ST...
  • Page 253 5 SETTINGS 5.5 FLEXLOGIC™ Table 5–13: L30 FLEXLOGIC™ OPERANDS (Sheet 6 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION INPUTS/OUTPUTS: Cont Op 1 (will not appear unless ordered) Contact outputs, Cont Op 2 (will not appear unless ordered) voltage ↓...
  • Page 254 5.5 FLEXLOGIC™ 5 SETTINGS Table 5–13: L30 FLEXLOGIC™ OPERANDS (Sheet 7 of 7) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION REMOTE DEVICES REMOTE DEVICE 1 On Flag is set, logic=1 REMOTE DEVICE 2 On Flag is set, logic=1 REMOTE DEVICE 3 On Flag is set, logic=1 ↓...
  • Page 255: Flexlogic™ Rules

    When making changes to FlexLogic entries in the settings, all FlexLogic equations are re-compiled whenever any new FlexLogic entry value is entered, and as a result of the re-compile all latches are reset automatically. GE Multilin L30 Line Current Differential System 5-111...
  • Page 256: Flexlogic™ Example

    Dropout State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–40: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS 5-112 L30 Line Current Differential System GE Multilin...
  • Page 257 Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." GE Multilin L30 Line Current Differential System 5-113...
  • Page 258 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On". 86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". 5-114 L30 Line Current Differential System GE Multilin...
  • Page 259 In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) GE Multilin L30 Line Current Differential System 5-115...
  • Page 260: Flexlogic™ Equation Editor

    TIMER 1 TYPE: This setting is used to select the time measuring unit. • TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". 5-116 L30 Line Current Differential System GE Multilin...
  • Page 261: Flexelements

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. GE Multilin L30 Line Current Differential System 5-117...
  • Page 262 The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS 5-118 L30 Line Current Differential System GE Multilin...
  • Page 263 Figure 5–47: FLEXELEMENT™ DIRECTION, PICKUP, AND HYSTERESIS In conjunction with the setting the element could be programmed to provide two extra charac- FLEXELEMENT 1 INPUT MODE teristics as shown in the figure below. GE Multilin L30 Line Current Differential System 5-119...
  • Page 264 BASE = 2000 kA (Brk X Arc Amp A, B, and C) DCmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured under the +IN and –IN inputs. 5-120 L30 Line Current Differential System GE Multilin...
  • Page 265 “Delta”. FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. GE Multilin L30 Line Current Differential System 5-121...
  • Page 266: Non-Volatile Latches

    LATCH N LATCH N LATCH N TYPE RESET Reset Dominant Previous Previous State State Dominant Previous Previous State State Figure 5–49: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC 5-122 L30 Line Current Differential System GE Multilin...
  • Page 267: Grouped Elements

      PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) LINE DIFFERENTIAL ELEMENTS  LINE DIFFERENTIAL  CURRENT See page 5-124.  ELEMENTS  DIFFERENTIAL  STUB BUS MESSAGE See page 5-128.  GE Multilin L30 Line Current Differential System 5-123...
  • Page 268 This CURRENT DIFF SIGNAL SOURCE 1 CURRENT DIFF SIGNAL SOURCE 4 source is mandatory and is assigned with the   menu. SYSTEM SETUP SIGNAL SOURCES SOURCE 1 5-124 L30 Line Current Differential System GE Multilin...
  • Page 269 If set to “Per phase”, the L30 performs inrush inhibit individually in each phase. – If set to “2-out-of-3”, the L30 checks second harmonic level in all three phases individually. If any two phases establish an inhibiting condition, then the remaining phase is restrained automatically.
  • Page 270 CURRENT DIFF DTT: This setting enables and disables the sending of a DTT by the current differential element on per single-phase basis to remote devices. To allow the L30 to restart from master-master to master-slave mode (very important on three-terminal applications), must be set to “Enabled”.
  • Page 271 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–50: CURRENT DIFFERENTIAL SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-127...
  • Page 272 The assigned current element should be mapped to appropriate output contact(s) to trip the stub bus breakers. It should be blocked unless disconnect is open. To prevent 87L tripping from remote L30 relays still protecting the line, the auxiliary contact of line disconnect switch (logic “1” when line switch is open) should be assigned to block the local 87L function by using the setting.
  • Page 273  PHASE IOC3 MESSAGE See page 5-137.   PHASE IOC4 MESSAGE See page 5-137.   PHASE MESSAGE See page 5–138.  DIRECTIONAL 1  PHASE MESSAGE See page 5–138.  DIRECTIONAL 2 GE Multilin L30 Line Current Differential System 5-129...
  • Page 274 5 SETTINGS b) INVERSE TIME OVERCURRENT CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 275 4.827 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 GE Multilin L30 Line Current Differential System 5-131...
  • Page 276 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 5-132 L30 Line Current Differential System GE Multilin...
  • Page 277 = characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–22: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...
  • Page 278 = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The L30 uses the FlexCurve™ feature to facilitate programming of 41 recloser curves. Please refer to the FlexCurve™ sec- tion in this chapter for additional details. 5-134...
  • Page 279 ‘Mvr’ times the setting. If the voltage restraint feature PHASE TOC1 PICKUP is disabled, the pickup level always remains at the setting value. GE Multilin L30 Line Current Differential System 5-135...
  • Page 280 PHASE TOC1 C DPO Multiplier-Phase C PHASE TOC1 C OP SETTING PHASE TOC1 PKP PHASE TOC1 VOLT RESTRAINT: PHASE TOC1 OP Enabled PHASE TOC1 DPO 827072A4.CDR Figure 5–53: PHASE TIME OVERCURRENT 1 SCHEME LOGIC 5-136 L30 Line Current Differential System GE Multilin...
  • Page 281 The input current is the fundamental phasor magnitude. For timing curves, see the publication Instan- taneous Overcurrent Element Response to Saturated Waveforms in UR-Series Relays (GET-8400A). Figure 5–54: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-137...
  • Page 282 CTs and the line-line voltage from the VTs, based on the 90° or quadrature connection. If there is a requirement to supervise overcurrent elements for flows in opposite directions, such as can happen through a bus-tie breaker, two phase directional elements should be programmed with opposite element characteristic angle (ECA) settings. 5-138 L30 Line Current Differential System GE Multilin...
  • Page 283 10 ms must be added to all the instantaneous protection elements under the supervi- sion of the phase directional element. If current reversal is of a concern, a longer delay – in the order of 20 ms – may be needed. GE Multilin L30 Line Current Differential System 5-139...
  • Page 284 MESSAGE See page 5-142.  ↓  NEUTRAL IOC4 MESSAGE See page 5-142.   NEUTRAL MESSAGE See page 5–143.  DIRECTIONAL 1  NEUTRAL MESSAGE See page 5–143.  DIRECTIONAL 2 5-140 L30 Line Current Differential System GE Multilin...
  • Page 285 NEUTRAL TOC1 PKP RESET: NEUTRAL TOC1 IN ≥ PICKUP NEUTRAL TOC1 DPO SOURCE: NEUTRAL TOC1 OP SETTING NEUTRAL TOC1 BLOCK: Off = 0 827034A3.VSD Figure 5–57: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-141...
  • Page 286 RESET DELAY : SETTING NEUTRAL IOC1 DPO NEUTRAL IOC1 OP 3( _0 - K _1 ) PICKUP NEUTRAL IOC1 BLOCK: Off=0 SETTING NEUTRAL IOC1 SOURCE: 827035A4.CDR Figure 5–58: NEUTRAL IOC1 SCHEME LOGIC 5-142 L30 Line Current Differential System GE Multilin...
  • Page 287 × × (EQ 5.19) – The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents resulting from: • System unbalances under heavy load conditions. GE Multilin L30 Line Current Differential System 5-143...
  • Page 288 REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation) The above bias should be taken into account when using the neutral directional overcurrent element to directionalize other protection elements. 5-144 L30 Line Current Differential System GE Multilin...
  • Page 289 If “Dual” polarizing is selected, the element performs both directional comparisons as described above. A given direction is confirmed if either voltage or current comparators indicate so. If a conflicting (simultaneous forward and reverse) indication occurs, the forward direction overrides the reverse direction. GE Multilin L30 Line Current Differential System 5-145...
  • Page 290 NEUTRAL DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the reverse direction. When selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique for the “Calculated 3I0” mode of operation. 5-146 L30 Line Current Differential System GE Multilin...
  • Page 291  GROUND TOC1 See page 5-148.    GROUND TOC2 MESSAGE See page 5-148.   GROUND IOC1 MESSAGE See page 5-149.  ↓  GROUND IOC4 MESSAGE See page 5-149.  GE Multilin L30 Line Current Differential System 5-147...
  • Page 292 GROUND TOC 1 SETTING RESET: GROUND TOC1 PKP GROUND TOC1 GROUND TOC1 DPO IG ≥ PICKUP SOURCE: GROUND TOC1 OP SETTING GROUND TOC1 BLOCK: 827036A3.VSD Off = 0 Figure 5–61: GROUND TOC1 SCHEME LOGIC 5-148 L30 Line Current Differential System GE Multilin...
  • Page 293 Enabled = 1 SETTING DELAY: GROUND IOC1 GROUND IOC1 RESET SETTING PICKUP: DELAY: GROUND IOC1 SOURCE: IG ≥ PICKUP SETTING GROUND IOC1 BLOCK: 827037A4.VSD Off = 0 Figure 5–62: GROUND IOC1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-149...
  • Page 294 < NEG SEQ PICKUP NEG SEQ TOC1 DPO NEG SEQ TOC1 BLOCK: NEG SEQ TOC1 OP Off=0 SETTING NEG SEQ TOC1 SOURCE: Neg Seq 827057A4.CDR Figure 5–63: NEGATIVE SEQUENCE TOC1 SCHEME LOGIC 5-150 L30 Line Current Differential System GE Multilin...
  • Page 295 SETTING NEG SEQ IOC1 DPO NEG SEQ IOC1 OP _2 - K _1 PICKUP NEG SEQ IOC1 BLOCK: Off=0 SETTING NEG SEQ IOC1 SOURCE: 827058A5.CDR Figure 5–64: NEGATIVE SEQUENCE IOC1 SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-151...
  • Page 296: Breaker Failure

    Range: 0.001 to 30.000 pu in steps of 0.001 BF1 N AMP HISET MESSAGE PICKUP: 1.050 pu Range: 0.001 to 30.000 pu in steps of 0.001 BF1 PH AMP LOSET MESSAGE PICKUP: 1.050 pu 5-152 L30 Line Current Differential System GE Multilin...
  • Page 297 GE Multilin L30 Line Current Differential System 5-153...
  • Page 298 BREAKER FAILURE TIMER No. 2 (±1/8 cycle) INITIATE (1/8 cycle) BREAKER FAILURE CURRENT DETECTOR PICKUP (1/8 cycle) BREAKER FAILURE OUTPUT RELAY PICKUP (1/4 cycle) FAULT cycles OCCURS 827083A6.CDR Figure 5–65: BREAKER FAILURE MAIN PATH SEQUENCE 5-154 L30 Line Current Differential System GE Multilin...
  • Page 299 In microprocessor relays this time is not significant. In L30 relays, which use a Fourier transform, the calculated current magnitude will ramp-down to zero one power frequency cycle after the current is interrupted, and this lag should be included in the overall margin duration, as it occurs after current interruption.
  • Page 300 Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command should be given via output operand BKR FAIL 1 TRIP OP 5-156 L30 Line Current Differential System GE Multilin...
  • Page 301 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–67: SINGLE-POLE BREAKER FAILURE, INITIATE GE Multilin L30 Line Current Differential System 5-157...
  • Page 302 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–68: SINGLE-POLE BREAKER FAILURE, TIMERS 5-158 L30 Line Current Differential System GE Multilin...
  • Page 303 5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–69: THREE-POLE BREAKER FAILURE, INITIATE GE Multilin L30 Line Current Differential System 5-159...
  • Page 304 5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–70: THREE-POLE BREAKER FAILURE, TIMERS 5-160 L30 Line Current Differential System GE Multilin...
  • Page 305: Voltage Elements

    ------------------ –   pickup where: T = operating time D = undervoltage delay setting (D = 0.00 operates instantaneously) V = secondary voltage applied to the relay = pickup level pickup GE Multilin L30 Line Current Differential System 5-161...
  • Page 306 Range: 0.000 to 3.000 pu in steps of 0.001 PHASE UV1 MINIMUM MESSAGE VOLTAGE: 0.100 pu Range: FlexLogic™ operand PHASE UV1 BLOCK: MESSAGE Range: Self-reset, Latched, Disabled PHASE UV1 MESSAGE TARGET: Self-reset Range: Disabled, Enabled PHASE UV1 MESSAGE EVENTS: Disabled 5-162 L30 Line Current Differential System GE Multilin...
  • Page 307 The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as cal- culated from phase-to-ground (wye) connected VTs. The specific voltages to be used for each phase are shown below. GE Multilin L30 Line Current Differential System 5-163...
  • Page 308 There are three negative-sequence overvoltage elements available. The negative-sequence overvoltage element may be used to detect loss of one or two phases of the source, a reversed phase sequence of voltage, or a non-symmetrical system voltage condition. 5-164 L30 Line Current Differential System GE Multilin...
  • Page 309 AUX UV1 EVENTS: MESSAGE Disabled The L30 contains one auxiliary undervoltage element for each VT bank. This element is intended for monitoring undervolt- age conditions of the auxiliary voltage. The selects the voltage level at which the time undervoltage ele- AUX UV1 PICKUP ment starts timing.
  • Page 310 AUX OV1 EVENTS: MESSAGE Disabled The L30 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM ...
  • Page 311 Off=0 DELAY : FLEXLOGIC OPERANDS < Vx Pickup AUX OV1 OP SETTING AUX OV1 DPO AUX OV1 SIGNAL AUX OV1 PKP SOURCE: AUXILIARY VOLT (Vx) 827836A2.CDR Figure 5–76: AUXILIARY OVERVOLTAGE SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-167...
  • Page 312: Supervising Elements

    DD CONTROL LOGIC: This setting is used to prevent operation of I_0 and I_2 logic of disturbance detector during conditions such as single breaker pole being open which leads to unbalanced load current in single-pole tripping schemes. Breaker auxiliary contact can be used for such scheme. 5-168 L30 Line Current Differential System GE Multilin...
  • Page 313 OR LOWER) IN 0.02 pu SETTING FLEXLOGIC OPERAND STEPS USING THE HIGHEST VALUE OF 50DD SV DD LOGIC I_0 AND I_2. SEAL-IN: Off=0 SETTING DD NON-CURRENT SUPV: Off=0 827044A6.CDR Figure 5–77: DISTURBANCE DETECTOR SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-169...
  • Page 314: Control Elements

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. 5-170 L30 Line Current Differential System GE Multilin...
  • Page 315 TRIP BUS 1 PKP = Enabled TRIP BUS 1 BLOCK = Off SETTINGS TRIP BUS 1 LATCHING = Enabled TRIP BUS 1 RESET = Off FLEXLOGIC OPERAND RESET OP 842023A1.CDR Figure 5–79: TRIP BUS LOGIC GE Multilin L30 Line Current Differential System 5-171...
  • Page 316: Setting Groups

    The assigned operand is used to control the “On” state of a particular settings group. VIRTUAL OUTPUT 1 5-172 L30 Line Current Differential System GE Multilin...
  • Page 317: Selector Switch

    SELECTOR 1 3BIT ACK: MESSAGE Range: Restore, Synchronize, Sync/Restore SELECTOR 1 POWER-UP MESSAGE MODE: Restore Range: Self-reset, Latched, Disabled SELECTOR 1 TARGETS: MESSAGE Self-reset Range: Disabled, Enabled SELECTOR 1 EVENTS: MESSAGE Disabled GE Multilin L30 Line Current Differential System 5-173...
  • Page 318 SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con- trol word pre-selects the position using the following encoding convention: POSITION rest 5-174 L30 Line Current Differential System GE Multilin...
  • Page 319 The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. GE Multilin L30 Line Current Differential System 5-175...
  • Page 320 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–81: TIME-OUT MODE 5-176 L30 Line Current Differential System GE Multilin...
  • Page 321 Make the following changes to selector switch element in the    SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 GE Multilin L30 Line Current Differential System 5-177...
  • Page 322 SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–83: SELECTOR SWITCH LOGIC 5-178 L30 Line Current Differential System GE Multilin...
  • Page 323: Underfrequency

    ≤ 0 < f PICKUP UNDERFREQ 1 OP UNDERFREQ 1 ACTUAL VALUES MIN VOLT / AMP: UNDERFREQ 1 SOURCE: ≥ Level Minimum VOLT / AMP Frequency 827079A8.CDR Figure 5–84: UNDERFREQUENCY SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-179...
  • Page 324: Synchrocheck

    ΔF. This time can be calculated by: ------------------------------- - (EQ 5.22) 360° ----------------- - × ΔF 2 ΔΦ × where: ΔΦ = phase angle difference in degrees; ΔF = frequency difference in Hz. 5-180 L30 Line Current Differential System GE Multilin...
  • Page 325 COMBINATION SOURCE Y SOURCE Z Phase VTs and Phase VTs and Phase Phase Auxiliary VT Auxiliary VT Phase VTs and Phase VT Phase Phase Auxiliary VT Phase VT Phase VT Phase Phase GE Multilin L30 Line Current Differential System 5-181...
  • Page 326 The relay will use the phase channel of a three-phase set of voltages if pro- grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as part of the Source and a three-phase set is not. 5-182 L30 Line Current Differential System GE Multilin...
  • Page 327 5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–85: SYNCHROCHECK SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-183...
  • Page 328: Autoreclose

    4.000 s Range: FlexLogic™ operand AR1 ADD DELAY 1: MESSAGE Range: 0.00 to 655.35 s in steps of 0.01 AR1 DELAY 1: MESSAGE 0.000 s Range: FlexLogic™ operand AR1 ADD DELAY 2: MESSAGE 5-184 L30 Line Current Differential System GE Multilin...
  • Page 329 Scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure, if any of the following occurs: • The maximum shot number was reached. • A ‘Block’ input is in effect (for instance; Breaker Failure, bus differential protection operated, etc.). GE Multilin L30 Line Current Differential System 5-185...
  • Page 330 ‘reclose-in-progress’ state. If all condi- tions allowing a breaker closure are not satisfied when this time expires, the scheme goes to “Lockout”. This timer must be set to a delay less than the reset timer. NOTE 5-186 L30 Line Current Differential System GE Multilin...
  • Page 331 5 SETTINGS 5.7 CONTROL ELEMENTS To sheet 2 Figure 5–86: AUTORECLOSURE SCHEME LOGIC (Sheet 1 of 2) GE Multilin L30 Line Current Differential System 5-187...
  • Page 332 5.7 CONTROL ELEMENTS 5 SETTINGS Figure 5–87: AUTORECLOSURE SCHEME LOGIC (Sheet 2 of 2) 5-188 L30 Line Current Differential System GE Multilin...
  • Page 333 5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–88: SINGLE SHOT AUTORECLOSING SEQUENCE - PERMANENT FAULT GE Multilin L30 Line Current Differential System 5-189...
  • Page 334: Digital Elements

    DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”. • DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to “Disabled”, the operation of the pickup LED is blocked. 5-190 L30 Line Current Differential System GE Multilin...
  • Page 335 In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. Figure 5–90: TRIP CIRCUIT EXAMPLE 1 GE Multilin L30 Line Current Differential System 5-191...
  • Page 336 In this case, it is not required to supervise the monitoring circuit with the breaker position – the setting is BLOCK selected to “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). Figure 5–91: TRIP CIRCUIT EXAMPLE 2 5-192 L30 Line Current Differential System GE Multilin...
  • Page 337 –2,147,483,648 counts, the counter will rollover to +2,147,483,647. • COUNTER 1 BLOCK: Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are blocked. GE Multilin L30 Line Current Differential System 5-193...
  • Page 338 COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A1.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–92: DIGITAL COUNTER SCHEME LOGIC 5-194 L30 Line Current Differential System GE Multilin...
  • Page 339 1000 kA2-cyc Range: FlexLogic™ operand BKR 1 ARC AMP BLOCK: MESSAGE Range: Self-reset, Latched, Disabled BKR 1 ARC AMP MESSAGE TARGET: Self-reset Range: Disabled, Enabled BKR 1 ARC AMP MESSAGE EVENTS: Disabled GE Multilin L30 Line Current Differential System 5-195...
  • Page 340 BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set. Breaker Contacts Initiate Extinguished Part Total Area = Breaker Arcing Current (kA·cycle) Programmable 100 ms Start Delay Start Stop Integration Integration Figure 5–93: ARCING CURRENT MEASUREMENT 5-196 L30 Line Current Differential System GE Multilin...
  • Page 341 BKR 1 ARCING AMP C Φ 827071A3.CDR BKR 1 OPERATING TIME A Φ BKR 1 OPERATING TIME B Φ BKR 1 OPERATING TIME C Φ BKR 1 OPERATING TIME Figure 5–94: BREAKER ARCING CURRENT SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-197...
  • Page 342 CT FAIL 3I0 INPUT 2 PICKUP: This setting selects the 3I_0 pickup value for input 2 (different CT input) of the relay. • CT FAIL 3V0 INPUT: This setting selects the voltage source. 5-198 L30 Line Current Differential System GE Multilin...
  • Page 343 An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized; positive- sequence voltage and current are both below threshold levels. The function setting enables and disables the fuse failure feature for each source. GE Multilin L30 Line Current Differential System 5-199...
  • Page 344 20 c cles Enabled = 1 SOURCE FLEX-A ALOG 3V_0(3rd Harmonic) SRC1 3V0 3rd Harmonic Note 3V_0 is the sample summation 827093AN.CDR of Va, Vb, and Vc. Figure 5–96: VT FUSE FAIL SCHEME LOGIC 5-200 L30 Line Current Differential System GE Multilin...
  • Page 345 • BROKEN CONDUCTOR 1 PKP DELAY: This setting specifies the pickup time delay for this function to operate after assertion of the broken conductor pickup FlexLogic™ operand. GE Multilin L30 Line Current Differential System 5-201...
  • Page 346 5.7 CONTROL ELEMENTS 5 SETTINGS Figure 5–97: BROKEN CONDUCTOR DETECTION LOGIC 5-202 L30 Line Current Differential System GE Multilin...
  • Page 347 • = measured load RMS current before overload occurs. • k= IEC 255-8 k-factor applied to I , defining maximum permissible current above nominal current. • = protected element base (nominal) current. GE Multilin L30 Line Current Differential System 5-203...
  • Page 348 When current is greater than the pickup level, I > k × I , element starts increasing the thermal energy: t Δ -------------- - (EQ 5.26) – op In 5-204 L30 Line Current Differential System GE Multilin...
  • Page 349 30 minutes Busbar 60 minutes 20 minutes Underground cable 20 to 60 minutes 60 minutes The logic for the thermal overload protection element is shown below. Figure 5–99: THERMAL OVERLOAD PROTECTION SCHEME LOGIC GE Multilin L30 Line Current Differential System 5-205...
  • Page 350 The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the L30 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
  • Page 351 Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. GE Multilin L30 Line Current Differential System 5-207...
  • Page 352 “Virtual Input 1 to OFF = 0” VIRTUAL INPUT 1 ID: (Flexlogic Operand) SETTING Virt Ip 1 VIRTUAL INPUT 1 TYPE: Latched Self - Reset 827080A2.CDR Figure 5–101: VIRTUAL INPUTS SCHEME LOGIC 5-208 L30 Line Current Differential System GE Multilin...
  • Page 353 The most dependable protection of the initiating contact is provided by directly measuring current in the tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in. This can be realized in the L30 using the FlexLogic™ operand to seal-in the contact output as follows: CONT OP 1 ION “Cont Op 1"...
  • Page 354 5 SETTINGS The L30 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop- ulates the setting menu accordingly.
  • Page 355 FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings would be programmed as follows: GE Multilin L30 Line Current Differential System 5-211...
  • Page 356 NOTE c) LOCAL DEVICES: DEVICE ID FOR TRANSMITTING GSSE MESSAGES In a L30 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message is programmed in the ...
  • Page 357 This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre- sponding settings on the sending device. setting provides for the choice of the L30 fixed (DNA/UserSt) dataset (that is, containing REMOTE DEVICE 1 DATASET DNA and UserSt bit pairs), or one of the configurable datasets.
  • Page 358 RemDPS , and FlexLogic™ operands. These operands can then be Ip 1 BAD RemDPS Ip 1 INTERM RemDPS Ip 1 OFF RemDPS Ip 1 ON used in breaker or disconnect control schemes. 5-214 L30 Line Current Differential System GE Multilin...
  • Page 359 Direct input and output FlexLogic™ operands to be used at the local relay are assigned as follows: • Direct input/output 1-1 through direct input/output 1-8 for communications channel 1. • Direct input/output 2-1 through direct input/output 2-8 for communications channel 2 (three-terminal systems only). GE Multilin L30 Line Current Differential System 5-215...
  • Page 360 FlexLogic™ operand. The setting above is used to select the operand which represents a specific function (as selected by the user) to be transmitted. 5-216 L30 Line Current Differential System GE Multilin...
  • Page 361 L90 communication channel (same for 1-2...1-8) (87L is Enabled) SETTING DIRECT OUTPUT 1-1: FLEXLOGIC OPERAND (same for 1-2...1-8) Fail DIRECT I/P 1-1 Off (Flexlogic Operand) (same for 1-2...1-8) 831024A1.CDR Figure 5–102: DIRECT INPUTS/OUTPUTS LOGIC GE Multilin L30 Line Current Differential System 5-217...
  • Page 362 GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna- log™ values in other L30 features, such as FlexElements™. The base factor is applied to the GOOSE analog input FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
  • Page 363 = maximum primary RMS value of all the sources related to the +IN and –IN inputs BASE (Max Delta Volts) The GOOSE analog input FlexAnalog™ values are available for use in other L30 functions that use FlexAnalog™ values. 5.8.12 IEC 61850 GOOSE INTEGERS ...
  • Page 364 –20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT H1 MIN VALUE DCMA INPUT H1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE 5-220 L30 Line Current Differential System GE Multilin...
  • Page 365 1.5 pu. FlexElement™ operands are available to FlexLogic™ for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. GE Multilin L30 Line Current Differential System 5-221...
  • Page 366 168.47 280.77 233.97 16.00 172.46 291.96 243.30 16.39 175.84 303.46 252.88 16.78 179.51 315.31 262.76 17.17 183.17 327.54 272.94 17.56 186.82 340.14 283.45 17.95 190.45 353.14 294.28 18.34 194.08 366.53 305.44 18.73 5-222 L30 Line Current Differential System GE Multilin...
  • Page 367 The feature is intentionally inhibited if the settings are entered incorrectly, e.g. when – MAX VAL MIN VAL MAX VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure. GE Multilin L30 Line Current Differential System 5-223...
  • Page 368 The minimum and maximum power values to be monitored (in pu) are: 20.65 MW 20.65 MW – ------------------------------ -------------------------- - minimum power 1.247 pu, maximum power 1.247 pu (EQ 5.33) – 16.56 MW 16.56 MW The following settings should be entered: 5-224 L30 Line Current Differential System GE Multilin...
  • Page 369 The minimum and maximum voltage values to be monitored (in pu) are: 161.66 kV 254.03 kV -------------------------- - -------------------------- - minimum voltage 0.404 pu, maximum voltage 0.635 pu (EQ 5.39) 400 kV 400 kV The following settings should be entered: GE Multilin L30 Line Current Differential System 5-225...
  • Page 370 1.27 kV – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. 5-226 L30 Line Current Differential System GE Multilin...
  • Page 371 TEST MODE FORCING: MESSAGE The L30 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face- plate by a Test Mode LED indicator.
  • Page 372 Following a restart, power up, settings TEST MODE FUNCTION upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a L30 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states.
  • Page 373 PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the   menu: SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin L30 Line Current Differential System 5-229...
  • Page 374: Channel Tests

    Range: 0.000 to 9.999 kA in steps of 0.001 PMU 1 IA TEST MESSAGE MAGNITUDE: 1.000 kA Range: –180.00 to 180.00° in steps of 0.05 PMU 1 IA TEST MESSAGE ANGLE: –10.00° 5-230 L30 Line Current Differential System GE Multilin...
  • Page 375 When required, it is recommended to use the user-pro- grammable digital channels to signal the C37.118 client that test values are being sent in place of the real measurements. GE Multilin L30 Line Current Differential System 5-231...
  • Page 376 5.10 TESTING 5 SETTINGS 5-232 L30 Line Current Differential System GE Multilin...
  • Page 377: Digital Counters

      ACTUAL VALUES  87L DIFFERENTIAL See page 6-13.  METERING  CURRENT  SOURCE SRC 1 See page 6-14.   SOURCE SRC 2   SYNCHROCHECK See page 6-17.  GE Multilin L30 Line Current Differential System...
  • Page 378: Dcma Inputs

     PMU RECORDS See page 6-23.   MAINTENANCE See page 6-24.   ACTUAL VALUES  MODEL INFORMATION See page 6-25.  PRODUCT INFO   FIRMWARE REVISIONS See page 6-25.  L30 Line Current Differential System GE Multilin...
  • Page 379: Remote Inputs

    The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. GE Multilin L30 Line Current Differential System...
  • Page 380: Remote Double-Point Status Inputs

    Range: On, Off, VOff, VOn, IOn, IOff  CONTACT OUTPUTS Cont Op 1  Range: On, Off, VOff, VOn, IOn, IOff Cont Op 2 MESSAGE ↓ Range: On, Off, VOff, VOn, IOn, IOff Cont Op xx MESSAGE L30 Line Current Differential System GE Multilin...
  • Page 381: Virtual Outputs

    The present state of the programmed remote devices is shown here. The message indicates ALL REMOTE DEVICES ONLINE whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required remote device is not online. GE Multilin L30 Line Current Differential System...
  • Page 382: Channel Tests

    Range: n/a, FAIL, OK VALIDITY OF CHANNEL MESSAGE CONFIGURATION: n/a Range: n/a, FAIL, OK PFLL MESSAGE STATUS: n/a The status information for two channels is shown here. A brief description of each actual value is below: L30 Line Current Differential System GE Multilin...
  • Page 383: Digital Counters

      PATH: ACTUAL VALUES STATUS SELECTOR SWITCHES Range: Current Position / 7  SELECTOR SWITCHES SELECTOR SWITCH 1  POSITION: 0/7 Range: Current Position / 7 SELECTOR SWITCH 2 MESSAGE POSITION: 0/7 GE Multilin L30 Line Current Differential System...
  • Page 384: Flex States

    UINT INPUT 16 MESSAGE The L30 Line Current Differential System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap- ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
  • Page 385: Ethernet Switch

    SWITCH MAC ADDRESS: MESSAGE 00A0F40138FA These actual values appear only if the L30 is ordered with an Ethernet switch module (type 2S or 2T). The status informa- tion for the Ethernet switch is shown in this menu. • SWITCH 1 PORT STATUS to SWITCH 6 PORT STATUS: These values represents the receiver status of each port on the Ethernet switch.
  • Page 386: Metering Conventions

    WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS 6-10 L30 Line Current Differential System GE Multilin...
  • Page 387 ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. GE Multilin L30 Line Current Differential System 6-11...
  • Page 388 The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a relative matter. It is important to remember that the L30 displays are always referenced as specified under SETTINGS ...
  • Page 389: Differential Current

    The metered current values are displayed for all line terminals in fundamental phasor form. All angles are shown with respect to the reference common for all L30 devices; that is, frequency, source currents, and voltages. The metered pri- mary differential and restraint currents are displayed for the local relay.
  • Page 390: Sources

    0.000 0.0° SRC 1 PHASOR Ic: MESSAGE 0.000 0.0° SRC 1 PHASOR In: MESSAGE 0.000 0.0° SRC 1 ZERO SEQ I0: MESSAGE 0.000 0.0° SRC 1 POS SEQ I1: MESSAGE 0.000 0.0° 6-14 L30 Line Current Differential System GE Multilin...
  • Page 391 RMS Vca: MESSAGE 0.00 SRC 1 PHASOR Vab: MESSAGE 0.000 0.0° SRC 1 PHASOR Vbc: MESSAGE 0.000 0.0° SRC 1 PHASOR Vca: MESSAGE 0.000 0.0° SRC 1 ZERO SEQ V0: MESSAGE 0.000 0.0° GE Multilin L30 Line Current Differential System 6-15...
  • Page 392 APPARENT PWR MESSAGE 3φ: 0.000 SRC 1 APPARENT PWR MESSAGE φa: 0.000 SRC 1 APPARENT PWR MESSAGE φb: 0.000 SRC 1 APPARENT PWR MESSAGE φc: 0.000 SRC 1 POWER FACTOR MESSAGE 3φ: 1.000 6-16 L30 Line Current Differential System GE Multilin...
  • Page 393: Synchrocheck

    S = V x Î x Î x Î (EQ 6.1) When VTs are configured in delta, the L30 does not calculate power in each phase and three-phase power is measured as S = V x Î x Î (EQ 6.2)
  • Page 394: Tracking Frequency

    = maximum nominal primary RMS value of the +IN and –IN inputs BASE SYNCHROCHECK = maximum primary RMS value of all the sources related to the +IN and –IN inputs BASE (Max Delta Volts) 6-18 L30 Line Current Differential System GE Multilin...
  • Page 395: Iec 61580 Goose Analog Values

    MESSAGE 0.000 The L30 Line Current Differential System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap- ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
  • Page 396 COUNTER: 0 The above actual values are displayed without the corresponding time stamp as they become available per the recording rate setting. Also, the recording post-filtering setting is applied to these values. 6-20 L30 Line Current Differential System GE Multilin...
  • Page 397: Transducer Inputs And Outputs

    RTD INPUT xx  -50 °C Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value. GE Multilin L30 Line Current Differential System 6-21...
  • Page 398: Records

    COMMANDS CLEAR RECORDS Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log operating phase output only without asserting the common three-phase operand event. 6-22 L30 Line Current Differential System GE Multilin...
  • Page 399: Oscillography

     RECORDING The number of triggers applicable to the phasor measurement unit recorder is indicated by the value. NUMBER OF TRIGGERS The status of the phasor measurement unit recorder is indicated as follows: GE Multilin L30 Line Current Differential System 6-23...
  • Page 400: Breaker Maintenance

    BKR 1 ARCING AMP  menu for clearing breaker arcing current records. The COMMANDS CLEAR RECORDS BREAKER OPERATING TIME defined as the slowest operating time of breaker poles that were initiated to open. 6-24 L30 Line Current Differential System GE Multilin...
  • Page 401: Product Information

    6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION   PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE Multilin order code format;  MODEL INFORMATION ORDER CODE LINE 1: example order code shown  L30-E00-HCH-F8F-H6A Range: standard GE Multilin order code format...
  • Page 402 6.5 PRODUCT INFORMATION 6 ACTUAL VALUES 6-26 L30 Line Current Differential System GE Multilin...
  • Page 403: Commands And Targets

    The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin L30 Line Current Differential System...
  • Page 404: Clear Records

    24-hour clock. The complete date, as a minimum, must be entered to allow execution of this com- mand. The new time will take effect at the moment the ENTER key is clicked. L30 Line Current Differential System GE Multilin...
  • Page 405: Relay Maintenance

    Various self-checking diagnostics are performed in the background while the L30 is running, and diagnostic information is stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the L30 is shipped from the factory, the user may want to clear the diagnostic information for themselves under certain circumstances.
  • Page 406 PMU and not to the absolute UTC time. Therefore a simple IRIG-B genera- tor could be used instead. Also, the test set does not have to support GPS synchronization. Any stable signal source can L30 Line Current Differential System GE Multilin...
  • Page 407 The one-shot feature can be used for ad hoc collection of synchronized measurements in the network. Two or more PMU can be pre-scheduled to freeze their measurements at the same time. When frozen the measurements could be collected using EnerVista UR Setup or a protocol client. GE Multilin L30 Line Current Differential System...
  • Page 408: Targets Menu

     MESSAGE Each L30 element with a TARGET setting has a target message that when activated by its element is displayed in sequence with any other currently active target messages in the menu. In the example shown, the Phase TOC4 TARGETS and Digital Element 48 target settings are active and so have their targets displayed.
  • Page 409 Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the L30 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod- ule (for example, F8L).
  • Page 410 • What to do: Verify that all the items in the GOOSE data set are supported by the L30. The EnerVista UR Setup soft- ware will list the valid items. An IEC61850 client will also show which nodes are available for the L30.
  • Page 411 How often the test is performed: Upon initiation of a contact output state change. • What to do: Verify the state of the output contact and contact the factory if the problem persists. GE Multilin L30 Line Current Differential System...
  • Page 412 Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the L30 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...
  • Page 413: Password Security

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the L30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 414: Password Security Menu

    ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both commands and settings. NOTE If a remote connection is established, local passcodes are not visible. NOTE L30 Line Current Differential System GE Multilin...
  • Page 415: Remote Passwords

    If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password value. If you establish a local connection to the relay (serial), you cannot view remote passcodes. NOTE GE Multilin L30 Line Current Differential System...
  • Page 416: Access Supervision

    INVALID ATTEMPTS BEFORE LOCKOUT The L30 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is UNAUTHORIZED ACCESS asserted.
  • Page 417 If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. GE Multilin L30 Line Current Differential System...
  • Page 418: Enervista Security Management System

    Select the Security > User Management menu item to open the user management configuration window. Enter a username in the User field. The username must be between 4 and 20 characters in length. L30 Line Current Differential System GE Multilin...
  • Page 419: Modifying User Privileges

    The EnerVista security management system must be enabled. The following procedure describes how to modify user privileges. Select the Security > User Management menu item to open the user management configuration window. Locate the username in the User field. GE Multilin L30 Line Current Differential System...
  • Page 420 When this box is checked, the user will become an EnerVista URPlus Setup administrator, therefore receiving all of the administrative rights. Exercise caution when granting administrator rights. Click OK to save the changes to user to the security management system. L30 Line Current Differential System GE Multilin...
  • Page 421: Theory Of Operation

    The second major technical consideration is the restraint characteristic, which is the decision boundary between situations that are declared to be a fault and those that are not. The L30 uses an innovative adaptive decision process based on an on-line computation of the sources of measurement error. In this adaptive approach, the restraint region is an ellipse with variable major axis, minor axis, and orientation.
  • Page 422: Removal Of Decaying Offset

    Since the sampling clocks are synchronized, the time stamp is simply a sequence number. L30 Line Current Differential System GE Multilin...
  • Page 423: Disturbance Detection

    CT saturation is detected (see CT Saturation Detection for details); is an adaptive restraint term (see Online Estimate Of Measurement Error for details) LOC_ADA_A The squared restraining current is calculated as a sum of squared local and all remote restraints: GE Multilin L30 Line Current Differential System...
  • Page 424: Ground Differential Element

    The line ground differential function allows sensitive ground protection for single-line to-ground faults, allowing the phase differential element to be set higher (above load) to provide protection for multi-phase faults. The L30 ground differential function calculates ground differential current from all terminal phase currents. The maximum phase current is used for the restraint.
  • Page 425: Clock Synchronization

    In all cases, an estimate of phase error is computed and used to automatically adapt the restraint region to compensate. Frequency tracking is provided that will accommodate any fre- quency shift normally encountered in power systems. GE Multilin L30 Line Current Differential System...
  • Page 426: Frequency Tracking And Phase Locking

    GPS (Global Positioning System) to compensate for the channel delay asymmetry. This feature requires a GPS receiver to provide a GPS clock signal to the L30 IRIG-B input. With this option there are two clocks as each terminal: a local sampling clock and a local GPS clock.
  • Page 427: Frequency Detection

    Current measurements can generally provide the most accurate information, but are not always available and may contain large errors during faults or switching transients. Time stamped messages are GE Multilin L30 Line Current Differential System...
  • Page 428 256 to the round trip and add 128 to the phase angle. Also, if the above equations are computed using integer values of time stamps, a conversion to phase angle in radians is required by multiplying by π / 32. L30 Line Current Differential System GE Multilin...
  • Page 429 ( T1 T2 T2 T1 ) i -3, i-2, i -1, δ θ Calculate 1, 1. Speed up Slow down 831729A2.CDR Figure 9–2: ROUND TRIP DELAY AND CLOCK OFFSET COMPUTATION FROM TIME STAMPS GE Multilin L30 Line Current Differential System...
  • Page 430: Phase Locking Filter

    T = the time between execution of the filter algorithm repeat = time constant for the primary phase locked loop phase = time constant for the frequency locked loop frequency 9-10 L30 Line Current Differential System GE Multilin...
  • Page 431: Matching Phaselets

    A 6 Mhz clock with a 16-bit hardware counter is adequate, provided the method is used for achieving the 32-bit resolu- tion that is described in this document. • An 8-bit time stamp is adequate provided time stamp messages are exchanged once per cycle. • A 4-bit message sequence number is adequate. GE Multilin L30 Line Current Differential System 9-11...
  • Page 432: Online Estimate Of Measurement Errors

    1_ADA_A 1_A k ( ) 1_MAG_A Another source of the measurement errors is clock synchronization error, resulting in a clock uncertainty term. The L30 algorithm accounts for two terms of synchronization error corresponding to: • Raw clock deviation computed from time stamps. There are several effects that cause it to not track exactly. First, the ping-pong algorithm inherently produces slightly different estimates of clock deviation at each terminal.
  • Page 433: Ct Saturation Detection

    For short transmission lines the charging current is a small factor and can therefore be treated as an unknown error. In this application the L30 can be deployed with- out voltage sensors and the line charging current is included as a constant term in the total variance, increasing the differ- ential restraint current.
  • Page 434: Differential Element Characteristics

    The L30 incorporates an adaptive differential algorithm based on the traditional percent differential principle. In the tradi- tional percent differential scheme, the operating parameter is based on the phasor sum of currents in the zone and the restraint parameter is based on the scalar (or average scalar) sum of the currents in the protected zone - when the operat- ing parameter divided by the restraint parameter is above the slope setting, the relay will operate.
  • Page 435: Relay Synchronization

    9.1 OVERVIEW The major difference between the L30 differential scheme and a percent differential scheme is the use of an estimate of errors in the input currents to increase the restraint parameter during faults, permitting the use of more sensitive settings than those used in the traditional scheme.
  • Page 436: Operating Condition Characteristics

    9.2OPERATING CONDITION CHARACTERISTICS 9.2.1 DESCRIPTION Characteristics of differential elements can be shown in the complex plane. The operating characteristics of the L30 are fundamentally dependant on the relative ratios of the local and remote current phasor magnitudes and the angles of as shown in the Restraint Characteristics figure.
  • Page 437 9 THEORY OF OPERATION 9.2 OPERATING CONDITION CHARACTERISTICS Figure 9–7: RESTRAINT CHARACTERISTICS GE Multilin L30 Line Current Differential System 9-17...
  • Page 438: Trip Decision Example

    Current differential section of chapter 5. The following figure shows how the L30 settings affect the restraint characteristics. The local and remote currents are 180° apart, which represents an external fault. The breakpoint between the two slopes indicates the point where the restraint area is becoming wider to override uncertainties from CT saturation, fault noise, harmonics, etc.
  • Page 439 9 THEORY OF OPERATION 9.2 OPERATING CONDITION CHARACTERISTICS loc pu OPERATE RESTRAINT BP=8, P=2, S1=30%, S2=50% BP=4, P=1, S1=30%, S2=50% BP=4, P=1, S1=20%, S2=40% OPERATE rem pu 831725A1.CDR Figure 9–8: SETTINGS IMPACT ON RESTRAINT CHARACTERISTIC GE Multilin L30 Line Current Differential System 9-19...
  • Page 440: Fault Locator

    Depending on the fault type, appropriate voltage and current signals are selected from the phase quantities before applying the two equations above (the superscripts denote phases, the subscripts denote stations). For AG faults: ⋅ (EQ 9.43) 9-20 L30 Line Current Differential System GE Multilin...
  • Page 441 -- - V (EQ 9.50) – – SYS0 -- - V – – SYS0 where Z is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu. SYS0 GE Multilin L30 Line Current Differential System 9-21...
  • Page 442 FAULT FAULT LOCATION 3I_0 LOCATOR 1 FAULT# RECLOSE SHOT VA or VAB VB or VBC VC or VCA Vn or V_0 SHOT # FROM 827094A5.CDR AUTO RECLOSURE Figure 9–10: FAULT LOCATOR SCHEME 9-22 L30 Line Current Differential System GE Multilin...
  • Page 443: Application Of Settings

    Practically, it is difficult to meet this criteria and avoid saturation completely. The L30 provides several means to ensure security during an external fault, including dual-slope restraint characteristics, adaptive restraint, and CT saturation mechanism, allowing the relay to be secure during severe external faults, while maintaining excellent performance for internal faults.
  • Page 444: Ct Saturation Analysis Tool

    10.1.2 CT SATURATION ANALYSIS TOOL The CT saturation analysis tool is an Excel spreadsheet provided for users to analyze the L30 reliability during CT satura- tion caused by an external fault, to investigate the effect of adjusting 87L settings, and to examine the possibility of reducing the CT requirement.
  • Page 445 You are encouraged to test different fault locations and different fault levels and distributions per short circuit studies. Alter- natively, the tool can help to estimate required CT parameters (ratio and knee point voltage), based on some pre-deter- mined criteria. GE Multilin L30 Line Current Differential System 10-3...
  • Page 446: Current Differential (87L) Settings

    10.2CURRENT DIFFERENTIAL (87L) SETTINGS 10.2.1 INTRODUCTION Software is available from the GE Multilin website that is helpful in selecting settings for the specific appli- cation. Checking the performance of selected element settings with respect to known power system fault NOTE parameters makes it relatively simple to choose the optimum settings for the application.
  • Page 447: Ct Tap

    For relay 1, channel 1 communicates to relay 2 and channel 2 communicates to relay 3 • For relay 2, channel 1 communicates to relay 1 and channel 2 communicates to relay 3 GE Multilin L30 Line Current Differential System 10-5...
  • Page 448 This satisfies the equality condition indicated earlier. During on-load tests, the differential current at all terminals should be the same and generally equal to the charging current if the tap and CT ratio settings are chosen correctly. 10-6 L30 Line Current Differential System GE Multilin...
  • Page 449: Channel Asymmetry Compensation Using Gps

    If GPS is enabled at all terminals and the GPS signal is present, the L30 compensates for the channel asymmetry. On the loss of the GPS signal, the L30 stores the last measured value of the channel asymmetry per channel and compensates for the asymmetry until the GPS clock is available.
  • Page 450: Compensation Method 2

    Create FlexLogic™ similar to that shown below to switch the 87L element to Settings Group 2 (with most sensitive set- tings) if the L30 has a valid GPS time reference. If a GPS or 87L communications failure occurs, the L30 will switch back to Settings Group 1 with less sensitive settings.
  • Page 451 Set the 87L element with different differential settings for Settings Groups 1 and 2 as shown below Enable GPS compensation when the GPS signal is valid and switch to Settings Group 2 (with more sensitive settings) as shown below. GE Multilin L30 Line Current Differential System 10-9...
  • Page 452: Instantaneous Elements

    10.4.1 INSTANTANEOUS ELEMENT ERROR DURING L30 SYNCHRONIZATION As explained in the Theory of Operation chapter, two or three L30 relays are synchronized to each other and to system fre- quency to provide digital differential protection and accurate measurements for other protection and control functions.
  • Page 453: Commissioning

    G.703, and RS422. The speed is 64 Kbaud in a transparent synchronous mode with automatic synchronous character detection and CRC insertion. The Local Loopback Channel Test verifies the L30 communication modules are working properly. The Remote Loopback –4 Channel Test verifies the communication link between the relays meets requirements (BER less than 10 ).
  • Page 454: Clock Synchronization Tests

    “OK” ACTUAL VALUES STATUS CHANNEL TESTS CHANNEL 1(2) STATUS:    “n/a” ACTUAL VALUES STATUS CHANNEL TESTS REMOTE LOOPBACK STATUS:    “OK” ACTUAL VALUES STATUS CHANNEL TESTS PFLL STATUS: 11-2 L30 Line Current Differential System GE Multilin...
  • Page 455: Current Differential

    Download the UR Test software from the GE Multilin website (http://www.gedigitalenergy.com/products/support/ur/ l90test.zip) or contact GE Multilin for information about the UR current differential test program which allows the NOTE user to simulate different operating conditions for verifying correct responses of the relays during commissioning activities.
  • Page 456: Local-Remote Relay Tests

    These phasors and differential currents can be monitored at the ACTUAL VAL-   menu where all current magnitudes and angles can be observed and con- METERING 87L DIFFERENTIAL CURRENT clusions of proper relay interconnections can be made. 11-4 L30 Line Current Differential System GE Multilin...
  • Page 457: Maintenance

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the L30. 842812A1.CDR Figure 12–1: UR MODULE WITHDRAWAL AND INSERTION (ENHANCED FACEPLATE)
  • Page 458 When the clips have locked into position, the module will be fully inserted. CPU connections must be individually disconnected from the module before the module can be removed from the chassis. NOTE NOTE 12-2 L30 Line Current Differential System GE Multilin...
  • Page 459: Batteries

    10. Reinstall the battery clip and the metal cover, and reinsert the power supply module into the unit. 11. Power on the unit. 12. Dispose of the old battery as outlined in the next section. GE Multilin L30 Line Current Differential System 12-3...
  • Page 460: Dispose Of Battery

    La batterie est marqué de ce symbole, qui comprennent les indications cadmium (Cd), plomb (Pb), ou mercure (Hg). Pour le recyclage, retourner la batterie à votre fournisseur ou à un point de collecte. Pour plus d'informations, voir: www.recyclethis.info. 12-4 L30 Line Current Differential System GE Multilin...
  • Page 461 Baterija je označena s tem simbolom, ki lahko vključuje napise, ki označujejo kadmij (Cd), svinec (Pb) ali živo srebro (Hg). Za ustrezno recikliranje baterijo vrnite dobavitelju ali jo odstranite na določenem zbirališču. Za več informacij obiščite spletno stran: www.recyclethis.info. GE Multilin L30 Line Current Differential System 12-5...
  • Page 462 North America 905-294-6222 Latin America +55 11 3614 1700 Europe, Middle East, Africa +(34) 94 485 88 00 Asia +86-21-2401-3208 India +91 80 41314617 From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574 12-6 L30 Line Current Differential System GE Multilin...
  • Page 463: Uninstall And Clear Files And Data

    Other files can be in standard formats, such as COMTRADE or .csv. You cannot erase directly the flash memory, but all records and settings in that memory can be deleted. Do this using the   command. SETTINGS PRODUCT SETUP CLEAR RELAY RECORDS GE Multilin L30 Line Current Differential System 12-7...
  • Page 464: Repairs

    Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty. • Fax a copy of the shipping information to the GE Digital Energy service department in Canada at +1 905 927 5098. Use the detailed return procedure outlined at https://www.gedigitalenergy.com/multilin/support/ret_proc.htm...
  • Page 465: Storage

    Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range outlined in the Specifications. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. GE Multilin L30 Line Current Differential System 12-9...
  • Page 466: Disposal

    European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove the modules as outlined earlier, dismantle the unit, and recycle the metal when possible. 12-10 L30 Line Current Differential System GE Multilin...
  • Page 467: Parameter Lists

    6230 SRC 2 Ig Mag Amps Source 2 ground current magnitude 6232 SRC 2 Ig Angle Degrees Source 2 ground current angle 6233 SRC 2 I_0 Mag Amps Source 2 zero-sequence current magnitude GE Multilin L30 Line Current Differential System...
  • Page 468 SRC 2 Vbc RMS Volts Source 2 phase BC voltage RMS 6739 SRC 2 Vca RMS Volts Source 2 phase CA voltage RMS 6741 SRC 2 Vab Mag Volts Source 2 phase AB voltage magnitude L30 Line Current Differential System GE Multilin...
  • Page 469 Source 2 phase A power factor 7226 SRC 2 Phase B PF Source 2 phase B power factor 7227 SRC 2 Phase C PF Source 2 phase C power factor 7552 SRC 1 Frequency Source 1 frequency GE Multilin L30 Line Current Differential System...
  • Page 470 9366 Diff Curr IC Mag Amps Differential current phase C magnitude 9368 Local IA Angle Degrees Local terminal current phase A angle 9369 Local IB Angle Degrees Local terminal current phase B angle L30 Line Current Differential System GE Multilin...
  • Page 471 Phasor measurement unit 1 negative-sequence current angle 9575 PMU 1 I0 Mag Amps Phasor measurement unit 1 zero-sequence current magnitude 9577 PMU 1 I0 Angle Degrees Phasor measurement unit 1 zero-sequence current angle GE Multilin L30 Line Current Differential System...
  • Page 472 RTD input 16 actual value 13568 RTD Inputs 17 Value RTD input 17 actual value 13569 RTD Inputs 18 Value RTD input 18 actual value 13570 RTD Inputs 19 Value RTD input 19 actual value L30 Line Current Differential System GE Multilin...
  • Page 473 45590 GOOSE Analog In 4 IEC 61850 GOOSE analog input 4 45592 GOOSE Analog In 5 IEC 61850 GOOSE analog input 5 45594 GOOSE Analog In 6 IEC 61850 GOOSE analog input 6 GE Multilin L30 Line Current Differential System...
  • Page 474: Flexinteger Items

    IEC61850 GOOSE UInteger input 13 9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 L30 Line Current Differential System GE Multilin...
  • Page 475: Modbus Communications

    See the Supported Function Codes section for complete details. An exception response from the slave is indi- cated by setting the high order bit of the function code in the response packet. See the Exception Responses section for further details. GE Multilin L30 Line Current Differential System...
  • Page 476: Modbus Rtu Crc-16 Algorithm

    This algorithm requires the characteristic polynomial to be reverse bit ordered. The most significant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder. A C programming language implementation of the CRC algorithm will be provided upon request. L30 Line Current Differential System GE Multilin...
  • Page 477 No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC GE Multilin L30 Line Current Differential System...
  • Page 478: Modbus Function Codes

    NUMBER OF REGISTERS - low DATA #2 - high CRC - low DATA #2 - low CRC - high DATA #3 - high DATA #3 - low CRC - low CRC - high L30 Line Current Differential System GE Multilin...
  • Page 479: Execute Operation (Function Code 05H

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high GE Multilin L30 Line Current Differential System...
  • Page 480: Store Multiple Settings (Function Code 10H

    PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte L30 Line Current Differential System GE Multilin...
  • Page 481: B.3.1 Obtaining Relay Files Via Modbus

    Familiarity with the data logger feature is required to understand this description. Refer to the Data Logger section of Chap- ter 5 for details. To read the entire data logger in binary COMTRADE format, read the following files. GE Multilin L30 Line Current Differential System...
  • Page 482: File Transfers

    “Number of Fault Reports' register. If the value changes, then the master reads all the new files. The contents of the file is in standard HTML notation and can be viewed via any commercial browser. L30 Line Current Differential System GE Multilin...
  • Page 483: Memory Mapping

    0412 Virtual Input 19 State 0 to 1 F108 0 (Off) 0413 Virtual Input 20 State 0 to 1 F108 0 (Off) 0414 Virtual Input 21 State 0 to 1 F108 0 (Off) GE Multilin L30 Line Current Differential System...
  • Page 484 0 to 4294967295 F003 part of time stamp) 0808 ...Repeated for Digital Counter 2 0810 ...Repeated for Digital Counter 3 0818 ...Repeated for Digital Counter 4 0820 ...Repeated for Digital Counter 5 B-10 L30 Line Current Differential System GE Multilin...
  • Page 485 Field Latching Output Close Operand States 0 to 65535 F500 1609 Field Latching Output Open Driver States 0 to 65535 F500 160A Field Latching Output Close Driver States 0 to 65535 F500 GE Multilin L30 Line Current Differential System B-11...
  • Page 486 Source 1 Positive Sequence Current Magnitude 0 to 999999.999 0.001 F060 181E Source 1 Positive Sequence Current Angle -359.9 to 0 degrees F002 181F Source 1 Negative Sequence Current Magnitude 0 to 999999.999 0.001 F060 B-12 L30 Line Current Differential System GE Multilin...
  • Page 487 Source 1 Three Phase Apparent Power -1000000000000 to 0.001 F060 1000000000000 1C12 Source 1 Phase A Apparent Power -1000000000000 to 0.001 F060 1000000000000 1C14 Source 1 Phase B Apparent Power -1000000000000 to 0.001 F060 1000000000000 GE Multilin L30 Line Current Differential System B-13...
  • Page 488 0 to 11 F148 0 (NA) 2365 Fault 1 Location based on Line length units (km or miles) -3276.7 to 3276.7 F002 2366 ...Repeated for Fault 2 238C ...Repeated for Fault 3 B-14 L30 Line Current Differential System GE Multilin...
  • Page 489 0 to 999999.999 0.001 F060 24BB Local IG Magnitude 0 to 999999.999 0.001 F060 24BD Local IG Angle -359.9 to 0 degrees F002 24BE Terminal 1 IG Magnitude 0 to 999999.999 0.001 F060 GE Multilin L30 Line Current Differential System B-15...
  • Page 490 Remote Double-Point Status Input 1 Events 0 to 1 F102 0 (Disabled) 2629 ... Repeated for Double-Point Status Input 2 2632 ... Repeated for Double-Point Status Input 3 263B ... Repeated for Double-Point Status Input 4 B-16 L30 Line Current Differential System GE Multilin...
  • Page 491 Oscillography Force Trigger 0 to 1 F126 0 (No) 3011 Oscillography Clear Data 0 to 1 F126 0 (No) Oscillography Analog Values (Read Only) 3012 Oscillography Number of Triggers 0 to 32767 F001 GE Multilin L30 Line Current Differential System B-17...
  • Page 492 Security (Read/Write Setting) 32D4 Observer Alphanumeric Password Setting F202 (none) Security (Read Only) 32DE Observer Alphanumeric Password Status 0 to 1 F102 0 (Disabled) Security (Read/Write) 32DF Observer Alphanumeric Password Entry F202 (none) B-18 L30 Line Current Differential System GE Multilin...
  • Page 493 -9999.999 to 9999.999 0.001 F004 RTD Input Values (Read Only) (48 modules) 34F0 RTD Input 1 Value -32768 to 32767 °C F002 34F1 RTD Input 2 Value -32768 to 32767 °C F002 GE Multilin L30 Line Current Differential System B-19...
  • Page 494 3806 Field Unit 1 Function 0 to 1 F102 0 (Disabled) 3807 Field Unit 1 Type 0 to 3 F243 0 (CC-05) 3808 Field Unit 1 Serial Number 1 to1 F205 "000000000000" B-20 L30 Line Current Differential System GE Multilin...
  • Page 495 ...Repeated for Field Contact Input 5 3937 ...Repeated for Field Contact Input 6 3942 ...Repeated for Field Contact Input 7 394D ...Repeated for Field Contact Input 8 3958 ...Repeated for Field Contact Input 9 GE Multilin L30 Line Current Differential System B-21...
  • Page 496 ...Repeated for Field Shared Input 16 Field Unit Contact Outputs (Read/Write Setting) (8 modules) 3BB0 Field Contact Output 1 ID (6 items) F205 "FCO U /OUT" 3BD4 Field Output 1 Operate (6 items) 0 to 65535 F300 B-22 L30 Line Current Differential System GE Multilin...
  • Page 497 ...Repeated for Field Unit RTD 2 3E90 ...Repeated for Field Unit RTD 3 3E98 ...Repeated for Field Unit RTD 4 3EA0 ...Repeated for Field Unit RTD 5 3EA8 ...Repeated for Field Unit RTD 6 GE Multilin L30 Line Current Differential System B-23...
  • Page 498 LED Test (Read/Write Setting) 4048 LED Test Function 0 to 1 F102 0 (Disabled) 4049 LED Test Control 0 to 65535 F300 Preferences (Read/Write Setting) 404F Language 0 to 4 F531 0 (English) B-24 L30 Line Current Differential System GE Multilin...
  • Page 499 DNP Channel 2 Port 0 to 5 F177 0 (None) 409C DNP Address 0 to 65519 F001 409D Reserved 0 to 1 F001 409E DNP Client Addresses (2 items) 0 to 4294967295 F003 GE Multilin L30 Line Current Differential System B-25...
  • Page 500 DNP Object 23 Default Variation 0 to 3 F523 0 (1) 4146 DNP Object 30 Default Variation 1 to 5 F001 4147 DNP Object 32 Default Variation 0 to 5 F525 0 (1) B-26 L30 Line Current Differential System GE Multilin...
  • Page 501 F118 0 (Auto. Overwrite) 41C2 Oscillography Trigger Position 0 to 100 F001 41C3 Oscillography Trigger Source 0 to 65535 F300 41C4 Oscillography AC Input Waveforms 0 to 4 F183 2 (16 samples/cycle) GE Multilin L30 Line Current Differential System B-27...
  • Page 502 ...Repeated for User-Programmable LED 42 42D4 ...Repeated for User-Programmable LED 43 42D6 ...Repeated for User-Programmable LED 44 42D8 ...Repeated for User-Programmable LED 45 42DA ...Repeated for User-Programmable LED 46 42DC ...Repeated for User-Programmable LED 47 B-28 L30 Line Current Differential System GE Multilin...
  • Page 503 0 to 12 F560 0 (None) 4606 In-Zone Transformer Location 0 to 2 F562 0 (Local-Tap) Breaker Control (Read/Write Settings) (2 modules) 4700 Breaker 1 Function 0 to 1 F102 0 (Disabled) GE Multilin L30 Line Current Differential System B-29...
  • Page 504 ...Repeated for User-Definable Display 2 4C40 ...Repeated for User-Definable Display 3 4C60 ...Repeated for User-Definable Display 4 4C80 ...Repeated for User-Definable Display 5 4CA0 ...Repeated for User-Definable Display 6 4CC0 ...Repeated for User-Definable Display 7 B-30 L30 Line Current Differential System GE Multilin...
  • Page 505 Repeated for Field Unit 5 4EDC Repeated for Field Unit 6 4F08 Repeated for Field Unit 7 4F34 Repeated for Field Unit 8 FlexLogic (Read/Write Setting) 5000 FlexLogic™ Entry (512 items) 0 to 65535 F300 8192 GE Multilin L30 Line Current Differential System B-31...
  • Page 506 ...Repeated for RTD Input 48 FlexLogic Timers (Read/Write Setting) (32 modules) 5800 FlexLogic™ Timer 1 Type 0 to 2 F129 0 (millisecond) 5801 FlexLogic™ Timer 1 Pickup Delay 0 to 60000 F001 B-32 L30 Line Current Differential System GE Multilin...
  • Page 507 Phase Instantaneous Overcurrent 1 Delay 0 to 600 0.01 F001 5A04 Phase Instantaneous Overcurrent 1 Reset Delay 0 to 600 0.01 F001 5A05 Phase IOC1 Block For Phase A 0 to 65535 F300 GE Multilin L30 Line Current Differential System B-33...
  • Page 508 Ground Instantaneous Overcurrent 1 Delay 0 to 600 0.01 F001 5E04 Ground Instantaneous Overcurrent 1 Reset Delay 0 to 600 0.01 F001 5E05 Ground Instantaneous Overcurrent 1 Block 0 to 65535 F300 B-34 L30 Line Current Differential System GE Multilin...
  • Page 509 0 (Disabled) 6010 87L Current Differential Tap 2 Setting 0.2 to 5 0.01 F001 Current Differential 87L In-Zone Transformer (Read/Write Grouped Setting) 601E 87L Inrush Inhibit Mode 0 to 3 F561 0 (Disabled) GE Multilin L30 Line Current Differential System B-35...
  • Page 510 F109 0 (Self-reset) 6308 Negative Sequence Time Overcurrent 1 Events 0 to 1 F102 0 (Disabled) 6309 Reserved (7 items) 0 to 1 F001 6310 ...Repeated for Negative Sequence Time Overcurrent 2 B-36 L30 Line Current Differential System GE Multilin...
  • Page 511 7266 Phase Directional Overcurrent 1 Target 0 to 2 F109 0 (Self-reset) 7267 Phase Directional Overcurrent 1 Events 0 to 1 F102 0 (Disabled) 7268 Reserved (8 items) 0 to 1 F001 GE Multilin L30 Line Current Differential System B-37...
  • Page 512 ...Repeated for DCmA Inputs 10 73F0 ...Repeated for DCmA Inputs 11 7408 ...Repeated for DCmA Inputs 12 7420 ...Repeated for DCmA Inputs 13 7438 ...Repeated for DCmA Inputs 14 7450 ...Repeated for DCmA Inputs 15 B-38 L30 Line Current Differential System GE Multilin...
  • Page 513 7754 Broken Conductor 1 I2/I1 Ratio 20 to 100 F001 7755 Broken Conductor 1 I1 Minimum 0.05 to 1 0.01 F001 7756 Broken Conductor 1 I1 Maximum 0.05 to 5 0.01 F001 GE Multilin L30 Line Current Differential System B-39...
  • Page 514 PMU 1 Ground Current Test Angle -180 to 180 ° 0.05 F002 78D1 PMU 1 Test Frequency 20 to 70 0.001 F003 60000 78D3 PMU 1 Test df/dt -10 to 10 Hz/s 0.01 F002 B-40 L30 Line Current Differential System GE Multilin...
  • Page 515 User Programmable Pushbuttons (Read/Write Setting) (16 modules) 7B60 User Programmable Pushbutton 1 Function 0 to 2 F137 0 (Disabled) 7B61 User Programmable Pushbutton 1 Top Line F202 (none) 7B6B User Programmable Pushbutton 1 On Text F202 (none) GE Multilin L30 Line Current Differential System B-41...
  • Page 516 0 to 65535 F300 7F36 Auxiliary Overvoltage 1 Target 0 to 2 F109 0 (Self-reset) 7F37 Auxiliary Overvoltage 1 Events 0 to 1 F102 0 (Disabled) 7F38 Reserved (8 items) 0 to 65535 F001 B-42 L30 Line Current Differential System GE Multilin...
  • Page 517 Breaker Failure 1 Trip Dropout Delay 0 to 65.535 0.001 F001 8618 Breaker Failure 1 Target 0 to 2 F109 0 (Self-reset) 8619 Breaker Failure 1 Events 0 to 1 F102 0 (Disabled) GE Multilin L30 Line Current Differential System B-43...
  • Page 518 ...Repeated for Digital Element 29 8C44 ...Repeated for Digital Element 30 8C58 ...Repeated for Digital Element 31 8C6C ...Repeated for Digital Element 32 8C80 ...Repeated for Digital Element 33 8C94 ...Repeated for Digital Element 34 B-44 L30 Line Current Differential System GE Multilin...
  • Page 519 0 to 1 F516 0 (LEVEL) 9007 FlexElement™ 1 Input 0 to 1 F515 0 (SIGNED) 9008 FlexElement™ 1 Direction 0 to 1 F517 0 (OVER) 9009 FlexElement™ 1 Hysteresis 0.1 to 50 F001 GE Multilin L30 Line Current Differential System B-45...
  • Page 520 ...Repeated for DCmA Output 19 9372 ...Repeated for DCmA Output 20 9378 ...Repeated for DCmA Output 21 937E ...Repeated for DCmA Output 22 9384 ...Repeated for DCmA Output 23 938A ...Repeated for DCmA Output 24 B-46 L30 Line Current Differential System GE Multilin...
  • Page 521 0 (Time-out) A28A Selector 1 Bit Acknowledge 0 to 65535 F300 A28B Selector 1 Power Up Mode 0 to 2 F084 0 (Restore) A28C Selector 1 Target 0 to 2 F109 0 (Self-reset) GE Multilin L30 Line Current Differential System B-47...
  • Page 522 ...Repeated for Digital Counter 3 A860 ...Repeated for Digital Counter 4 A880 ...Repeated for Digital Counter 5 A8A0 ...Repeated for Digital Counter 6 A8C0 ...Repeated for Digital Counter 7 A8E0 ...Repeated for Digital Counter 8 B-48 L30 Line Current Differential System GE Multilin...
  • Page 523 F206 (none) AC0B IEC 61850 Logical Node PTOCx Name Prefix (24 items) 0 to 65534 F206 (none) AC53 IEC 61850 Logical Node PTUVx Name Prefix (13 items) 0 to 65534 F206 (none) GE Multilin L30 Line Current Differential System B-49...
  • Page 524 ...Repeated for IEC 61850 GGIO4 Analog Input 3 AF25 ...Repeated for IEC 61850 GGIO4 Analog Input 4 AF2C ...Repeated for IEC 61850 GGIO4 Analog Input 5 AF33 ...Repeated for IEC 61850 GGIO4 Analog Input 6 B-50 L30 Line Current Differential System GE Multilin...
  • Page 525 0.001 to 100 0.001 F003 10000 B0CA IEC 61850 MMXU PPV.phsAB Deadband 1 0.001 to 100 0.001 F003 10000 B0CC IEC 61850 MMXU PPV.phsBC Deadband 1 0.001 to 100 0.001 F003 10000 GE Multilin L30 Line Current Differential System B-51...
  • Page 526 ...Repeated for Received Analog 22 B23C ...Repeated for Received Analog 23 B23E ...Repeated for Received Analog 24 B240 ...Repeated for Received Analog 25 B242 ...Repeated for Received Analog 26 B244 ...Repeated for Received Analog 27 B-52 L30 Line Current Differential System GE Multilin...
  • Page 527 0 to 1 F102 0 (Disabled) BB07 Contact Input 1 Debounce Time 0 to 16 F001 BB08 ...Repeated for Contact Input 2 BB10 ...Repeated for Contact Input 3 BB18 ...Repeated for Contact Input 4 GE Multilin L30 Line Current Differential System B-53...
  • Page 528 ...Repeated for Contact Input 53 BCA8 ...Repeated for Contact Input 54 BCB0 ...Repeated for Contact Input 55 BCB8 ...Repeated for Contact Input 56 BCC0 ...Repeated for Contact Input 57 BCC8 ...Repeated for Contact Input 58 B-54 L30 Line Current Differential System GE Multilin...
  • Page 529 ...Repeated for Virtual Input 4 BE60 ...Repeated for Virtual Input 5 BE6C ...Repeated for Virtual Input 6 BE78 ...Repeated for Virtual Input 7 BE84 ...Repeated for Virtual Input 8 BE90 ...Repeated for Virtual Input 9 GE Multilin L30 Line Current Differential System B-55...
  • Page 530 ...Repeated for Virtual Input 58 C0E8 ...Repeated for Virtual Input 59 C0F4 ...Repeated for Virtual Input 60 C100 ...Repeated for Virtual Input 61 C10C ...Repeated for Virtual Input 62 C118 ...Repeated for Virtual Input 63 B-56 L30 Line Current Differential System GE Multilin...
  • Page 531 ...Repeated for Virtual Output 45 C298 ...Repeated for Virtual Output 46 C2A0 ...Repeated for Virtual Output 47 C2A8 ...Repeated for Virtual Output 48 C2B0 ...Repeated for Virtual Output 49 C2B8 ...Repeated for Virtual Output 50 GE Multilin L30 Line Current Differential System B-57...
  • Page 532 Test Mode Forcing 0 to 65535 F300 C436 Relay Reboot Command 0 to 1 F126 0 (No) Clear Commands (Read/Write) C433 Clear All Relay Records Command 0 to 1 F126 0 (No) B-58 L30 Line Current Differential System GE Multilin...
  • Page 533 ...Repeated for Contact Output 39 C614 ...Repeated for Contact Output 40 C620 ...Repeated for Contact Output 41 C62C ...Repeated for Contact Output 42 C638 ...Repeated for Contact Output 43 C644 ...Repeated for Contact Output 44 GE Multilin L30 Line Current Differential System B-59...
  • Page 534 1 to 2 F001 C844 Remote Diagnostics Transmit 0 to 2 F223 0 (NO TEST) Direct Input/Output Settings (Read/Write Setting) C850 Direct Input Default States (8 items) 0 to 1 F108 0 (Off) B-60 L30 Line Current Differential System GE Multilin...
  • Page 535 ...Repeated for Remote Input 21 D072 ...Repeated for Remote Input 22 D07C ...Repeated for Remote Input 23 D086 ...Repeated for Remote Input 24 D090 ...Repeated for Remote Input 25 D09A ...Repeated for Remote Input 26 GE Multilin L30 Line Current Differential System B-61...
  • Page 536 ...Repeated for Remote Output 5 D2B4 ...Repeated for Remote Output 6 D2B8 ...Repeated for Remote Output 7 D2BC ...Repeated for Remote Output 8 D2C0 ...Repeated for Remote Output 9 D2C4 ...Repeated for Remote Output 10 B-62 L30 Line Current Differential System GE Multilin...
  • Page 537 IEC 61850 GGIO2.CF.SPCSO28.ctlModel Value 0 to 2 F001 D33C IEC 61850 GGIO2.CF.SPCSO29.ctlModel Value 0 to 2 F001 D33D IEC 61850 GGIO2.CF.SPCSO30.ctlModel Value 0 to 2 F001 D33E IEC 61850 GGIO2.CF.SPCSO31.ctlModel Value 0 to 2 F001 GE Multilin L30 Line Current Differential System B-63...
  • Page 538 ...Repeated for Remote Device 15 D3BC ...Repeated for Remote Device 16 Phasor Measurement Unit Basic Configuration (Read/Write Setting) D400 PMU 1 Function 0 to 1 F102 0 (Disabled) D401 PMU 1 IDcode 1 to 65534 F001 B-64 L30 Line Current Differential System GE Multilin...
  • Page 539 0 to 4294967295 F050 Settings File Template (Read/Write Setting) ED09 Template Bitmask (750 items) 0 to 65535 F001 Phasor Measurement Unit Records (Read Only) EFFF PMU Recording Number of Triggers 0 to 65535 F001 GE Multilin L30 Line Current Differential System B-65...
  • Page 540: Data Formats

    Last 16 bits are Year (xx/xx/YYYY): 1970 to 2106 in steps of 1. 0 = 25%, 1 = 50%, 2 = 75%, 3 = 100% F102 ENUMERATION: DISABLED/ENABLED 0 = Disabled, 1 = Enabled B-66 L30 Line Current Differential System GE Multilin...
  • Page 541 ENUMERATION: ELEMENT INPUT SIGNAL TYPE F113 0 = Phasor, 1 = RMS ENUMERATION: PARITY 0 = None, 1 = Odd, 2 = Even F123 ENUMERATION: CT SECONDARY 0 = 1 A, 1 = 5 A GE Multilin L30 Line Current Differential System B-67...
  • Page 542 Non-volatile Latch 14 87L Current Differential Non-volatile Latch 15 50DD Disturbance Detector Non-volatile Latch 16 CT Failure Digital Counter 1 87L Trip (Current Differential Trip) Digital Counter 2 Stub Bus Digital Counter 3 B-68 L30 Line Current Differential System GE Multilin...
  • Page 543 RTD Input 36 Digital Element 44 RTD Input 37 Digital Element 45 RTD Input 38 Digital Element 46 RTD Input 39 Digital Element 47 RTD Input 40 Digital Element 48 RTD Input 41 GE Multilin L30 Line Current Differential System B-69...
  • Page 544 Process Bus Trouble ENUMERATION: CONTACT INPUT THRESHOLD Brick Trouble 0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC Field RTD Trouble B-70 L30 Line Current Differential System GE Multilin...
  • Page 545 0 = Disabled, 1 = Open, 2 = Closed Unauthorized Access System Integrity Recovery System Integrity Recovery 06 System Integrity Recovery 07 F147 ENUMERATION: LINE LENGTH UNITS 0 = km, 1 = miles GE Multilin L30 Line Current Differential System B-71...
  • Page 546 F174 DNA-23 UserSt-26 ENUMERATION: TRANSDUCER RTD INPUT TYPE DNA-24 UserSt-27 0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel, DNA-25 UserSt-28 2 = 100 Ohm Nickel, 3 = 10 Ohm Copper B-72 L30 Line Current Differential System GE Multilin...
  • Page 547 20 registers, 16 Bits: 1st Char MSB, 2nd Char LSB F186 F202 ENUMERATION: MEASUREMENT MODE TEXT20: 20-CHARACTER ASCII TEXT 0 = Phase to Ground, 1 = Phase to Phase 10 registers, 16 Bits: 1st Char MSB, 2nd Char LSB GE Multilin L30 Line Current Differential System B-73...
  • Page 548 0 = Calculated V0, 1 = Measured VX MMXU2.MX.TotVAr.mag.f MMXU2.MX.TotVA.mag.f F232 MMXU2.MX.TotPF.mag.f ENUMERATION: CONFIGURABLE GOOSE Tx MMXU2.MX.Hz.mag.f DATASET ITEMS MMXU2.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.PPV.phsAB.cVal.ang.f Value IEC 61850 Tx dataset item MMXU2.MX.PPV.phsBC.cVal.mag.f None MMXU2.MX.PPV.phsBC.cVal.ang.f GGIO1.ST.Ind1.q MMXU2.MX.PPV.phsCA.cVal.mag.f GGIO1.ST.Ind1.stVal MMXU2.MX.PPV.phsCA.cVal.ang.f B-74 L30 Line Current Differential System GE Multilin...
  • Page 549 MMXU3.MX.PhV.phsA.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU4.MX.VA.phsA.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU3.MX.A.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f MMXU3.MX.A.phsB.cVal.ang.f MMXU4.MX.PF.phsC.cVal.mag.f MMXU3.MX.A.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU3.MX.A.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f MMXU3.MX.A.neut.cVal.mag.f MMXU5.MX.TotVA.mag.f MMXU3.MX.A.neut.cVal.ang.f MMXU5.MX.TotPF.mag.f MMXU3.MX.W.phsA.cVal.mag.f MMXU5.MX.Hz.mag.f MMXU3.MX.W.phsB.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.mag.f GE Multilin L30 Line Current Differential System B-75...
  • Page 550 MMXU6.MX.PPV.phsAB.cVal.ang.f GGIO4.MX.AnIn23.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f GGIO4.MX.AnIn24.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f GGIO4.MX.AnIn25.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f GGIO4.MX.AnIn26.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f GGIO4.MX.AnIn27.mag.f MMXU6.MX.PhV.phsA.cVal.mag.f GGIO4.MX.AnIn28.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f GGIO4.MX.AnIn29.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f GGIO4.MX.AnIn30.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f GGIO4.MX.AnIn31.mag.f MMXU6.MX.PhV.phsC.cVal.mag.f GGIO4.MX.AnIn32.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f GGIO5.ST.UIntIn1.q MMXU6.MX.A.phsA.cVal.mag.f GGIO5.ST.UIntIn1.stVal MMXU6.MX.A.phsA.cVal.ang.f GGIO5.ST.UIntIn2.q MMXU6.MX.A.phsB.cVal.mag.f GGIO5.ST.UIntIn2.stVal MMXU6.MX.A.phsB.cVal.ang.f GGIO5.ST.UIntIn3.q MMXU6.MX.A.phsC.cVal.mag.f GGIO5.ST.UIntIn3.stVal B-76 L30 Line Current Differential System GE Multilin...
  • Page 551 GGIO3.ST.UIntIn6.stVal ↓ ↓ GGIO3.ST.UIntIn7.q GGIO1.ST.Ind64q GGIO3.ST.UIntIn7.stVal GGIO1.ST.Ind64.stVal GGIO3.ST.UIntIn8.q GGIO3.MX.AnIn1.mag.f GGIO3.ST.UIntIn8.stVal GGIO3.MX.AnIn2.mag.f GGIO3.ST.UIntIn9.q GGIO3.MX.AnIn3.mag.f GGIO3.ST.UIntIn9.stVal GGIO3.MX.AnIn4.mag.f GGIO3.ST.UIntIn10.q GGIO3.MX.AnIn5.mag.f GGIO3.ST.UIntIn10.stVal GGIO3.MX.AnIn6.mag.f GGIO3.ST.UIntIn11.q GGIO3.MX.AnIn7.mag.f GGIO3.ST.UIntIn11.stVal GGIO3.MX.AnIn8.mag.f GGIO3.ST.UIntIn12.q GGIO3.MX.AnIn9.mag.f GGIO3.ST.UIntIn12.stVal GGIO3.MX.AnIn10.mag.f GGIO3.ST.UIntIn13.q GGIO3.MX.AnIn11.mag.f GGIO3.ST.UIntIn13.stVal GGIO3.MX.AnIn12.mag.f GGIO3.ST.UIntIn14.q GE Multilin L30 Line Current Differential System B-77...
  • Page 552 U5/AC1..3 Value Instance U5/AC5..7 First U6/AC1..3 Second U6/AC5..7 Third U7/AC1..3 Fourth U7/AC5..7 Last U8/AC1..3 U8/AC5..7 F243 ENUMERATION: FIELD UNIT TYPE 0 = CC-05, 1 = CV-05, 2 = CC-01, 3 = CV-01 B-78 L30 Line Current Differential System GE Multilin...
  • Page 553 [28] INSERT (via keypad only) ENUMERATION: BRICK RTD TYPE [30] DELETE (via keypad only) [32] END 0 = 100 Ohm Nickel, 1 = 120 Ohm Nickel, 2 = 100 Ohm Platinum [34] NOT (1 INPUT) GE Multilin L30 Line Current Differential System B-79...
  • Page 554 Low byte of register indicates LED status with bit 0 representing the top LED and bit 7 the bottom LED. A bit value of 1 indicates the LED is on, 0 indicates the LED is off. 0 = Off, 1 = On B-80 L30 Line Current Differential System GE Multilin...
  • Page 555 90° lag 0 = Automatic Overwrite, 1 = Protected 120° lag 150° lag 180° lag F543 ENUMERATION: PMU PHASORS 210° lag 240° lag Value Phasor Value Phasor 270° lag 300° lag 330° lag GE Multilin L30 Line Current Differential System B-81...
  • Page 556 ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT PDIS8.ST.Op.general PDIS9.ST.Str.general Enumeration Remote double-point status input PDIS9.ST.Op.general None PDIS10.ST.Str.general Remote input 1 PDIS10.ST.Op.general Remote input 2 PIOC1.ST.Str.general Remote input 3 PIOC1.ST.Op.general ↓ ↓ PIOC2.ST.Str.general Remote input 64 PIOC2.ST.Op.general PIOC3.ST.Str.general B-82 L30 Line Current Differential System GE Multilin...
  • Page 557 PIOC22.ST.Str.general PIOC48.ST.Op.general PIOC22.ST.Op.general PIOC49.ST.Str.general PIOC23.ST.Str.general PIOC49.ST.Op.general PIOC23.ST.Op.general PIOC50.ST.Str.general PIOC24.ST.Str.general PIOC50.ST.Op.general PIOC24.ST.Op.general PIOC51.ST.Str.general PIOC25.ST.Str.general PIOC51.ST.Op.general PIOC25.ST.Op.general PIOC52.ST.Str.general PIOC26.ST.Str.general PIOC52.ST.Op.general PIOC26.ST.Op.general PIOC53.ST.Str.general PIOC27.ST.Str.general PIOC53.ST.Op.general PIOC27.ST.Op.general PIOC54.ST.Str.general PIOC28.ST.Str.general PIOC54.ST.Op.general PIOC28.ST.Op.general PIOC55.ST.Str.general PIOC29.ST.Str.general PIOC55.ST.Op.general PIOC29.ST.Op.general PIOC56.ST.Str.general GE Multilin L30 Line Current Differential System B-83...
  • Page 558 PTOC3.ST.Str.general PTOV5.ST.Op.general PTOC3.ST.Op.general PTOV6.ST.Str.general PTOC4.ST.Str.general PTOV6.ST.Op.general PTOC4.ST.Op.general PTOV7.ST.Str.general PTOC5.ST.Str.general PTOV7.ST.Op.general PTOC5.ST.Op.general PTOV8.ST.Str.general PTOC6.ST.Str.general PTOV8.ST.Op.general PTOC6.ST.Op.general PTOV9.ST.Str.general PTOC7.ST.Str.general PTOV9.ST.Op.general PTOC7.ST.Op.general PTOV10.ST.Str.general PTOC8.ST.Str.general PTOV10.ST.Op.general PTOC8.ST.Op.general PTRC1.ST.Tr.general PTOC9.ST.Str.general PTRC1.ST.Op.general PTOC9.ST.Op.general PTRC2.ST.Tr.general PTOC10.ST.Str.general PTRC2.ST.Op.general PTOC10.ST.Op.general PTRC3.ST.Tr.general B-84 L30 Line Current Differential System GE Multilin...
  • Page 559 RBRF3.ST.OpEx.general RREC1.ST.AutoRecSt.stVal RBRF3.ST.OpIn.general RREC2.ST.Op.general RBRF4.ST.OpEx.general RREC2.ST.AutoRecSt.stVal RBRF4.ST.OpIn.general RREC3.ST.Op.general RBRF5.ST.OpEx.general RREC3.ST.AutoRecSt.stVal RBRF5.ST.OpIn.general RREC4.ST.Op.general RBRF6.ST.OpEx.general RREC4.ST.AutoRecSt.stVal RBRF6.ST.OpIn.general RREC5.ST.Op.general RBRF7.ST.OpEx.general RREC5.ST.AutoRecSt.stVal RBRF7.ST.OpIn.general RREC6.ST.Op.general RBRF8.ST.OpEx.general RREC6.ST.AutoRecSt.stVal RBRF8.ST.OpIn.general CSWI1.ST.Loc.stVal RBRF9.ST.OpEx.general CSWI1.ST.Pos.stVal RBRF9.ST.OpIn.general CSWI2.ST.Loc.stVal RBRF10.ST.OpEx.general CSWI2.ST.Pos.stVal RBRF10.ST.OpIn.general CSWI3.ST.Loc.stVal GE Multilin L30 Line Current Differential System B-85...
  • Page 560 CSWI22.ST.Loc.stVal GGIO1.ST.Ind36.stVal CSWI22.ST.Pos.stVal GGIO1.ST.Ind37.stVal CSWI23.ST.Loc.stVal GGIO1.ST.Ind38.stVal CSWI23.ST.Pos.stVal GGIO1.ST.Ind39.stVal CSWI24.ST.Loc.stVal GGIO1.ST.Ind40.stVal CSWI24.ST.Pos.stVal GGIO1.ST.Ind41.stVal CSWI25.ST.Loc.stVal GGIO1.ST.Ind42.stVal CSWI25.ST.Pos.stVal GGIO1.ST.Ind43.stVal CSWI26.ST.Loc.stVal GGIO1.ST.Ind44.stVal CSWI26.ST.Pos.stVal GGIO1.ST.Ind45.stVal CSWI27.ST.Loc.stVal GGIO1.ST.Ind46.stVal CSWI27.ST.Pos.stVal GGIO1.ST.Ind47.stVal CSWI28.ST.Loc.stVal GGIO1.ST.Ind48.stVal CSWI28.ST.Pos.stVal GGIO1.ST.Ind49.stVal CSWI29.ST.Loc.stVal GGIO1.ST.Ind50.stVal CSWI29.ST.Pos.stVal GGIO1.ST.Ind51.stVal B-86 L30 Line Current Differential System GE Multilin...
  • Page 561 GGIO1.ST.Ind89.stVal MMXU1.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind90.stVal MMXU1.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind91.stVal MMXU1.MX.PhV.phsC.cVal.mag.f GGIO1.ST.Ind92.stVal MMXU1.MX.PhV.phsC.cVal.ang.f GGIO1.ST.Ind93.stVal MMXU1.MX.A.phsA.cVal.mag.f GGIO1.ST.Ind94.stVal MMXU1.MX.A.phsA.cVal.ang.f GGIO1.ST.Ind95.stVal MMXU1.MX.A.phsB.cVal.mag.f GGIO1.ST.Ind96.stVal MMXU1.MX.A.phsB.cVal.ang.f GGIO1.ST.Ind97.stVal MMXU1.MX.A.phsC.cVal.mag.f GGIO1.ST.Ind98.stVal MMXU1.MX.A.phsC.cVal.ang.f GGIO1.ST.Ind99.stVal MMXU1.MX.A.neut.cVal.mag.f GGIO1.ST.Ind100.stVal MMXU1.MX.A.neut.cVal.ang.f GGIO1.ST.Ind101.stVal MMXU1.MX.W.phsA.cVal.mag.f GGIO1.ST.Ind102.stVal MMXU1.MX.W.phsB.cVal.mag.f GGIO1.ST.Ind103.stVal MMXU1.MX.W.phsC.cVal.mag.f GGIO1.ST.Ind104.stVal MMXU1.MX.VAr.phsA.cVal.mag.f GE Multilin L30 Line Current Differential System B-87...
  • Page 562 MMXU2.MX.VAr.phsB.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.ang.f MMXU2.MX.VAr.phsC.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.mag.f MMXU2.MX.VA.phsA.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.ang.f MMXU2.MX.VA.phsB.cVal.mag.f MMXU4.MX.PhV.phsA.cVal.mag.f MMXU2.MX.VA.phsC.cVal.mag.f MMXU4.MX.PhV.phsA.cVal.ang.f MMXU2.MX.PF.phsA.cVal.mag.f MMXU4.MX.PhV.phsB.cVal.mag.f MMXU2.MX.PF.phsB.cVal.mag.f MMXU4.MX.PhV.phsB.cVal.ang.f MMXU2.MX.PF.phsC.cVal.mag.f MMXU4.MX.PhV.phsC.cVal.mag.f MMXU3.MX.TotW.mag.f MMXU4.MX.PhV.phsC.cVal.ang.f MMXU3.MX.TotVAr.mag.f MMXU4.MX.A.phsA.cVal.mag.f MMXU3.MX.TotVA.mag.f MMXU4.MX.A.phsA.cVal.ang.f MMXU3.MX.TotPF.mag.f MMXU4.MX.A.phsB.cVal.mag.f MMXU3.MX.Hz.mag.f MMXU4.MX.A.phsB.cVal.ang.f MMXU3.MX.PPV.phsAB.cVal.mag.f MMXU4.MX.A.phsC.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.ang.f MMXU4.MX.A.phsC.cVal.ang.f MMXU3.MX.PPV.phsBC.cVal.mag.f MMXU4.MX.A.neut.cVal.mag.f B-88 L30 Line Current Differential System GE Multilin...
  • Page 563 MMXU5.MX.A.neut.cVal.ang.f GGIO4.MX.AnIn4.mag.f MMXU5.MX.W.phsA.cVal.mag.f GGIO4.MX.AnIn5.mag.f MMXU5.MX.W.phsB.cVal.mag.f GGIO4.MX.AnIn6.mag.f MMXU5.MX.W.phsC.cVal.mag.f GGIO4.MX.AnIn7.mag.f MMXU5.MX.VAr.phsA.cVal.mag.f GGIO4.MX.AnIn8.mag.f MMXU5.MX.VAr.phsB.cVal.mag.f GGIO4.MX.AnIn9.mag.f MMXU5.MX.VAr.phsC.cVal.mag.f GGIO4.MX.AnIn10.mag.f MMXU5.MX.VA.phsA.cVal.mag.f GGIO4.MX.AnIn11.mag.f MMXU5.MX.VA.phsB.cVal.mag.f GGIO4.MX.AnIn12.mag.f MMXU5.MX.VA.phsC.cVal.mag.f GGIO4.MX.AnIn13.mag.f MMXU5.MX.PF.phsA.cVal.mag.f GGIO4.MX.AnIn14.mag.f MMXU5.MX.PF.phsB.cVal.mag.f GGIO4.MX.AnIn15.mag.f MMXU5.MX.PF.phsC.cVal.mag.f GGIO4.MX.AnIn16.mag.f MMXU6.MX.TotW.mag.f GGIO4.MX.AnIn17.mag.f MMXU6.MX.TotVAr.mag.f GGIO4.MX.AnIn18.mag.f MMXU6.MX.TotVA.mag.f GGIO4.MX.AnIn19.mag.f GE Multilin L30 Line Current Differential System B-89...
  • Page 564 GGIO1.ST.Ind6.stVal XSWI13.ST.Loc.stVal GGIO1.ST.Ind7.q XSWI13.ST.Pos.stVal GGIO1.ST.Ind7.stVal XSWI14.ST.Loc.stVal GGIO1.ST.Ind8.q XSWI14.ST.Pos.stVal GGIO1.ST.Ind8.stVal XSWI15.ST.Loc.stVal GGIO1.ST.Ind9.q XSWI15.ST.Pos.stVal GGIO1.ST.Ind9.stVal XSWI16.ST.Loc.stVal GGIO1.ST.Ind10.q XSWI16.ST.Pos.stVal GGIO1.ST.Ind10.stVal XSWI17.ST.Loc.stVal GGIO1.ST.Ind11.q XSWI17.ST.Pos.stVal GGIO1.ST.Ind11.stVal XSWI18.ST.Loc.stVal GGIO1.ST.Ind12.q XSWI18.ST.Pos.stVal GGIO1.ST.Ind12.stVal XSWI19.ST.Loc.stVal GGIO1.ST.Ind13.q XSWI19.ST.Pos.stVal GGIO1.ST.Ind13.stVal XSWI20.ST.Loc.stVal GGIO1.ST.Ind14.q XSWI20.ST.Pos.stVal B-90 L30 Line Current Differential System GE Multilin...
  • Page 565 GGIO1.ST.Ind33.q GGIO1.ST.Ind59.stVal GGIO1.ST.Ind33.stVal GGIO1.ST.Ind60.q GGIO1.ST.Ind34.q GGIO1.ST.Ind60.stVal GGIO1.ST.Ind34.stVal GGIO1.ST.Ind61.q GGIO1.ST.Ind35.q GGIO1.ST.Ind61.stVal GGIO1.ST.Ind35.stVal GGIO1.ST.Ind62.q GGIO1.ST.Ind36.q GGIO1.ST.Ind62.stVal GGIO1.ST.Ind36.stVal GGIO1.ST.Ind63.q GGIO1.ST.Ind37.q GGIO1.ST.Ind63.stVal GGIO1.ST.Ind37.stVal GGIO1.ST.Ind64.q GGIO1.ST.Ind38.q GGIO1.ST.Ind64.stVal GGIO1.ST.Ind38.stVal GGIO1.ST.Ind65.q GGIO1.ST.Ind39.q GGIO1.ST.Ind65.stVal GGIO1.ST.Ind39.stVal GGIO1.ST.Ind66.q GGIO1.ST.Ind40.q GGIO1.ST.Ind66.stVal GGIO1.ST.Ind40.stVal GGIO1.ST.Ind67.q GE Multilin L30 Line Current Differential System B-91...
  • Page 566 GGIO1.ST.Ind86.q GGIO1.ST.Ind112.stVal GGIO1.ST.Ind86.stVal GGIO1.ST.Ind113.q GGIO1.ST.Ind87.q GGIO1.ST.Ind113.stVal GGIO1.ST.Ind87.stVal GGIO1.ST.Ind114.q GGIO1.ST.Ind88.q GGIO1.ST.Ind114.stVal GGIO1.ST.Ind88.stVal GGIO1.ST.Ind115.q GGIO1.ST.Ind89.q GGIO1.ST.Ind115.stVal GGIO1.ST.Ind89.stVal GGIO1.ST.Ind116.q GGIO1.ST.Ind90.q GGIO1.ST.Ind116.stVal GGIO1.ST.Ind90.stVal GGIO1.ST.Ind117.q GGIO1.ST.Ind91.q GGIO1.ST.Ind117.stVal GGIO1.ST.Ind91.stVal GGIO1.ST.Ind118.q GGIO1.ST.Ind92.q GGIO1.ST.Ind118.stVal GGIO1.ST.Ind92.stVal GGIO1.ST.Ind119.q GGIO1.ST.Ind93.q GGIO1.ST.Ind119.stVal GGIO1.ST.Ind93.stVal GGIO1.ST.Ind120.q B-92 L30 Line Current Differential System GE Multilin...
  • Page 567 MMXU1.MX.A.phsB.cVal.ang.f MMXU2.MX.PF.phsC.cVal.mag.f MMXU1.MX.A.phsC.cVal.mag.f MMXU3.MX.TotW.mag.f MMXU1.MX.A.phsC.cVal.ang.f MMXU3.MX.TotVAr.mag.f MMXU1.MX.A.neut.cVal.mag.f MMXU3.MX.TotVA.mag.f MMXU1.MX.A.neut.cVal.ang.f MMXU3.MX.TotPF.mag.f MMXU1.MX.W.phsA.cVal.mag.f MMXU3.MX.Hz.mag.f MMXU1.MX.W.phsB.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.mag.f MMXU1.MX.W.phsC.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.ang.f MMXU1.MX.VAr.phsA.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.mag.f MMXU1.MX.VAr.phsB.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.ang.f MMXU1.MX.VAr.phsC.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.mag.f MMXU1.MX.VA.phsA.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.ang.f MMXU1.MX.VA.phsB.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.mag.f MMXU1.MX.VA.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU1.MX.PF.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU1.MX.PF.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f GE Multilin L30 Line Current Differential System B-93...
  • Page 568 MMXU4.MX.PhV.phsC.cVal.mag.f MMXU5.MX.VA.phsA.cVal.mag.f MMXU4.MX.PhV.phsC.cVal.ang.f MMXU5.MX.VA.phsB.cVal.mag.f MMXU4.MX.A.phsA.cVal.mag.f MMXU5.MX.VA.phsC.cVal.mag.f MMXU4.MX.A.phsA.cVal.ang.f MMXU5.MX.PF.phsA.cVal.mag.f MMXU4.MX.A.phsB.cVal.mag.f MMXU5.MX.PF.phsB.cVal.mag.f MMXU4.MX.A.phsB.cVal.ang.f MMXU5.MX.PF.phsC.cVal.mag.f MMXU4.MX.A.phsC.cVal.mag.f MMXU6.MX.TotW.mag.f MMXU4.MX.A.phsC.cVal.ang.f MMXU6.MX.TotVAr.mag.f MMXU4.MX.A.neut.cVal.mag.f MMXU6.MX.TotVA.mag.f MMXU4.MX.A.neut.cVal.ang.f MMXU6.MX.TotPF.mag.f MMXU4.MX.W.phsA.cVal.mag.f MMXU6.MX.Hz.mag.f MMXU4.MX.W.phsB.cVal.mag.f MMXU6.MX.PPV.phsAB.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU6.MX.PPV.phsAB.cVal.ang.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f B-94 L30 Line Current Differential System GE Multilin...
  • Page 569 GGIO4.MX.AnIn11.mag.f GGIO5.ST.UIntIn16.stVal GGIO4.MX.AnIn12.mag.f PDIF1.ST.Str.general GGIO4.MX.AnIn13.mag.f PDIF1.ST.Op.general GGIO4.MX.AnIn14.mag.f PDIF2.ST.Str.general GGIO4.MX.AnIn15.mag.f PDIF2.ST.Op.general GGIO4.MX.AnIn16.mag.f PDIF3.ST.Str.general GGIO4.MX.AnIn17.mag.f PDIF3.ST.Op.general GGIO4.MX.AnIn18.mag.f PDIF4.ST.Str.general GGIO4.MX.AnIn19.mag.f PDIF4.ST.Op.general GGIO4.MX.AnIn20.mag.f PDIS1.ST.Str.general GGIO4.MX.AnIn21.mag.f PDIS1.ST.Op.general GGIO4.MX.AnIn22.mag.f PDIS2.ST.Str.general GGIO4.MX.AnIn23.mag.f PDIS2.ST.Op.general GGIO4.MX.AnIn24.mag.f PDIS3.ST.Str.general GGIO4.MX.AnIn25.mag.f PDIS3.ST.Op.general GGIO4.MX.AnIn26.mag.f PDIS4.ST.Str.general GE Multilin L30 Line Current Differential System B-95...
  • Page 570 PIOC13.ST.Str.general PIOC39.ST.Op.general PIOC13.ST.Op.general PIOC40.ST.Str.general PIOC14.ST.Str.general PIOC40.ST.Op.general PIOC14.ST.Op.general PIOC41.ST.Str.general PIOC15.ST.Str.general PIOC41.ST.Op.general PIOC15.ST.Op.general PIOC42.ST.Str.general PIOC16.ST.Str.general PIOC42.ST.Op.general PIOC16.ST.Op.general PIOC43.ST.Str.general PIOC17.ST.Str.general PIOC43.ST.Op.general PIOC17.ST.Op.general PIOC44.ST.Str.general PIOC18.ST.Str.general PIOC44.ST.Op.general PIOC18.ST.Op.general PIOC45.ST.Str.general PIOC19.ST.Str.general PIOC45.ST.Op.general PIOC19.ST.Op.general PIOC46.ST.Str.general PIOC20.ST.Str.general PIOC46.ST.Op.general PIOC20.ST.Op.general PIOC47.ST.Str.general B-96 L30 Line Current Differential System GE Multilin...
  • Page 571 PIOC66.ST.Str.general PTOC20.ST.Op.general PIOC66.ST.Op.general PTOC21.ST.Str.general PIOC67.ST.Str.general PTOC21.ST.Op.general PIOC67.ST.Op.general PTOC22.ST.Str.general PIOC68.ST.Str.general PTOC22.ST.Op.general PIOC68.ST.Op.general PTOC23.ST.Str.general PIOC69.ST.Str.general PTOC23.ST.Op.general PIOC69.ST.Op.general PTOC24.ST.Str.general PIOC70.ST.Str.general PTOC24.ST.Op.general PIOC70.ST.Op.general PTOV1.ST.Str.general PIOC71.ST.Str.general PTOV1.ST.Op.general PIOC71.ST.Op.general PTOV2.ST.Str.general PIOC72.ST.Str.general PTOV2.ST.Op.general PIOC72.ST.Op.general PTOV3.ST.Str.general PTOC1.ST.Str.general PTOV3.ST.Op.general PTOC1.ST.Op.general PTOV4.ST.Str.general GE Multilin L30 Line Current Differential System B-97...
  • Page 572 PTUV7.ST.Str.general RBRF20.ST.OpIn.general PTUV7.ST.Op.general RBRF21.ST.OpEx.general PTUV8.ST.Str.general RBRF21.ST.OpIn.general PTUV8.ST.Op.general RBRF22.ST.OpEx.general PTUV9.ST.Str.general RBRF22.ST.OpIn.general PTUV9.ST.Op.general RBRF23.ST.OpEx.general PTUV10.ST.Str.general RBRF23.ST.OpIn.general PTUV10.ST.Op.general RBRF24.ST.OpEx.general PTUV11.ST.Str.general RBRF24.ST.OpIn.general PTUV11.ST.Op.general RFLO1.MX.FltDiskm.mag.f PTUV12.ST.Str.general RFLO2.MX.FltDiskm.mag.f PTUV12.ST.Op.general RFLO3.MX.FltDiskm.mag.f PTUV13.ST.Str.general RFLO4.MX.FltDiskm.mag.f PTUV13.ST.Op.general RFLO5.MX.FltDiskm.mag.f RBRF1.ST.OpEx.general RPSB1.ST.Str.general RBRF1.ST.OpIn.general RPSB1.ST.Op.general B-98 L30 Line Current Differential System GE Multilin...
  • Page 573 CSWI13.ST.Loc.stVal XSWI9.ST.Pos.stVal CSWI13.ST.Pos.stVal XSWI10.ST.Loc.stVal CSWI14.ST.Loc.stVal XSWI10.ST.Pos.stVal CSWI14.ST.Pos.stVal XSWI11.ST.Loc.stVal CSWI15.ST.Loc.stVal XSWI11.ST.Pos.stVal CSWI15.ST.Pos.stVal XSWI12.ST.Loc.stVal CSWI16.ST.Loc.stVal XSWI12.ST.Pos.stVal CSWI16.ST.Pos.stVal XSWI13.ST.Loc.stVal CSWI17.ST.Loc.stVal XSWI13.ST.Pos.stVal CSWI17.ST.Pos.stVal XSWI14.ST.Loc.stVal CSWI18.ST.Loc.stVal XSWI14.ST.Pos.stVal CSWI18.ST.Pos.stVal XSWI15.ST.Loc.stVal CSWI19.ST.Loc.stVal XSWI15.ST.Pos.stVal CSWI19.ST.Pos.stVal XSWI16.ST.Loc.stVal CSWI20.ST.Loc.stVal XSWI16.ST.Pos.stVal CSWI20.ST.Pos.stVal XSWI17.ST.Loc.stVal GE Multilin L30 Line Current Differential System B-99...
  • Page 574 Has been activated, whether the password has been set. XSWI24.ST.Loc.stVal 1 = Bit#0, Administrator password was set. The list is continued for XSWI24.ST.Pos.stVal all other roles (Engineer = bit#2, Operator = bit#3, Observer = XCBR1.ST.Loc.stVal bit#3). XCBR1.ST.Pos.stVal XCBR2.ST.Loc.stVal B-100 L30 Line Current Differential System GE Multilin...
  • Page 575: Iec 61850

    The L30 relay supports IEC 61850 server services over both TCP/IP and TP4/CLNP (OSI) communication protocol stacks. The TP4/CLNP profile requires the L30 to have a network address or Network Service Access Point (NSAP) to establish a communication link. The TCP/IP profile requires the L30 to have an IP address to establish communications. These addresses are located in the ...
  • Page 576: File Transfer By Iec 61850

    APPENDIX C C.1.3 FILE TRANSFER BY IEC 61850 The L30 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as an example. In the AX-S4 61850 Explorer window, click the Tools menu and access the SISCO File Transfer Utility.
  • Page 577: Server Data Organization

    C.2.2 GGIO1: DIGITAL STATUS VALUES The GGIO1 logical node is available in the L30 to provide access to as many 128 digital status points and associated time- stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients.
  • Page 578: Mmxu: Analog Measured Values

    A limited number of measured analog values are available through the MMXU logical nodes. Each MMXU logical node provides data from a L30 current and voltage source. There is one MMXU available for each con- figurable source (programmed in the ...
  • Page 579 The protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 is PIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the L30 protection elements, these flags take their values from the pickup and operate FlexLogic™ operands for the corresponding element.
  • Page 580: Server Features And Configuration

    C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the L30. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of the two character strings programmed in the settings.
  • Page 581: Logical Node Name Prefixes

    A built-in TCP/IP connection timeout of two minutes is employed by the L30 to detect ‘dead’ connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the L30. This frees up the con- nection to be used by other clients.
  • Page 582: Generic Substation Event Services: Gsse And Goose

    MAC address for GSSE messages. If GSSE DESTINATION MAC ADDRESS a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the L30 will use the source Ether- net MAC address as the destination, with the multicast bit set.
  • Page 583 The L30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 584: Ethernet Mac Address For Gsse/Goose

    REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic™ equations or other settings. The L30 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.
  • Page 585: Gsse Id And Goose Id Settings

    GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the L30 is configured to use an automated multicast MAC scheme. If the L30 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina- tion MAC will be the same as the local MAC address, but with the multicast bit set.
  • Page 586: Iec 61850 Implementation Via Enervista Ur Setup

    An ICD file is generated for the L30 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 587: Configuring Iec 61850 Settings

    Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the L30 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file.
  • Page 588: About Icd Files

    Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
  • Page 589 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. GE Multilin L30 Line Current Differential System C-15...
  • Page 590 Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure C–4: ICD FILE STRUCTURE, IED NODE C-16 L30 Line Current Differential System GE Multilin...
  • Page 591 BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure C–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE GE Multilin L30 Line Current Differential System C-17...
  • Page 592: Creating An Icd File With Enervista Ur Setup

    The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file. The time to create an ICD file from the offline L30 settings file is typically much quicker than create an ICD file directly from the relay.
  • Page 593 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE GE Multilin L30 Line Current Differential System C-19...
  • Page 594 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. C-20 L30 Line Current Differential System GE Multilin...
  • Page 595: Importing An Scd File With Enervista Ur Setup

    Figure C–9: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the L30 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
  • Page 596 The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
  • Page 597: Acsi Conformance

    REPORTING Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion GE Multilin L30 Line Current Differential System C-23...
  • Page 598: Acsi Services Conformance Statement

    UR FAMILY PUBLISHER SERVER (CLAUSE 6) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 7) Associate Abort Release LOGICAL DEVICE (CLAUSE 8) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 9) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 10) GetDataValues SetDataValues GetDataDirectory GetDataDefinition C-24 L30 Line Current Differential System GE Multilin...
  • Page 599 S27-3 data-update (dupd) GetURCBValues SetURCBValues LOGGING (CLAUSE 14) LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 14.3.5.3.4) GOOSE-CONTROL-BLOCK SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK SendGSSEMessage GetReference GE Multilin L30 Line Current Differential System C-25...
  • Page 600 NOTE c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) C-26 L30 Line Current Differential System GE Multilin...
  • Page 601: C.7.1 Logical Nodes Table

    RDRE: Disturbance recorder function RADR: Disturbance recorder channel analogue RBDR: Disturbance recorder channel binary RDRS: Disturbance record handling RBRF: Breaker failure RDIR: Directional element RFLO: Fault locator RPSB: Power swing detection/blocking RREC: Autoreclosing GE Multilin L30 Line Current Differential System C-27...
  • Page 602 T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TCTR: Current transformer TVTR: Voltage transformer Y: LOGICAL NODES FOR POWER TRANSFORMERS YEFN: Earth fault neutralizer (Peterson coil) YLTC: Tap changer YPSH: Power shunt YPTR: Power transformer C-28 L30 Line Current Differential System GE Multilin...
  • Page 603 ZCON: Converter ZGEN: Generator ZGIL: Gas insulated line ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component GE Multilin L30 Line Current Differential System C-29...
  • Page 604 C.7 LOGICAL NODES APPENDIX C C-30 L30 Line Current Differential System GE Multilin...
  • Page 605: Interoperability Document

    Balanced Transmission Not Present (Balanced Transmission Only)   Unbalanced Transmission One Octet  Two Octets  Structured  Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin L30 Line Current Differential System...
  • Page 606  <18> := Packed start events of protection equipment with time tag M_EP_TB_1  <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1  <20> := Packed single-point information with status change detection M_SP_NA_1 L30 Line Current Differential System GE Multilin...
  • Page 607  <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1  <104> := Test command C_TS_NA_1  <105> := Reset process command C_RP_NA_1  <106> := Delay acquisition command C_CD_NA_1  <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin L30 Line Current Differential System...
  • Page 608 •Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 L30 Line Current Differential System GE Multilin...
  • Page 609 M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin L30 Line Current Differential System...
  • Page 610 F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization:  Remote initialization Cyclic Data Transmission:  Cyclic data transmission Read Procedure:  Read procedure L30 Line Current Differential System GE Multilin...
  • Page 611  Mode B: Local freeze with counter interrogation  Mode C: Freeze and transmit by counter-interrogation commands  Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously  Counter read  Counter freeze without reset GE Multilin L30 Line Current Differential System...
  • Page 612 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs L30 Line Current Differential System GE Multilin...
  • Page 613: Point List

    The IEC 60870-5-104 data points are configured through the    SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin L30 Line Current Differential System...
  • Page 614 D.1 IEC 60870-5-104 APPENDIX D D-10 L30 Line Current Differential System GE Multilin...
  • Page 615: Device Profile Document

    Maximum Data Link Re-tries: Maximum Application Layer Re-tries:  None  None  Fixed at 3  Configurable  Configurable Requires Data Link Layer Confirmation:  Never  Always  Sometimes  Configurable GE Multilin L30 Line Current Differential System...
  • Page 616 FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. L30 Line Current Differential System GE Multilin...
  • Page 617  16 Bits (Counter 8) Default Variation: 1  32 Bits (Counters 0 to 7, 9)  Point-by-point list attached  Other Value: _____  Point-by-point list attached Sends Multi-Fragment Responses:  Yes  No GE Multilin L30 Line Current Differential System...
  • Page 618: E.1.2 Implementation Table

    Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. L30 Line Current Differential System GE Multilin...
  • Page 619 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. GE Multilin L30 Line Current Differential System...
  • Page 620 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. L30 Line Current Differential System GE Multilin...
  • Page 621 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the L30 is not restarted, but the DNP process is restarted. GE Multilin L30 Line Current Differential System...
  • Page 622: Dnp Point Lists

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 L30 Line Current Differential System GE Multilin...
  • Page 623: Binary And Control Relay Output

    Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin L30 Line Current Differential System...
  • Page 624: Counters

    Events Since Last Clear A counter freeze command has no meaning for counters 8 and 9. L30 Digital Counter values are represented as 32-bit inte- gers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values.
  • Page 625: Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin L30 Line Current Differential System E-11...
  • Page 626 E.2 DNP POINT LISTS APPENDIX E E-12 L30 Line Current Differential System GE Multilin...
  • Page 627: Change Notes

    11-2840 1601-9050-X2 6.0x 5 April 2012 12-3254 1601-9050-X3 6.0x 31 August 2015 12-0025 F.1.2 CHANGES TO THE L30 MANUAL Table F–2: MAJOR UPDATES FOR L30 MANUAL REVISION X3 PAGE PAGE CHANGE DESCRIPTION (X2) (X3) Update Updated content throughout document Update...
  • Page 628 Removed references to 9L, 9M, 9P, and 9R modules in table and figure from section 3.2.9 CPU Communication Ports Update Updated Figure 3-5 L30 Vertical Mounting and Dimensions to version A4 Update Update Figure 3-12 Typical Wiring Diagram to version A2...
  • Page 629 APPENDIX F F.1 CHANGE NOTES Table F–4: MAJOR UPDATES FOR L30 MANUAL REVISION X1 PAGE PAGE CHANGE DESCRIPTION (W1) (X1) Title Title Update Manual part number to 1601-9050-X1 3-23 3-23 Update Updated RS485 PORTS section Table F–5: MAJOR UPDATES FOR L30 MANUAL REVISION W1...
  • Page 630: Abbreviations

    MTR ....Motor FD ....Fault Detector MVA ....MegaVolt-Ampere (total 3-phase) FDH....Fault Detector high-set MVA_A ... MegaVolt-Ampere (phase A) FDL ....Fault Detector low-set MVA_B ... MegaVolt-Ampere (phase B) FLA....Full Load Current L30 Line Current Differential System GE Multilin...
  • Page 631 ROD ....Remote Open Detector WRT....With Respect To RST ....Reset RSTR ..... Restrained X .....Reactance RTD....Resistance Temperature Detector XDUCER..Transducer RTU....Remote Terminal Unit XFMR....Transformer RX (Rx) ..Receive, Receiver Z......Impedance, Zone GE Multilin L30 Line Current Differential System...
  • Page 632: Warranty

    F.3.1 GE MULTILIN WARRANTY For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Digital Energy Terms and Conditions at https://www.gedigitalenergy.com/multilin/warranty.htm...
  • Page 633 Modbus registers ............B-20 Modbus registers ............B-42 CAUTIONS ................. 1-1 settings ............... 5-166 CE APPROVALS .............. 2-28 specifications ..............2-19 CHANGES TO L90 MANUAL ..........F-1 CHANNEL ASYMMETRY settings ................. 5-67 CHANNEL COMMUNICATION .......... 3-28 GE Multilin L30 Line Current Differential System...
  • Page 634 DATE ................7-2 CONTACT OUTPUTS DCMA INPUTS ..............6-21 actual values ..............6-4 Modbus registers ..........B-19, B-38 FlexLogic™ operands ........5-108, 5-109 settings ................ 5-220 Modbus registers .........B-11, B-17, B-59 specifications ..............2-23 settings ............... 5-209 L30 Line Current Differential System GE Multilin...
  • Page 635 ............3-51 FlexLogic™ operands ..........5-108 settings ................. 5-38 logic ................5-77 uploading setting files ............ 3-52 settings ................. 5-75 EVENT CAUSE INDICATORS ........4-16, 4-17 DISPLAY ............1-17, 4-23, 5-13 DISPOSAL ..............12-10 GE Multilin L30 Line Current Differential System...
  • Page 636 FLEXCURVES™ equation ..............5-134 G.703 ............ 3-31, 3-32, 3-33, 3-37 Modbus registers ..........B-30, B-48 G.703 WIRE SIZE .............3-31 settings ................. 5-78 GE TYPE IAC CURVES ..........5-133 specifications..............2-20 GROUND CURRENT METERING ........6-15 table ................5-78 GROUND IOC FLEXELEMENTS™ FlexLogic™ operands ........... 5-105 actual values ..............
  • Page 637 ..............2-22 INTELLIGENT ELECTRONIC DEVICE ........ 1-3 power ................2-22 INTER-RELAY COMMUNICATIONS ......2-11, 2-26 voltage ................2-22 INTRODUCTION ..............1-3 METERING CONVENTIONS ..........6-11 INVERSE TIME UNDERVOLTAGE ........5-162 IN-ZONE TRANSFORMER ..........5-70 GE Multilin L30 Line Current Differential System...
  • Page 638 IRIG-B ................2-24 Modbus registers ............B-36 latching outputs ........... 2-23, 5-209 settings ............... 5-150 remote outputs ............. 5-215 specifications..............2-18 virtual outputs .............. 5-211 NEUTRAL DIRECTIONAL OC OVERCURRENT CURVE TYPES ........5-130 Modbus registers ............B-38 L30 Line Current Differential System GE Multilin...
  • Page 639 PHASE ROTATION ............5-61 device ID ..............5-213 PHASE TIME OVERCURRENT error messages .............. 7-10 see entry for PHASE TOC FlexLogic™ operands ........... 5-110 Modbus registers ..........B-11, B-17 settings ............... 5-212 statistics ................6-6 GE Multilin L30 Line Current Differential System...
  • Page 640 FlexLogic™ operands ..........5-107 Modbus registers ............B-43 logic ................5-178 SUPERVISING ELEMENTS ..........5-168 Modbus registers ............B-47 SURGE IMMUNITY ............2-27 settings ............... 5-173 SYMMETRICAL COMPONENTS METERING .....6-11 specifications..............2-21 timing ..............5-176, 5-177 viii L30 Line Current Differential System GE Multilin...
  • Page 641 ................. 5-48 TRACKING FREQUENCY ........6-18, B-43 USERST-1 BIT PAIR ............5-215 TRANSDUCER I/O actual values ..............6-21 settings ............. 5-220, 5-221 specifications ..............2-23 wiring ................3-20 VIBRATION TESTING ............2-27 GE Multilin L30 Line Current Differential System...
  • Page 642 VOLTAGE RESTRAINT CHARACTERISTIC ....5-135 WITHDRAWAL FROM OPERATION ........12-7 VT FUSE FAILURE logic ................5-200 settings ............... 5-199 VT INPUTS ............3-11, 5-7, 5-61 VT WIRING ..............3-11 ZERO SEQUENCE CORE BALANCE .........3-11 ZERO-SEQUENCE CURRENT REMOVAL ......5-67 L30 Line Current Differential System GE Multilin...

Table of Contents