GE ALPS Instruction Manual page 273

Advanced line protection system
Table of Contents

Advertisement

12 ASCII COMMUNICATIONS
Table 12–2: ASCII COMMAND LIST (Sheet 2 of 5)
ASCII
COMMAND DESCRIPTION
COMMAND
MNEMONIC
EVEnts
Display events
TRIP
Open Breaker command;
issues the command to
open breaker; breaker will
be determined by settings
NUM_BRKR and NUM_TC
CLOSe
Close Breaker command;
issues the command to
close breaker; breaker will
be determined by settings
NUM_BRKR and NUM_TC
ENOUT
Enable outputs
DISABle
Disable outputs
outputs
STATUs
Display status of the relay
DATAReset
Clear various data logs
maintained in the relay
DIGTest
Perform Digital Output tests;
the test energizes the
selected output until END is
chosen or another output is
tested
GROUP
INPuts
Request contact converter
status
GE Power Management
LOWEST
RELAY PROMPT
LEVEL
PASSWORD
NEEDED
VIEW
List of events with date and time. Example:
06/30/98 16:26:29.7562 Host Logoff on MMI
06/30/98 16:24:37.5944 Host Logon OK on Port 2
06/30/98 16:10:45.6505 Recloser in RESET state
06/30/98 16:10:40.0000 Settings File 0 in Use
06/30/98 16:10:40.0000 System booted
Press ENTER to continue, B to go back a screen, or
ESC to quit
CONTROL
Enter Breaker No. (1 / 2 / BOTH)
TRIP BREAKER 1,! Are you sure? (Y/N)
Breaker open command sent
CONTROL
Enter Breaker No. (1 / 2 / BOTH)
CLOSE BREAKER 1,! Are you sure? (Y/N)
Breaker close command sent
CONTROL
Enable Outputs, Are you sure? (Y/N)
Outputs are disabled or Outputs cannot be disabled
CONTROL
Disable Outputs, Are you sure? (Y/N)
Outputs are disabled or Outputs cannot be disabled
VIEW
RELAY STATUS
Refer to the servicing section for status messages
for the ALPS
Press ENTER to continue
SETTING
To clear FAULT REPORT and OSCILLOGRAPHY
enter F
To clear OST REPORT enter S
To clear EVENT DATA enter E
To reset target LED and clear warn, failure, and trip
messages enter L
To clear BREAKER HEALTH enter B
To quit press ESC
Enter your choice:
MASTER
Turn Protection off (Y/N):
Enter the number of the Digital Output to be tested
(1 to 18)
Enter END to end test
To see list of Digital Outputs enter H
To quit press ESC
Enter your choice: 4
Digital Output #4 is Activated
Turn Protection on? (Y/N):
SETTING
The active Protectioning Setting Group number is 1
To select a Setting Group enter Setting Group
Number ('1' - '4')
To select active setting group through Contact
Converter Inputs enter '0'
To quit press ESC
Enter your choice:
Are you sure (Y/N):? y
New Active Group = 3
VIEW
Contact Converter #0=0 ( SETTING GROUP BIT 0 )
Contact Converter #1=1 ( SETTING GROUP BIT 1 )
Contact Converter #2=1
Contact Converter #3=0
Contact Converter #4=0
Contact Converter #5=1
Contact Converter #6=0
Contact Converter #7=1
ALPS Advanced Line Protection System
12.1 INTRODUCTION
USER
RESPONSE
None
1, 2, or BOTH;
Y to trip, N to
cancel
1, 2, or BOTH;
Y to trip, N to
cancel
Y for OK, N to
cancel; command
Y for OK, N to
cancel; command
None
Enter letter, press
ENTER
Enter letter; Enter
digit form 1 to 18;
enter letter
Enter digit from 0
to 4; enter letter
None
(not assigned)
(not assigned)
(not assigned)
(not assigned)
(not assigned)
(not assigned)
12
12-3

Advertisement

Table of Contents
loading

Table of Contents