Binary Counter, Frozen Counter - GE ALPS Instruction Manual

Advanced line protection system
Table of Contents

Advertisement

C.3 POINT LISTS
Table C–5: POINT LIST: OBJECTS 20 & 21
BINARY COUNTER (OBJECT 20)
FROZEN COUNTER (OBJECT 21)
INDEX
DESCRIPTION
0
Breaker Health Accumulator – Phase A
1
Breaker Health Accumulator – Phase B
2
Breaker Health Accumulator – Phase C
3
Number Of Trips – Phase A
4
Number Of Trips – Phase B
C
5
Number Of Trips – Phase C
None of the above counters can be cleared with the Freeze/Clear (function code 9) operation. Instead, the control relay out-
put block points can be used to clear groups of counters. There is only one copy of each counter, so clearing a counter from
other serial ports or MMI causes the corresponding DNP counter point to be cleared and vice-versa. However, note that
counters 2 to 5 cannot be cleared using DNP protocol. The Breaker Health can be set via MMI or from other serial ports
using GE_MODEM, MODBUS or ASCII protocols.
C-12
ALPS Advanced Line Protection System
C.3.4 BINARY COUNTER, FROZEN COUNTER
ROLLOVER POINT
4294967295
4294967295
4294967295
65535
65535
65535
GE Power Management
APPENDIX C

Advertisement