If you use a multi-conductor cable, 1 of the conductors of the brake resistor cable stays unconnected. It is also possible to use a single cable if you obey the minimum cross-sectional
area of the cable.

10.4 Cable Stripping Lengths

See the illustration for parts of cables to be stripped and check the corresponding stripping length in the table.
G
1
1 Mains cable
Illustration 58:
Cable Stripping
Table 28: Cable Stripping Lengths, in mm
Enclosure size
MR4
MR5
MR6
MR7
112 | Danfoss A/S © 2019.05
I
[A]
Fuse (Class
Mains, motor
L
T/J) [A]
and brake re-
sistor
Cu [AWG]
144.0
175
3/0
170.0
200
4/0
208.0
250
300 kcmil
261.0
350
2xAWG2/0
2
A
B
C
15
35
10
20
40
10
20
90
15
20
80
20
Mains terminal cable size
[AWG]
(1)
cable
1 AWG–350 kcmil
1 AWG–350 kcmil
1 AWG–350 kcmil
1 AWG-350 kcmil
2 Motor cable
D
E
F
20
7
35
30
10
40
60
15
60
80
20
80
Specifications
Grounding terminal cable
size [AWG]
1 AWG–350 kcmil
1 AWG–350 kcmil
1 AWG–350 kcmil
1 AWG-350 kcmil
G
As short as possible
As short as possible
As short as possible
As short as possible