Operating Guide | VACON® 100 Wall-mounted Drives
I
I L*110%
I L
1 min
Illustration 59:
Low Overload
The high overload means that if 150% of the continuous current (I
minutes must be approximately 92% of I
I
I
H*150%
I
H
1 min
Illustration 60:
High Overload
For more information, refer to the standard IEC61800-2.
High overload is available only for VACON
Danfoss A/S © 2019.05
I L*110%
9 min
or less. This is to make sure that the output current is not more than I
H
I
H*150%
9 min
N O T I C E
®
100 INDUSTRIAL
t
) is required for 1 minute every 10 minutes, the remaining 9
H
t
Specifications
during the duty cycle.
H
AQ298036140958en-000101 / DPD01711| 125