6.2 EMC-compliant Installation

For cable selections in different EMC levels, see
To comply with the EMC levels, use a grommet when installing the motor cable at the two ends. For the EMC level C2, it is necessary to
have a 360º grounding of the shield with grommets in the motor end.
Table 14: Recommendations for Cables
Cable
Category C2
type
Motor ca-
A symmetrical power cable with a compact low-impe-
ble
dance shield.
A cable for the specified mains voltage.
We recommend an MCCMK, or an EMCMK cable. See
illustration
9.
We recommend that the cable transfer impedance
(1–30 MHz) is a maximum of 100 mΩ/m.
Mains ca-
A power cable for a fixed installation.
ble
A cable for the specified mains voltage.
A shielded cable is not necessary.
We recommend an MCMK cable.
Control
A shielded cable with a compact low-impedance shield, for example a JAMAK, or an SAB/ÖZCuY-O cable.
cable
1
st
1
environment
2
nd
2
environment
For the definitions of EMC protection levels, see IEC/EN 61800-3 + A1.
A
C
A The PE conductor and the shield
C The shield
Illustration 9:
Cables with PE Conductors
34 | Danfoss A/S © 2019.05
table
14.
(1)
B
Category C3
(2)
A symmetrical power cable with a concentric protection wire.
A cable for the specified mains voltage.
We recommend an MCMK cable. See
B The PE conductors
Electrical Installation
Category C4
(2)
illustration
9.