Operating Guide | VACON® 100 Wall-mounted Drives
10.8.6 Brake Resistance and Brake Power, Mains Voltage 380–500 V
Table 44: The Minimum Brake Resistance and Brake Power, Mains Voltage 380–500 V
Enclosure size
MR4
MR5
MR6
MR7
MR8
MR9A
MR9B
1
When using recommended resistor types.
10.8.7 Brake Resistance and Brake Power, Mains Voltage 525–600 V
Table 45: The Minimum Brake Resistance and Brake Power, Mains Voltage 525–600 V
Enclosure size
The minimum brake resistance [Ω]
MR5
100
MR6
30
MR7
18
MR8
9
MR9A
7
MR9B
2.5
1
When using recommended resistor types.
10.8.8 Brake Resistance and Brake Power, Mains Voltage 525–690 V
Table 46: The Minimum Brake Resistance and Brake Power, Mains Voltage 525–690 V
Enclosure size
The minimum brake resistance [Ω]
MR6
30
MR7
18
MR8
9
MR9A
7
MR9B
2.5
1
When using recommended resistor types.
Danfoss A/S © 2019.05
The minimum brake resistance [Ω]
63.0
41.0
21.0
14.0
6.5
3.3
1.4
Brake power @845 VDC [kW]
11.3
17.0
34.0
51.0
109.9
216.4
250
Brake power @1014 VDC [kW]
7.5
22.4
44.8
93.3
145
183
Brake power @1166 VDC [kW]
30
55
110
193
250
AQ298036140958en-000101 / DPD01711| 129