Operating Guide | VACON® 100 Wall-mounted Drives
Technical item or
Technical item or function
function
EMC (at default set-
Immunity
tings)
Emissions
Noise level
Average noise level (min-max)
sound pressure level in dB(A)
Safety standards
-
and certifications
Protections
Overvoltage trip limit
Undervoltage trip limit
Earth fault protection
Mains supervision
Motor phase supervision
Overcurrent protection
Unit overtemperature protection
Motor overload protection
Motor stall protection
Motor underload protection
Short-circuit protection of +24 V
and +10 V reference voltages
1
For the motor thermal memory and the memory retention function to obey the UL 61800-5-1 requirements, you must use the system software version FW0065V021 or a newer
version. If you use an older system software version, you must install a motor overtemperature protection to obey the UL regulations.
144 | Danfoss A/S © 2019.05
Technical information
Fulfils EN 61800-3 (2004), 1st and 2nd environment
200–500 V: EN 61800-3 (2004), category C2.
All: The product is configurable to category C4 for installation on IT
networks. The drive can be modified for IT type mains. See
tion in an IT
System. The IP00/UL Open Type drive has by default cate-
gory C4.
The sound pressure depends on the cooling fan speed, which is con-
trolled in accordance with the drive temperature.
MR4: 45–56
MR5: 57–65
MR6: 63–72
MR7: 43–73
MR8: 58–73
MR9: 54–75
EN 61800-5-1 (2007), CE, cUL (See the nameplate of the drive for more
approvals.)
Mains voltage 240 V: 456 VDC
Mains voltage 500 V: 911 VDC
Depends on mains voltage (0.8775 x mains voltage):
Mains voltage 240 V: trip limit 211 VDC
Mains voltage 400 V: trip limit 351 VDC
Mains voltage 500 V: trip limit 438 VDC
Mains voltage 525 V: trip limit 461 VDC
Yes
Yes
Yes
Yes
Yes
Yes.
(1)
The motor overload protection activates at 110% of the full load
current.
Yes
Yes
Yes
Specifications
6.6 Installa-
AQ298036140958en-000101 / DPD01711