Operating Guide | VACON® 100 Wall-mounted Drives
Technical item or
Technical item or function
function
Ambient condi-
Ambient operating tempera-
tions
ture
Storage temperature
Relative humidity
Air quality:
Altitude
Pollution degree
Vibration:
Shock:
Enclosure class
Danfoss A/S © 2019.05
chemical vapors
mechanical particles
EN 61800-5-1
EN 60068-2-6
EN 60068-2-27
Technical information
I
current: -10°C (no frost)...+40 °C
L
Maximum operating temperature: +50 °C with derating (1.5%/1°C)
-40 °C...+70 °C
0–95% RH, non-condensing, non-corrosive
Tested according to IEC 60068-2-60 Test Ke: Flowing mixed gas corrosion
test, Method 1 (H2S [hydrogen sulfide] and SO2 [sulfur dioxide])
Designed according to
IEC 60721-3-3, unit in operation, class 3C3 (IP21/UL Type 1 Models 3C2)
IEC 60721-3-3, unit in operation, class 3S2
100% nominal rating (no derating) up to 1000 m
1% derating for each 100 m above 1000 m
Maximum altitudes:
208–240 V: 4000 m (TN and IT systems)
380–500 V: 4000 m (TN and IT systems)
380–500 V: 2000 m (corner-grounded network)
525–690 V: 2000 m (TN and IT systems, no corner grounding)
Voltage for relay outputs:
Up to 3000 m: Allowed up to 240 V
3000–4000 m: Allowed up to 120 V
Corner grounding is allowed for MR4-MR6 (main voltage 208–230 V) up to
2000 m (see
6.2.1 Installation in a Corner-grounded
PD2
5–150 Hz
Displacement amplitude 1 mm (peak) at 5–15.8 Hz (MR4-MR9)
Maximum acceleration amplitude 1 G at 15.8–150 Hz (MR4-MR9)
UPS Drop Test (for applicable UPS weights)
Storage and shipping: maximum 15 G, 11 ms (in package)
IP21/UL Type 1: standard in entire kW/HP range
IP54/UL Type 12: option
NOTE! For IP54/Type 12, a control panel adapter is necessary.
Specifications
Network).
AQ298036140958en-000101 / DPD01711| 139