How To Install; Cabling; Cable Lengths; Cable Specifications - Danfoss FC 300 Manual

Canopen
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 CANopen

How to Install

Cabling

Cable Lengths

Cable Specifications

Bus length in
Bus cabel
meters
Resistance
mΩ/m
0-40
70
40-300
<60
300-600
<40
600-1000
<26
Cable Specifications
The cable used should be according to the pecifications.
Be aware that the "Flat Cable" is an unscreened cable type, and is not suited for use with frequency
converters.
Termination resistor
Cross section
mm²
0.25-0.34
124
0.34-0.6
150-300
0.5-0.6
150-300
0.75-0.8
150-300
MG.33.J1.02 VER. 050301 – VLT is a registered Danfoss trademark
Baudrate
Kbit/s
1000 (up to 30m)
>500 (up to 100m)
>100 (up to 500m)
>50 (up to 1000m)
9