Specifications

6.4 General Technical Data

6.4.1 Protection and Features

Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips in case of overtem-
perature.
The adjustable frequency drive is protected against short-circuits between motor terminals U, V, W.
When a motor phase is missing, the adjustable frequency drive trips and issues an alarm.
When a line power phase is missing, the adjustable frequency drive trips or issues a warning (depending on the
load).
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips when the
intermediate circuit voltage is too low or too high.
The adjustable frequency drive is protected against ground faults on motor terminals U, V, W.

6.4.2 Line power supply (L1, L2, L3)

Supply voltage
Supply voltage
Supply voltage
Supply frequency
Maximum imbalance temporary between line power phases
True power factor (λ)
Displacement power factor (cosφ) near unity
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H1–H5, I2, I3, I4
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H6–H8, I6–I8
Environment according to EN 60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 240/480 V
maximum.

6.4.3 Motor Output (U, V, W)

Output voltage
Output frequency
Switching on output
Ramp times
6.4.4 Cable Lengths and Cross–sections
Maximum motor cable length, shielded/armored (EMC-compatible installation)
Maximum motor cable length, non-shielded/unarmored
Maximum cross-section to motor, line power
Cross-section DC terminals for filter feedback on enclosure frame H1–H3, I2, I3, I4
Cross-section DC terminals for filter feedback on enclosure frame H4–H5
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
Minimum cross-section to control terminals
1) See chapter 6.1.2 3x380–480 V AC for more information
MG18A622
Quick Guide
1)
Danfoss A/S © 08/2014 All rights reserved.
200–240 V ±10%
380–480 V ±10%
525–600 V ±10%
3.0% of rated supply voltage
≥0.9 nominal at rated load
Maximum 2 times/min.
Maximum 1 time/min.
Overvoltage category III/pollution degree 2
0–100% of supply voltage
+
0–200 Hz (VVC
), 0–400 Hz (u/f)
See chapter 6.2.1 EMC Emission Test Results
4 mm
16 mm
2.5 mm
2.5 mm
0.05 mm
6
6
50/60 Hz
(>0.98)
Unlimited
0.05-3600 s
50 m (164 ft)
2
/11 AWG
2
/6 AWG
2
/14 AWG
2
/14 AWG
2
/30 AWG
55