Local Thermostat Mode, VAV staged units

ECTO 6.01 option 0 (default) or 12;
ECTO 6.01 option 0 (default) or 12;
ECTO 0.01 option 3 (MSAV)
This configuration is a special case application
g
where the blower speed is staged by the factory
h
th bl
d i
installed VFD for fixed speeds for different op
installed VFD for fixed speeds for different op-
eration. There are seven different speed stages,
eration There are seven different speed stages
one for each cooling compressor stage (4), one
one for each cooling compressor stage (4), one
for ventilation, one for heating and one for opera-
for ventilation, one for heating and one for opera-
tion during smoke alarm modes. The blower is
tion during smoke alarm modes. The blower is
enabled by a G demand. This table shows the
y
d f
default staged speeds.
lt t
d
d
9.2.7.

L Connection Network, VAV units

ECTO 6.01 option 4, 5, 6, or 7;
ECTO 0.01 option 63
This configuration is used for L Connection VAV zoning systems. There are four different setpoints: one for cooling, one for
ventilation, one for operation during smoke alarm modes, and one for heating. Network commands energize the blower.
Blower will cycle with demand unless ECTO 6.17 is set to 1. In that case the blower will operate continuously during occupied
periods and will cycle during unoccupied periods. Network commands controls occupied/unoccupied periods.
All delays as described in Local Tstat Mode still apply. Blower speed is controlled by the factory installed VFD between a
minimum and maximum speed to maintain duct static pressure setpoints. There are three different setpoints, one for cool-
ing, one for ventilation and one for operation during smoke alarm modes. The M2 controls the duct static pressure by reading
the duct pressure and varying the blower speed on units with VFDs
The min/max. speed and static pressure setpoints are listed below:
Operation
Operation
Default
Cooling
50%
Ventilation
50%
Smoke Alarm Modes
50%
50%
Heating
9.2.8.
VAV Staged Units: A Box (3− to 5−ton units)
Energence A Box 3− to 5−ton units use a single, 2−step capacity, compressor. These units use a variable output blower that
operates at high or low. (The 6−ton Energence A Box has a single capacity compressor, and a single speed blower,
so it is not an MSAV type of unit, and the following does not apply to it.)
High efficiency Energence A Box units use a direct−drive ECM constant torque motor. The blower runs at a selected high
or low output depending on unit operation. The actual blower speed and CFM delivered will depend on the flow restriction as
well as the percent output. The blower output for each mode of operation has been factory set, but it will need to be adjusted
based on the installed ductwork and the air delivery required for the application. The table shows the default blower output
and the ECTO location where the output value for the each mode is stored. The default blower output selection for smoke
mode operation is the same as high speed, but it can be set to a different value using ECTO 0.02.
Standard efficiency Energence A Box unit use a belt−drive 2−speed motor. The blower runs at low or high speed depend-
ing on unit operation, but the speed is not ECTO−selectable. High speed blower runs during smoke mode operation. The
table also shows, for units equipped with an economizer or motorized outdoor air damper, the damper percent output when
the blower is running and the space is occupied. The default value of 101 for ECTO 5.24 is used to indicate that the min
position potentiometer on the M2 board is used to set the high−blower damper position. Setting ECTO 5.24 to a value in the
range of 0−100 causes this value to be used for the damper minimum position during high blower operation.
High Efficiency Factory Settings (as percent output) − A Box (3− to 5−ton units)
Operation
Cooling low, Free cooling low, Ventilation low
Cooling high, Free cooling high, Ventilation high, Heating
Smoke alarm modes
Minimum damper during low blower
Minimum damper during high blower
506457−01 05/10
p
pp
t
d b th f t
Minimum Position
ECTO
0.06
0.06
0.06
0.07
Operation
Operation
Cooling compressor 1
Cooling compressor 2
Cooling compressor 3
Cooling compressor 4
Ventilation or economizer free cooling
Smoke Alarm Modes
Heating
(1)
Staged % speed must be adjusted for each operation.
Maximum Position
Default
ECTO
100%
0.08
100%
0.08
100%
0.08
100%
0.08
3− ton
28
55
55
Page 38
9.
Supply Air Delivery
Staged Speed
(1)
Default ECTO
51%
51%
51%
51%
51%
51%
51%
Duct Static SP
Default
1.00"w.c.
1.00"w.c.
1.00"w.c.
1.00"w.c.
4− ton
5− ton
40
36
80
59
80
59
30
101
0.05
0.14
0.15
0.16
0.03
0.02
0.04
ECTO
0.05
0.03
0.02
0.04
ECTO
0.05
0.04
0.02
0.09
5.24