Lennox Prodigy M2 Application Manual page 76

Hide thumbs Also See for Prodigy M2:
Table of Contents

Advertisement

Control Parameter
No.
Name
Min.
5.04
CL_Staging
0
5.05
RAT_LT
0
95
5.06
RAT_HT_LT
100
124
5.07
RAT_CL_LT
80
A42_Input_
5.08
1
Occurrences
5.09
HT_Staging
0
LP_Strike_3_
0
5.10
Run_Time_1
0
LP_Strike_3_
0
5.11
Run_Time_2
0
LP_Strike_3_
0
5.12
Run_Time_3
0
LP_Strike_3_
0
5.13
Run_Time_4
0
LP_Strike_3_
28
5.14
Off_Time
3584
LP_Strike_3_
50
5.15
Temp_SP
100
DCV_Max_
0
5.16
Damper_Open
0
DCV_Damper
0
5.17
_Start_Open_
0
SP
OAC_Dampr_St
0
art_Open_SP
DCV_Dampr_
0
5.18
Full_Open_SP
0
OAC_Dampr_F
0
ull_Open_SP
DCV_Low_T em
0
p_Override_
5.19
132
Full_Closed
DCV_Low_T em
0
5.20
p_ Override_
132
Start_Closing
DCV − High-
0
5.21
Temp. Override
132
Start Closing
DCV_High_T em
0
5.22
p_ Override_
132
Full_Close
Free_CL_
0
5.23
Max_Damper
0
506457−01 05/10
Control Value
Default
Max.
Block 5 Miscellaneous Parameters (continued)
2
4
0
1
117
154
85
60
X:DegF
146
154
65
60
X:DegF
3
15
2
2
45
255
360
2040
90
255
720
2040
C: Sec.
15
255
120
2040
38
255
304
2040
113
169
14464
21632
97
191
70
10
100
100
100
100
64
255
502
2000
2.51
10
128
255
1004
2000
5.02
10
191
255
10
−31
Y:Deg.F
144
255
40
−31
Y:Deg.F
89
255
75
−31
Y:Deg.F
42
255
105
−31
Y:Deg.F
100
100
100
100
17.
Electronic Configure To Order (ECTO) Control Parameters
Units
Description
Cooling staging options:
0−
No cooling operation
1−
Basic Tstat operation. Two cooling stages. Units with Economiz-
ers Y1=FreeCooling,
Y2=adds all mechanical stages.
2−
Basic Tstat operation. Two cooling stages. Units with Economiz-
Option
ers Y1=Free Cooling, Y2= adds first stage of mechanical.
3−
Basic Tstat operation. Three cooling stages. Y1 only = first
stage, Y2 only = second stage, Y1+Y2 = third stage. Units with
Economizers Y2 only adds first stage of mechanical, Y1+Y2
adds first and second stage of mechanical.
4−
Discharge air control. Up to four stages.
Enables return air temperature limit option.
Return air limits may be used for limiting zone temperatures. Continu-
Option
ous fan operation recommended.
Return air limit for heating. If the return air heating limit is exceeded,
Counts
the heating demands are interrupted. 5.05 MUST BE SET TO 1 TO
ENABLE
Return air limit for cooling. If the return air cooling limit is exceeded,
Counts
the cooling demands are interrupted. 5.05 MUST BE SET TO 1 TO
ENABLE
A42 input occurrences before service relay is energized.
Counts
(A55_P299_6)
Heating staging options:
0−
No heating operation.
Option
1−
Discharge air control with up to 4 stages.
2−
Thermostat operation.
Counts
Ignore LP trip when compressor run time less than this. LONG/HOT
C:Sec.
condition.
Counts
Ignore LP trip when compressor run time less than this. LONG/COLD
condition.
Counts
Ignore LP trip when compressor run time less than this. SHORT/HOT
C:Sec.
condition.
Counts
Ignore LP trip when compressor run time less than this. SHORT/
C:Sec.
COLD condition.
Counts
Low Pressure Switch Strike Three compressor off time breakpoint
E:Sec
for LONG/SHORT evaluation.
Counts
Low Pressure Switch Strike Three outdoor air temperature breakpoint
Y:Deg.
for HOT/COLD evaluation.
Counts
Maximum allowed Demand Control Ventilation damper open position.
P:%
(Set to 0 to disable IAQ). Also used for OAC.
Count
Damper start open" CO
I:PPM
Level where fresh air damper begins to open.
Damper start open" setpoint for Outdoor Air Control. Level where
R: Volt
fresh air damper begins to open.
Count
Damper full open" CO
I:PPM
el where fresh air damper is opened to maximum.
Damper full open" setpoint for Outdoor Air Control. Level where fresh
R: Volt
air damper is opened to maximum.
Low outdoor air temp. where fresh air damper is closed to minimum
Counts
position for Demand Control Ventilation and Outdoor Air Control
(OAC).
Low outdoor air temp. where fresh air damper begins to close. Set
Counts
ECTO 5.20 = 255 to disable the outdoor Low Temp. override of DCV
operation. Also used for OAC.
High outdoor air temp. where fresh air damper begins to close. Set
Counts
5.21 =0 to disable the outdoor High Temp override of DCV opera-
tion. Also used for OAC.
Counts
High outdoor air temp. where fresh air damper is closed to minimum
position. Also used for OAC.
Counts
The maximum allowed fresh air damper opening for FREE COOLING.
P:%
Page 76
setpoint for Demand Control Ventilation.
2
setpoint for Demand Control Ventilation. Lev-
2
table continued on next page