Discharge Air Control Heating Total Reset Limit - Lennox Prodigy M2 Application Manual

Hide thumbs Also See for Prodigy M2:
Table of Contents

Advertisement

10.8. Discharge Air Control Heating Total Reset Limit

ECTO 8.08 (default=10) defines the total DACH setpoint reset limit. This total limit is the sum of both return and outdoor DACH
resets. This parameter limits total DACH_SP adjustment band and overrides the adjustment bands for RAT and OAT (ECTO
8.11 & 8.14) if necessary.
Table 32. Discharge Air Heating ECTO Parameters Summary
Control Parameter
No.
Name
Min.
5.09
HT_Staging
0
6.01
System_Mode
0
DACH_OCP
36
7.10
_SP
140
DACH_UnOCP
36
7.11
_SP
140
7
7.12
DACH_Stg_DB
5
DACH_&_FAH_
0
7.13
StgUp_Delay
0
DACH_&_FAH_
0
7.14
StgDn_Delay
0
DACH_Stg_
3
7.15
Diff
2
DACH_RS_
7
8.08
Limit
5
DACH_RAT_
124
8.09
RS_SP.
80
DACH_RAT_
1
8.10
RS_Proportion-
1
al_ Band
DACH_RAT_
0
RS_Adjust_
8.11
0
Band
DACH_OAT_
113
8.12
RS_SP
60
DACH_OAT_R
1
8.13
S_Proportional_
1
Band.
DACH_OAT_R
0
8.14
S_Adjust_ Band
0
Control Value
Default
Max
Units
2
2
Option
0
12
Option
Counts
80
124
110
80
X:DegF
Counts
95
124
X:DegF
100
80
7
30
Counts
5
20
V:DegF
45
225
Counts
180
900
B: Sec.
30
150
Counts
120
600
B: Sec.
3
30
Counts
2
20
V:DegF
15
29
Counts
10
20
V:DegF
Counts
139
169
X:DegF
70
50
15
44
Counts
10
30
V:DegF
0
44
Counts
0
30
V:DegF
144
255
Counts
40
−31
Y:DegF
Counts
31
94
O:DegF
20
60
0
47
Counts
0
30
O:DegF
Description
Heating staging options:
0−
No heating operation.
1−
Discharge air control with up to 4 stages.
2−
Thermostat operation.
System mode of operation.
Control
Value
System Mode
0
Local Thermostat
1
Zone Sensor
2
Zone Sensor
3
Zone Sensor
4
Remote Demand
5
Remote Demand
6
Remote Demand
7
Remote Demand
8
Future Use
9
Future Use
10
Future Use
11
Future Use
12
A138 4−Stg. Tstat Interface
Discharge Air Control Heating setpoint during occupied period.
Discharge Air Control Heating setpoint during unoccupied period.
Discharge Air Control Heating deadband.
Discharge Air Control Heating and Fresh Air Heating stage−up time delay.
Discharge Air Control Heating and Fresh Air Heating stage−down time delay.
Discharge Air Control Heating stage differential
Discharge Air Control Heating reset limit. This limits the total DACH reset al-
lowed.
Discharge Air Control Heating return air heating reset setpoint.
Discharge Air Control Heating return air heating reset proportional band.
Discharge Air Control Heating return reset adjustment band.
0 value disables return air heating reset.
Discharge Air Control Heating outdoor temperature reset setpoint.
Discharge Air Control Heating temperature reset proportional band.
Discharge Air Control Heating outdoor temperature reset adjustment band.
0 disables outdoor temperature heating reset
Page 47
10.
Discharge Air Control
Backup Mode
None
None
Local Thermostat
Return Air Sensor
None
Local Thermostat
Return Air Sensor
Zone Sensor
None
Local Thermostat
Return Air Sensor
Zone Sensor
None
PRODIGYT M2 UNIT CONTROLLER