Control Parameter
No.
Name
Min
OAC_Dampr_St
5.17
0
art_Open_SP
OAC_Dampr_F
5.18
0
ull_Open_SP
IAQ_Input_
5.26
0
Source/Mode
A01_control_
9.01
0
mode
0
0
9.02
AO1_SP_A
−0.5
0
AO1_PID_P_
9.09
0
Constant
AO1_PID_I_
9.10
0
Constant
Table 27. Outdoor Air Control ECTO Parameter Summary
Control Value
Default
Max.
Units
2.51
10
R: Volt
5.02
10
R: Volt
0
5
Option
0
11
Option
127
255
Counts
5.00
10.0
R:Volts
0
0.5
M:"w.c.
2.5
5.0
N:"w.c.
0
127
Counts
0
127
Counts
Description
Damper start open" setpoint for Outdoor Air Control. Level where fresh air
damper begins to open.
Damper full open" setpoint for Outdoor Air Control. Level where fresh air damp-
er is opened to maximum.
IAQ input source and mode (0−3 operate only when blower is on).
0− DCV System IAQ. Either P298−3 or network IAQ.
1− DCV System IAQ. Either P298−3 or network IAQ with no OAT limits.
2− Outdoor Air Control Sensor A24 (A133_P194−6) (TB22−6).
3− Outdoor Air Control Sensor A24 (A133_P194−6) (TB22−6) with no OAT limits.
4− DCV System IAQ. Either P298−3 or network IAQ with blower on/auto operation.
5− DCV System IAQ. Either P298−3 or network IAQ with blower on/auto operation
with no OAT limits.
Analog output channel 1 control mode.
0 − No operation. Analog Output 1 off.
Enabled When
1−
Occupied
Unoccupied
2−
Occupied
Unoccupied
3−
Occupied
Unoccupied
4−
Occupied
Unoccupied
5−
Blower On
Blower Off
6−
Blower On
Blower Off
7−
Blower On
Blower Off
8−
Blower On
Blower Off
9 −
DI2 (A133_P194−2) on
DI1 (A133_P194−1) on
Otherwise off
10−
DI2 (A133_P194−2) on
DI1 (A133_P194−1) on
Otherwise off
11−
DI2 (A133_P194−2) on
DI1 (A133_P194−1) on
Otherwise off
(1) −DI1 (A133_P194−2) doesn't matter
(2) −DI2 (A133_P194−1) is off
Analog output channel 1 setpoint A
Analog output channel 1 PID loop proportional constant.
Analog output channel 1 PID loop integral constant.
Page 33
7.
Economizer
Control
PID setpoint A
PID setpoint B
PID setpoint A
Staged output B
Staged output A
PID setpoint B
Staged output A
Staged output B
PID setpoint A
PID setpoint B
PID setpoint A
Staged output B
Staged output A
PID setpoint B
Staged output A
Staged output B
PID setpoint B (1)
PID setpoint A (2)
PID setpoint B (1)
Staged output A (2)
Staged output B (1)
Staged output A (2)
PRODIGYT M2 UNIT CONTROLLER