Lennox Prodigy M2 Application Manual page 74

Hide thumbs Also See for Prodigy M2:
Table of Contents

Advertisement

Control Parameter
No.
Name
Min.
0
4.01
CoolDn_Delay
0
0
4.02
BL_On_Delay
0
0
4.03
BL_Off_Delay
0
Max_Frz_Stat_
4.04
1
Occurrences
Cond_Fan_
0
4.05
ReStart_ Delay
0
LAC_SP_
113
4.06
Temp_ 1
60
LAC_SP_
113
4.07
Temp_2
60
Compr_1_Low_
81
4.08
Temp_
80
Lockout
Compr_2_Low_
81
4.09
Temp_ Lockout
80
Compr_3_Low_
81
4.10
Temp_
80
Lockout
Compr_4_Low_
81
Temp_
4.11
80
Lockout
Compr_Min_
30
4.12
Off_Delay
60
Compr_Min_
30
4.13
Run_Time
60
Max_HP_
4.14
1
Occurrences
Max_LP_
4.15
1
Occurrences
Cond_Fan_
0
4.16
Delay
0
4.17
Stg_2_Latch
0
4.18
Stg_3_Latch
0
4.19
Stg_4_Latch
0
Stg_2_StgUp_
0
4.20
Timer
0
Stg_3_StgUp_
0
4.21
Timer
0
Stg_4_StgUp_
0
4.22
Timer
0
0
4.23
StgDn_Timer
0
506457−01 05/10
Control Value
Default
Max.
Block 4 Cooling Parameters
56
255
1792
8160
0
15
0
60
0
60
0
240
3
5
3
8
6
16
144
191
40
10
120
191
55
10
Y:Deg.F
207
255
0
−31
Y:DegF
207
255
0
−31
Y:Deg.F
207
255
0
−31
Y:DegF
207
255
0
−31
Y:DegF
150
255
300
510
120
255
240
510
3
8
3
8
1
120
2
240
0
1
0
1
0
1
57
225
912
3600
57
225
912
3600
57
225
912
3600
57
225
912
3600
17.
Electronic Configure To Order (ECTO) Control Parameters
Units
Description
Cool down tine delay. Time that Y2 is ignored during cool down period
Counts
(when first occupied + cool demand) This delay is only used if an
D:Sec.
economizer is used and the outdoor air is suitable.
Counts
Blower on delay. The time before the blower turns on after a cooling
B:Sec.
demand.
Counts
Blower off delay. The time the blower stays on after the cooling de-
B:Sec.
mand is lost.
Service output activation and compressor lockout. Maximum Freeze
Stat occurrences stored before service relay is energized and com-
Counts
pressor is locked−out. If value (4 or 5) is set, service output is dis-
abled and compressor is not locked−out. If value 5 is set, alarms are
not stored, but only displayed as they occur.
Counts
Low ambient anti−windmilling condenser fan delay. The time period
A:Sec.
that the last operating fan is turned off before starting the next fan.
Low ambient outdoor air limit temp. 1. Parameters 4.06 and 4.07 are
Counts
used to shed fans. See Operation section. Temperature setting must
Y:DegF
be < or = 4.07.
Low ambient outdoor air limit temp. 2. Parameters 4.06 and 4.07 are
Counts
used to shed fans. See Operation section. Temperature setting must
be > or = 4.06.
Low ambient lockout for compressor 1.
Counts
A value of 255 (−31°F) will disable low ambient lockout function.
Temperature setting must be < or = 4.09.
Low ambient lockout for compressor 2.
Counts
A value of 255 (−31F) will disable low ambient lockout function.
Temperature setting must be > or = 4.08 AND < or = 4.10.
Low ambient lockout for compressor 3.
Counts
A value of 255(−31F) will disable low ambient lockout function.
Temperature setting must be > or = 4.09 AND < or = 4.11.
Low ambient lockout for compressor 4.
Counts
A value of 255 (−31F) will disable low ambient lockout function.
Temperature setting must be > or = 4.10.
Counts
Compressor minimum off delay. Used on 1 PH units.
A:Sec.
Counts
Compressor minimum run time. Used on 3 PH units.
A:Sec.
Maximum High Pressure occurrences that are stored before control
locks off compressor stage and energizes the service output. If max
Counts
value is set, lockout and service output features are disabled.
Maximum Low Pressure occurrences that are stored before control
Counts
locks off compressor stage and energizes the service relay. If max
value is set, lockout and service output features are disabled.
Counts
Condenser fan delay. Used only on 6 fan units.
A:Sec.
Stage 2 latch option. Used in zone sensor applications.
Option
0: Latch Disabled
1: Latch Enabled
Stage 3 latch option. Used in zone sensor applications.
0: Latch Disabled
Option
1: Latch Enabled
Stage 4 latch option. Used in zone sensor applications.
Option
0: Latch Disabled
1: Latch Enabled
Stage 2 stage up timer. The maximum time that cooling stage 1 runs
Counts
before calling cooling stage 2. Used in zone sensor applications.
F:Sec
Disabled if set to 0.
Stage 3 stage up timer. The maximum time that cooling stage 2 runs
Counts
before calling cooling stage 3. Used in zone sensor applications.
F:Sec
Disabled if set to 0.
Stage 4 stage up timer. The maximum time that cooling stage 3 runs
Counts
before calling cooling stage 4. Used in zone sensor applications.
F:Sec
Disabled if set to 0.
Counts
Time delay before a lower stage turns off following a higher stage
F:Sec
termination. Used in zone sensor applications.
Page 74