Control Parameter
No.
Name
Min.
DO_ Mode_
A133 (MGV
3.21
0
mode)
0
0
o
DO_SP_A133
3.22
0
(MGV mode)
132
−0.5
0
2
0
16
2
DO_DB_A133_(
3.23
1
MGV mode)
64
0.01
0
Control Value
Default
Max.
Units
Block 3 Gas Heating Parameters (continued)
0
127
Option
127
255
Counts
5.0
10.0
R:Volts
996
2000
100
100
51
−31
Y:DegF
0
0.5
M:"w.c.
2.5
5.0
N:"w.c.
13
255
Counts
.50
10.0
R:Volts
102
2000
13
100
8
162
O:DegF
416
8160
D:Sec.
0.05
1.0
L:"w.c.
.25
5.0
N:"w.c.
17.
Electronic Configure To Order (ECTO) Control Parameters
Description
GP1 Digital Out Mode = X + 32*Y + 16*Z
Input source= X:
0−
None.
1−
Compressor 1 duty cycle. (Compressor crankcase heater func-
tion.) On when OAT <= ECTO 3.22 and >= ECTO 3.23 seconds
have passed with compressor 1 off. Off when OAT > ECTO3.22
+ 3ºF (fixed deadband) or < ECTO 3.23 sec have passed with
compressor 1 off
2−
On when occupied.
3−
On when blower on,
4−
On when heating demand.
5−
On when cooling demand.
6−
On when heating or cooling demand.
7−
System RH (A55_P298_5 RH)
8−
System IAQ. (A55_P298_3 IAQ)
9−
System OAT (A55_P267_1/2 OAT)
7−
System RH (Either A55_ P114−10 or network RH)
11− AI2 (A133_P194−7) (SP and DB set with ECTO3.22 & 3.23)
12− AI3 (A133_P194−8) (SP and DB set with ECTO3.22 & 3.23)
13− AI4 (A133_P194−9) (SP and DB set with ECTO3.22 & 3.23)
14− AO1 (A133_P194−11)
15− AO2 (A133_P194−12)
Algorithm Y for input sources 7−15:
0−
Hysteresis loop
On when input >= ECTO 3.22
Off when input < ECTO 3.22−ECTO 3.23
1 Window
On when input is in range; >= ECTO 3.22
and <= ECTO 3.22 + ECTO 3.23
(Fixed 3−count hysteresis loop on rising and
falling edges of window.)
2−
Delayed−on.
On when input is >= ECTO 3.22
for >= ECTO 3.23 seconds.
Off when input is < ECTO 3.22 − 3.
(Fixed 3−count hysteresis loop on edge.)
3−
Delayed−off.
On when input is >= ECTO 3.22.
Off when input is < ECTO 3.22 −3
for >= ECTO 3.23 seconds.
(Fixed 3−count hysteresis loop on edge.)
Inversion Z:
0 − Output not inverted.
1 − Output inverted.
I:ppm
P:%
A133 (w/DIP set to MGV) digital output mode setpoint
I:ppm
P:%
A133 (w/DIP set to MGV ) digital output mode deadband or delay.
Page 73
OFF
3.22−3.23
ON
OFF
3.22
3.22 + 3.23
OFF
DELAY
3.22
3.23
DELAY
3.23
OFF
0.24
Graphs indicate output not
inverted. See figure 33.
table continued on next page
PRODIGYT M2 UNIT CONTROLLER
ON
3.22
OFF
ON
ON