ECTO
No.
Name
5.09
HT_Staging
7.10
DACH_OCP_SP
7.11
DACH_UnOCP_ SP
7.12
DACH_Stg_DB
DACH_&_FAC_
7.13
StgUp_Delay
ECTO
Name
No.
DACH_&_FAC_
7.14
SgDn_Delay
7.15
DACH_Stg_Diff
8.08
DACH_RS_Limit
8.09
DACH_RAT_RS_SP
DACH_RAT_RS_
8.10
Proportional_ Band.
DACH_RAT_RS_
8.11
Adjust_Band
8.12
DACH_OAT_RS_SP
DACH_OAT_RS_
8.13
Proportional_ Band.
DACH_OAT_RS_
8.14
Adjust_Band
506457−01 05/10
Default
Setting
Setting Required
Discharge Air Control Setup for Heating
2
1
110
Select 80−140F
100
Select 80−140F
Select 5−20F
(Recommend
5F
default)
Select 0−900Sec.
180 Sec.
(Recommend
default)
Discharge Air Control Setup for Heating
Default
Setting Required
Setting
Select 0−600Sec.
120 Sec.
(Recommend
default)
Select 2−20F
(Recommend
2F
default)
Select 5−20F. (Rec-
10F
ommend default)
70F
Select 50−80F.
10F
Select 1−30F.
0F
Select 0−30F.
(disabled)
40F
Select −31−60F.
20F
Select 1−60F.
0F (dis-
Select 0−30F.
abled)
Description
Option 1 sets control to operate discharge air control heating when W1 is
energized.
Discharge Air Control Heating setpoint during occupied period.
Discharge Air Control Heating setpoint during unoccupied period.
Discharge Air Control Heating deadband.
Discharge Air Control Heating and Fresh Air Heating stage−up time delay.
Description
Discharge Air Control Heating and Fresh Air Heating stage−down time delay.
Discharge Air Control Heating stage differential
Discharge Air Control Heating reset limit. This limits the total DACH reset
allowed.
Discharge Air Control Heating return air heating reset setpoint.
Discharge Air Control Heating return air heating reset proportional band.
Discharge Air Control Heating return reset adjustment band. 0 value disables
return air heating reset.
Discharge Air Control Heating outdoor temperature reset setpoint.
Discharge Air Control Heating temperature reset proportional band.
Discharge Air Control Heating outdoor temperature reset adjustment band. 0
disables outdoor temperature heating reset
Page 52