Demand Control Ventilation; General - Lennox Prodigy M2 Application Manual

Hide thumbs Also See for Prodigy M2:
Table of Contents

Advertisement

Step 7. Enthalpy Sensor Operation (A7 and A62)
A
Connect a DC ammeter as shown in figure 12 to measure current of A7 or A62.
DISCONNECT J/P104
Damper Travel: % of Maximum Open
PLACE JUMPER WIRE HERE
DC AMMETER
Measure A7 Current in Series
B
The reading will be between 4 and 20 ma. depending on outdoor temperature and humidity. Refer to figure 13 to
approximate reading.
Figure 13. Enthalpy Sensor Output Current Honeywell C7400
C
If the meter reads zero, check sensor wiring harness for continuity and/or check polarity of sensor wiring.

7.12. Demand Control Ventilation

7.12.1. General

A field−provided and installed indoor air quality sensor can be used with the modulating economizer to control CO
the conditioned space. The CO
rises (indicating the occupancy of a room has increased), economizer dampers modulate open − regardless of outdoor air
enthalpy. Likewise, as the CO
closed.
Standard economizer installations have a minimum fresh air ventilation requirement based on maximum room occupancy.
With standard economizer use, the amount of air required for maximum room occupancy is heated or cooled with each
heating or cooling cycle. IAQ economizer installations use the maximum amount of required ventilation air only with maxi-
mum room occupancy; less outdoor air needs to be heated or cooled when fewer people are in the conditioned space.
If the economizer is operating in the free cooling mode and the IAQ control requires the damper to open further, the IAQ
demand will override the free cooling demand. A flashing OAS LED (see figure 8) indicates an IAQ override condition.
The IAQ function is not energized during the unoccupied or night time period.
NOTE − The IAQ sensor may also be used with systems containing a motorized outdoor air damper.
READ
CURRENT
HERE
+
Figure 12. Measure A7 and A62 Current in Series
100
90
80
70
60
50
40
30
20
10
40°F
50°F
level in a space is an indicator of the number of people occupying a room. As the CO
2
level falls (indicating the occupancy has decreased), economizer dampers modulate further
2
DISCONNECT J/P105
PLACE JUMPER WIRE HERE
Measure A62 Current in Series
60°F
70°F
80°F
90°F
Page 29
7.
READ
CURRENT
HERE
+
DC AMMETER
100°F
PRODIGYT M2 UNIT CONTROLLER
Economizer
levels in
2
level