Lennox Prodigy M2 Application Manual page 72

Hide thumbs Also See for Prodigy M2:
Table of Contents

Advertisement

Control Parameter
No.
Name
Min.
0
3.12
StgDn_Timer
0
MGV_Control_
3.13
0
Mode
MGV_startup_
2
3.14
Phase2_delay
4
60
3.15
MGV_Max
60
0
3.16
MGV_Min
0
MGV_PID_
0
3.17
ManRS
0
MGV_PID_P_
3.18
0
Constant
MGV_PID_I_
3.19
0
Constant
MGV_PID_D_
3.20
0
Constant
506457−01 05/10
Control Value
Default
Max.
Block 3 Gas Heating Parameters (continued)
0
225
0
3600
0
6
8
150
16
300
80
100
80
100
20
100
20
100
50
100
50
100
40
127
0
127
0
127
17.
Electronic Configure To Order (ECTO) Control Parameters
Units
Description
Counts
Time delay before a lower stage turns off following a higher stage
F: Sec
termination. Used in zone sensor applications.
Modulating Gas Valve Mode
0−
A133 (GP1) not installed.
1−
A133 (GP1 w/DIP set to MGV) installed, but no MGV. Data log-
ging only.
2−
Two−stage fire; min. or 100% (with or without low−fire FAH)
3−
2 + modulating FAH
4−
Direct mode.
Option
AI1 (A133_P194−11) scaled to 0−100% and output on AO1.
AI2 (A133_P194_12)scaled to 0−100% and output on AO2.
5−
DACH control; min. to maximum (with or without lo−fire FAH)
6−
5 + modulating FAH
Lighting sequence is followed for all modes; 2−6. See ECTO 3.14 and
3.15.
Modulating gas startup delay. At startup, run burners on low stage
main gas valves(s) with MGV(s) at 100% for ECTO 3.05 seconds.
Counts
Increase burners to high stage of main gas valve(s) with MGV(s)
A: Sec.
opened to ECTO 3.15 for ECTO 3.14 seconds. Begin PID or staged
control of MGV(s).
Counts
Modulating gas valve maximum.
P:%
Counts
Modulating gas valve minimum.
P:%
Counts
Modulating gas valve PID manual reset value.
P:%
Counts
Modulating gas valve PID proportional constant.
Counts
Modulating gas valve PID integral constant.
Counts
Modulating gas valve PID derivative constant.
Page 72
table continued on next page