Zone Sensor Mode, Single Zone Cav Units; L Connection Network, Cav Bypass Zoning Units - Lennox Prodigy M2 Application Manual

Hide thumbs Also See for Prodigy M2:
Table of Contents

Advertisement

9.2.2.

Zone Sensor mode, Single Zone CAV Units

ECTO 6.01 option 1,2,3
This configuration is used with an L Connection Zone sensor for single zone constant air volume application. Blower cycles
with demand unless ECTO 6.17 is set to 1. In that case the blower will operate continuously during occupied periods and
cycles with demands during unoccupied periods. All delays as described in Local Tstat Mode still apply.
9.2.3.
Local Thermostat Mode, CAV Bypass Zoning Units
ECTO 6.01 option 0 (default) or 12
ECTO 0.01 option 1
This configuration is used for 3
are four different setpoints: one for cooling, one for ventilation, one for operation during smoke alarm modes, and one for
heating. Blower operates when the G demand is energized. The blower also operates anytime a heat limit trips. All delays as
described in Local Tstat Mode still apply. The M2 controls duct static pressure by reading the duct pressure and varying the
bypass damper position between minimum and maximum positions.
The mininimum/maximum damper positions and static pressure setpoints are listed as follows:
Operation
Operation
Default
Cooling
20%
Ventilation
20%
Smoke Alarm Modes
20%
Heating
20%
9.2.4.

L Connection Network, CAV Bypass Zoning Units

ECTO 6.01 option 4,5,6,7;
ECTO 0.01 option 1
This configuration is used for L Connection Zoning that utilizes a blower bypass damper for controlling duct static. There are
four different setpoints: one for cooling, one for ventilation, one for operation during smoke alarm modes, and one for heat-
ing. Network commands energize the blower. Blower will cycle with demand unless ECTO 6.17 is set to 1. In that case, the
blower will operate continuously during occupied periods and will cycle during unoccupied periods. Blower also operates
anytime a heat limit trips. All delays as described in Local Tstat Mode still apply.
The M2 controls duct static pressure by reading the duct pressure and varying the bypass damper position between and
minimum and maximum positions. The min/max damper positions and static pressure setpoints are listed as follows:
Operation
Operation
Default
Cooling
20%
Ventilation
20%
Smoke Alarm Modes
20%
Heating
20%
9.2.5.
Local Thermostat Mode, VAV units
ECTO 6.01 option 0 (default) or 12;
ECTO 0.01 option 63
This configuration is used for 3
a minimum and maximum speed to maintain duct static pressure setpoints. There are four different setpoints: one for cool-
ing, one for ventilation, one for operation during smoke alarm modes, and one for heating. The blower is enabled by a G
demand. The M2 controls the duct static pressure by reading the duct pressure and varying the blower speed on units with
VFDs.
The minimum/maximum speed and static pressure setpoints are listed as follows:
Operation
Operation
Default
Cooling
50%
Ventilation
50%
Smoke Alarm Modes
50%
Heating
50%
rd
party zoning systems that utilize a blower bypass damper for controlling duct static. There
Minimum Position
ECTO
0.17
0.17
0.17
0.18
Minimum Position
ECTO
0.17
0.17
0.17
0.18
rd
party VAV zoning systems. Blower speed is controlled by the factory installed VFD between
Minimum Speed
ECTO
0.06
0.06
0.06
0.07
Maximum Position
Default
ECTO
100%
0.19
100%
0.19
100%
0.19
100%
0.19
Maximum Position
Default
ECTO
100%
0.19
100%
0.19
100%
0.19
100%
0.19
Maximum Speed
Default
ECTO
100%
0.08
100%
0.08
100%
0.08
100%
0.08
Page 37
9.
Supply Air Delivery
Duct Static SP
Default
ECTO
1.00"w.c.
0.16
1.00"w.c.
0.14
1.00"w.c.
0.13
1.00"w.c.
0.15
Duct Static SP
Default
ECTO
1.00"w.c.
0.16
1.00"w.c.
0.14
1.00"w.c.
0.13
1.00"w.c.
0.15
Duct Static SP
Default
ECTO
1.00"w.c.
0.05
1.00"w.c.
0.03
1.00"w.c.
0.02
1.00"w.c.
0.04
PRODIGYT M2 UNIT CONTROLLER