Lennox Prodigy M2 Application Manual page 77

Hide thumbs Also See for Prodigy M2:
Table of Contents

Advertisement

Control Parameter
No.
Name
Min.
Min_Damper_
0
5.24
Position
0
Zone_Sensor_
15
5.25
StartUp_ Delay
2
IAQ_Input_
5.26
0
Source/Mode
Net_Sig_
5.27
0
Sources
6.01
System_Mode
0
OCP_HT_
20
6.02
BkUp_ SP
95
UnOcp_HT_
20
6.03
BkUp_SP
95
Ocp_CL_
20
6.04
BkUp_ SP
95
UnOcp_CL_
20
6.05
BkUp_SP
95
Override_
0
6.06
Timer
0
4
6.07
HT_Stg_DB
1
Control Value
Default
Max.
Units
Block 5 Miscellaneous Parameters (continued)
101
100
Counts
101
100
15
225
Counts
2
30
C:Min.
0
5
Option
0
15
Option
Block 6 System 1 Parameters
0
12
Option
120
240
Counts
70
40
Z:DegF
160
240
Counts
60
40
Z:DegF
100
240
Counts
75
40
Z:DegF
60
240
Counts
85
40
Z:DegF
28
225
Counts
3584
28800
E: Sec
4
15
Counts
1
3.75
W:DegF
17.
Electronic Configure To Order (ECTO) Control Parameters
Description
Minimum fresh air damper position during occupied operation. Value
of 101 allows adjustment by potentiometer on economizer board A55
only. When in global mode with A55 EM1 versions 2.01 and earlier,
P: %
only 101 should be used.
Start−up demand delay. Holds off all unit operation zone sensor and
CAVB applications. Hold off FAH−Reheat, FAC, FAH options and all
GP outputs.
May be used to stagger unit start−ups. Does NOT delay demands in
thermostat mode.
IAQ input source and mode (0−3 operate only when blower is on).
0− DCV System IAQ. Either P298−3 or network IAQ.
1− DCV System IAQ. Either P298−3 or network IAQ with no OAT limits.
2− Outdoor Air Control Sensor A24 (A133_P194−6) (TB22−6).
3− Outdoor Air Control Sensor A24 (A133_P194−6) (TB22−6) with no
OAT limits.
4− DCV System IAQ. Either P298−3 or network IAQ with blower on/auto
operation.
5− DCV System IAQ. Either P298−3 or network IAQ with blower on/auto
operation with no OAT limits.
Network Signal Sources
Weight
Description
1−
IAQ (A63)
2−
Zone Temp. (A2)
4−
Outdoor Enthalpy (A7)
8−
Indoor RH (A91)
Option is sum of the weights for all input signals that are provided
remotely over the network.
Note: When network sensor is used the physical analog input is ig-
nored. Loss of sensor alarms will not occur unless network commu-
nication is lost for 5 minutes, or has not been established within 5
minutes after reset.
System mode of operation.
Control System
Value
Mode
0−
Local Thermostat
1−
Zone Sensor
2−
Zone Sensor
3−
Zone Sensor
4−
Remote Demand
5−
Remote Demand
6−
Remote Demand
7−
Remote Demand
Backup occupied heating setpoint. Used if the communications link is
lost for 5 minutes between the M2 and NCP. Used only with zone
sensor applications.
Setpoint temperature must be < or = (6.04 − 6.15).
Backup unoccupied heating setpoint. Used if the communications link
is lost for 5 minutes between the M2 and NCP. Used only in zone
sensor applications. Setpoint temperature must be < or = (6.05 −
6.15).
Backup occupied cooling setpoint. Used if the communications link is
lost for 5 minutes between the M2 and NCP. Used only in zone sen-
sor applications. Setpoint temperature must be > or = (6.02 + 6.15).
Backup unoccupied cooling setpoint. Used if the communications link
is lost for 5 minutes between the M2 and NCP. Used only in zone
sensor applications. Setpoint temperature must be > or = (6.03 +
6.15).
After hours override timer. Only used on zone sensor applications
without a Network Control Panel (NCP).
Heating deadband. Used only with M2 zone sensor applications.
Deadband must be < or = 6.15 − 6.08.
Page 77
Backup
Mode
None
None
Local Thermostat
Return Air Sensor
None
Local Thermostat
Return Air Sensor
Zone Sensor
table continued on next page
PRODIGYT M2 UNIT CONTROLLER