Lennox Prodigy M2 Application Manual page 75

Hide thumbs Also See for Prodigy M2:
Table of Contents

Advertisement

Control Parameter
No.
Name
Min.
Reheat_
4.24
0
Control
0
4.25
Reheat_SP
0
Reheat_
1
4.26
RH_DB
1
81
4.27
FC_LAL_SP
80
5.01
SMK_Alarm
0
Error_Timed_
8
5.02
Off_Delay
64
5.03
Display_Temp
0
Control Value
Default
Max.
Units
Block 4 Cooling Parameters (continued)
0
7
Option
60
100
Counts
60
100
P:%RH
3
10
Counts
3
10
P:%RH
120
136
Counts
55
45
Y:DegF
Block 5 Miscellaneous Parameters
0
7
Option
38
225
Counts
304
1800
C:Sec.
0
1
Option
17.
Electronic Configure To Order (ECTO) Control Parameters
Description
Reheat Control Mode
0−
No reheat.
1−
Supermarket reheat using De−Humidistat (Tstat mode only)
2−
Supermarket reheat using RH sensor.
3−
Humiditrol reheat. Conditions: Blower must be energized, Must
be occupied, At least one previous cooling demand.
4−
RH measurement / display. No Supermarket or Humiditrol re-
heat.
5−
Humiditrol reheat. Conditions: At least one previous cooling
demand.
6−
Humiditrol reheat. Conditions: Blower must be energized, Must
be occupied.
7−
Humiditrol reheat. Conditions: None
Percent relative humidity where supermarket or Humiditrol reheat
demand is energized. Used of Reheat option 2,3,5,6,or 7. Reheat is
de−energized at setpoint – deadband (ECTO 4.26).
If value = 100, Humiditrol reheat is controlled by
the digital input A55_P299−8 Digital Input 4 only.
Energized input signal calls for reheat demand.
L Connection Network RH setpoint will
override this setpoint. (Such as from NCP).
Reheat RH deadband.
Used of Reheat option 2,3,5,6,or 7. Reheat is on when RH>=ECTO
4.25 and off when RH< ECTO 4.25 – ECTO 4.26.
Free−cooling Low Ambient Lockout Setpoint.
When outdoor air is suitable for free cooling and an economizer is
present, the compressor will not run when ambient is below this val-
ue. A value of 207 (0 degF) disables this feature. A value of 81 (80
degF) locks out compressor operation whenever OAS, regardless of
OAT.
Smoke alarm control options.
0−
Unit off.
1−
Blower on, exhaust fan off, OD air damper open (positive pres-
sure)
2−
Blower on, exhaust fan on, OD air damper closed (negative
pressure). On VAV units, exhaust fan will run at speed set in
ECTO 8.19 with blower).
3−
Blower on, exhaust fan on, OD air damper open (purge). On
VAV units, exhaust fan will run at speed set in ECTO 8.19.
4−
Blower off, exhaust fan on, OD air damper closed (negative
pressure). On VAV units, exhaust fan will run at speed set in
ECTO 8.19.
5−
Blower on, exhaust fan on, OD air damper closed (negative
pressure). On VAV units, exhaust fan will run to maintain pres-
sure setpoint set in ECTO 8.19 with blower).
6−
Blower on, exhaust fan on, OD air damper open (purge). On
VAV units, exhaust fan will run to maintain pressure setpoint set
in ECTO 8.19.
7−
Blower off, exhaust fan on, OD air damper closed (negative
pressure). On VAV units, exhaust fan will run to maintain pres-
sure setpoint set in ECTO 8.19.
Off time delay if a no−run" error occurs. Off delay for error codes 5,
10, 11, 20, 21, 44, 45, 83, 86, 87 and 114.
Degrees Celsius option for A55 Display
0: Displays degrees Fahrenheit
1: Displays degrees Celsius
Page 75
OFF
4.25−4.26
table continued on next page
PRODIGYT M2 UNIT CONTROLLER