Control Parameter
No.
Name
Min.
B, C, D, & E BOXES
DO_Mode_
0.23
A133_(VAV
0
mode)
0
0
DO_SP_
0
0.24
A133_
0
(VAV mode)
132
−.05
0
2
0
16
DO_DB_A133_
2
0.25
1
(VAV mode)
64
0.01
0
Supply_Static-
30
0.26
Sensor_Low_
30
Alarm_Check
Control Value
Default
Max.
Block 0 VAV, CAVB, & MSAV Parameters (continued)
0
127
127
255
5.0
10.0
996
2000
100
100
51
−31
0
0.5
2.5
5.0
13
255
.50
10.0
102
2000
13
100
8
162
416
8160
0.05
1.0
.25
5.0
40
101
40
101
17.
Electronic Configure To Order (ECTO) Control Parameters
Units
Description
A133 (w/DIP set to VAV) Digital Out Mode = X + 32*Y + 16*Z
Input source= X:
0−
None. Output enables exhaust fan stage 2.
1−
Compressor 1 duty cycle. (Compressor crankcase heater func-
tion.) On when OAT <= ECTO 0.24 and >= ECTO 0.25 seconds
have passed with compressor 1 off. Off when OAT > ECTO 0.24
+ 3 deg F (fixed deadband) or < ECTO 0.25 sec have passed
with compressor 1 off.
2−
On when occupied.
3−
On when blower on.
4−
On when heating demand.
5−
On when cooling demand.
6.−
On when heating or cooling demand.
7−
System RH (A55_P298_5 RH)
8−
System IAQ. (A55_P298_3 IAQ)
9−
System OAT (A55_P267_1/2 OAT)
10− AI1. (A133_P194−6).
11− AI2. (A133_P194−7).
12− AI3. (A133_P194−8).
13− AI4. (A133_P194−9).
14− AO1. (A133_P194−11).
15
AO2. (A133_P194−12).
Option
Algorithm Y for input sources 7−15:
0−
Hysteresis loop
On when input >= ECTO 0.24
Off when input < ECTO 0.24−ECTO 0.25
1−
Window
On when input is in range; >= ECTO 0.24
and <= ECTO 0.24 + ECTO 0.25
(Fixed 3−count hysteresis loop on rising
and falling edges of window.)
2−
Delayed−on.
On when input is >= ECTO 0.24
for >= ECTO 0.25 seconds.
Off when input is < ECTO 0.24 − 3.
(Fixed 3−count hysteresis loop on edge.)
3−
Delayed−off.
On when input is >= ECTO 0.24.
Off when input is < ECTO 0.24 − 3
for >= ECTO 0.25 seconds.
(Fixed 3−count hysteresis loop on edge.)
Inversion Z:
0 − Output not inverted.
1 − Output inverted.
Counts
R:Volts
I:ppm
P:%
A133 (w/DIP set to VAV) digital output mode setpoint
Y:DegF
M:"w.c.
N:"w.c.
Counts
R:Volts
I:ppm
P:%
A133 (w/DIP set to VAV) digital output mode deadband or delay.
O:DegF
D:Sec.
L:"w.c.
N:"w.c.
Supply Static Pressure Sensor (A30) connected at (A133_P195_6)
Count
(TB18_6) alarm threshold. Blower percent speed before checking
sensor after a 20 second delay. A value of 101 disables the low
P:%
threshold or open" alarm trap.
Page 69
ON
OFF
0.24
0.24−0.25
O
N
OFF
OFF
0.24
0.24+0.25
OFF
DELAY
0.24
DELAY
0.25
OFF
0.24
Graphs indicate output not
inverted. See figure 33.
table continued on next page
PRODIGYT M2 UNIT CONTROLLER