Control Parameter
No.
Name
Min.
Block 9 Optional A133 Board in GP Mode (DIP switch set to GP) Parameters (continued)
DO_Control_
9.23
0
Mode
0
0
16
9.24
DO_SP
0
132
−0.5
0
2
0
0
2
9.25
DO_DB
1
64
0.01
0
Control Value
Default
Max.
Units
0
127
Option
127
255
Counts
5.0
10.0
R:Volts
996
2000
100
100
51
−31
Y:DegF
0
0.5
M:"w.c.
2.5
5.0
N:"w.c.
13
255
Counts
.50
10.0
R:Volts
102
2000
13
100
8
162
O:DegF
416
8160
D:Sec.
.05
1.0
L:"w.c.
.25
5.0
N:"w.c.
17.
Electronic Configure To Order (ECTO) Control Parameters
Description
GP1 Digital Out Control Mode = X + 32*Y + 16*Z
Input source = X:
0−
None.
1−
Compressor 1 duty cycle. (Compressor crankcase heater func-
tion.) On when OAT <= ECTO 9.24 and >= ECTO 9.25 seconds
have passed with compressor 1 off. Off when OAT > ECTO 9.24
+ 3 deg F (fixed deadband) or < ECTO 9.25 seconds have
passed with compressor 1 off.
2−
On when occupied.
3−
On when blower on,
4−
On when heating demand.
5−
On when cooling demand.
6−
On when heating or cooling demand.
7−
System RH (A55_P298_5 RH)
8−
System IAQ. (A55_P298_3 IAQ)
9−
System OAT (A55_P267_1/2 OAT)
10− On base on AI1. (A133_P194−6)
11− On based on AI2. (A133_P194−7)
12− On based on AI3. (A133_P194−8)
13− On based on AI4. (A133_P194−9)
14− On based on AO1. (A133_P194−11)
15− On based on AO2. (A133_P194−12)
Algorithm Y for input sources 7−15:
0−
Hysteresis loop
On when input >= ECTO 9.24
Off when input < ECTO 9.24−ECTO 9.25
1−
Window
On when input is in range; >= ECTO 9.24
and <= ECTO 9.24 + ECTO 9.25
(Fixed 3−count hysteresis loop on rising
and falling edges of window.)
2−
Delayed−on.
On when input is >= ECTO 9.24
for >= ECTO 9.25 seconds.
Off when input is < ECTO 9.24 − 3.
(Fixed 3−count hysteresis loop on edge.)
3−
Delayed−off.
On when input is >= ECTO 9.24.
Off when input is < ECTO 9.24 − 3
for >= ECTO 9.25 seconds.
(Fixed 3−count hysteresis loop on edge.)
Inversion Z:
0 − Output not inverted.
1 − Output inverted.
I:ppm
P: %
Digital output control mode setpoint
I:ppm
P: %
Digital output control mode deadband or delay.
Page 85
ON
OFF
9.24−9.25 9.24
ON
OFF
OFF
9.24
9.24 + 9.25
ON
OFF
Delay
9.2
9.25
4
ON
OFF
9.24
Graphs indicate output
not inverted. see figure
33.
PRODIGYT M2 UNIT CONTROLLER