12.4. Analog Output Objects
Optional Properties Supported:
Optional Writable Properties:
Analog output object's Overridden status flag set if the equivalent setpoint in the M2 is written to by an Sbus device.
Object ID
Object Name
101
Application Mode Control
102
Outdoor Air Min Pos Control
103
Occupancy Override Control
104
Occupancy Scheduler Control
107
Occupancy Sensor Input
108
Space Dehumidification Setpoint
109
Temperature Setpoint (abs)
110
Temperature Setpoint Offset
113
Space Temperature Input
114
Emergency Override Control
115
Compressor Enable Control
117
Primary Heat Enable Control
119
Auxiliary Heat Enable Control
123
Duct Static Setpoint
124
Building Static Setpoint
125
Discharge Air Cooling Setpoint
126
Discharge Air Heating Setpoint
127
Supply Fan Capacity Input
128
Exhaust Fan Capacity Input
129
Set Economizer Outdoor Air Suitable
12.5. Analog Value Objects
Optional Properties Supported:
Optional Writable Properties:
Object ID
Object Name
1
Baud Rate Setting
130
Heating Occupied Setpoint
131
Cooling Occupied Setpoint
132
Heating Unoccupied Setpoint
133
Cooling Unoccupied Setpoint
12.6. Analog Input Objects
Optional Properties Supported:
Optional Writable Properties:
506457−01 05/10
Min_Pres_Value, Max_Pres_Value
Out_Of_Service
Table 34. Analog Output Objects List
Units
Min. Value
None
Percent
None
None
None
Percent
Deg. F
36.25
Deg. F
Deg. F
36.25
None
None
None
None
In. of water
In. of water
Deg. F
Deg. F
Percent
Percent
None
* see Application Details section for limitations on data ranges.
None
Present_Value
Table 35. Analog Value Objects List
Min.
Max.
Units
Value
Value
None
9600
76800
Deg. F
40
95
Deg. F
40
95
Deg. F
40
95
Deg. F
40
95
None
Out_Of_Service (AI239 − AI252, AI274 − AI285 only)
Page 56
Max. Value
0
255
0,1,3,6,9,208,209,216,217,218,224-254,255*
0
255
0
255
0
255
0
255
0
100
100
−32
31.75
100
0
255
0
255
0
255
0
255
0
5
−0.5
0.5
40
80
80
140
33
255
33
255
0
255
Valid Values
within Range
9600, 19200, 38400, 76800
all
all
all
all
12.
BACnet®
Valid Values within Range
all
all
all
all
all
all
all
all
all
all
all
all
all
all
−9,40-80*
−9,80-140*
all*
all
all
Note
38400 default
For occupied and unoccupied set-
p
p
points considered separately, the
points considered separately the
heating setpoint must be lower than
heating setpoint must be lower than
the cooling setpoint by at least the
auto−changeover deadband value set
auto−changeover deadband value set
in M2 ECTO 6.15 (default 3 degF).